FlexiSmoke™ 

WSC 520 / 540 / 560 

Utilization examples 

 

 

 
 

 

 

 

 

 

 

 

Summary of Contents for FlexiSmoke WSC 520

Page 1: ...info windowmaster de CH 41 0 62 289 22 22 info windowmaster ch www windowmaster com Other markets 45 4567 0300 info windowmaster com FlexiSmoke Utilization examples 1507 EN WindowMaster 2013 2015 Win...

Page 2: ...dware configuration diagram 38 3 3 Configuration 39 3 3 1 Configuration of local output 39 3 3 2 Configuration of local input 40 4 Example D 1 WSC 540 5 motor groups in 1 smoke zone rain wind directio...

Page 3: ...the break glass units and 2 are connected to input terminals on the WSA 5IO module The smoke zone fire alarm can be triggered from 2 break glass units and from a signal from the BMS system Smoke dete...

Page 4: ...4 47 Figure 2 overview of the smoke zone motor groups and motor lines Figure 3 overview of the smoke panel and how the different components are connected it...

Page 5: ...el rights Warning icon appears since motors break glass units and comfort keypads have been connected but the panel is not yet configured Press the key button Enter the PIN code 4321 for level 3 Level...

Page 6: ...art the configuration 1 3 2 Configuration of motor lines Press Motor line Select the motor line to configure In this example we select the S5 X1 Slot 5 motor output 1 motor line Set the Motor Configur...

Page 7: ...m with check mark Set the stroke time the time to open of the actuators connected on the motor line Enter the stroke time in seconds In this set up the stroke time is set to 50 seconds Confirm with ch...

Page 8: ...p 1 Confirm with check mark Press the arrow down to get further options If required change the Retry during alarm parameter to Yes Selecting yes will prompt the motor line to repeatedly attempt to rea...

Page 9: ...o configure all motor lines Note Motor lines not in use must be configured with Motor configuration None to clear the warning icons 1 3 3 Configuration of motor Groups Press Motor group Select the mot...

Page 10: ...In this set up smoke zone 1 is selected Confirm with check mark Continue to associate all 4 motor groups with smoke zone 1 Press Return to return to the main menu 1 3 4 Configuration of break glass u...

Page 11: ...to all the break glass units and specifies weather all break glass units are connected in a bus topology or not In this setup the bus topology is not a ring topology Select No Confirm with check mark...

Page 12: ...The unique serial number of the selected break glass unit is shown Associate break glass unit 1 with a smoke zone Press 1 to associate the break glass unit with smoke zone 1 Confirm with check mark S...

Page 13: ...to operate all the motor groups associated with this smoke zone from this comfort input Confirm with check mark Select the motor groups to operate with this comfort input In this set up we associate m...

Page 14: ...In this set up there is only one smoke zone In this set up the smoke detectors and break glass units are in the same smoke zone Confirm with checkmark If you would like to identify the physical positi...

Page 15: ...n of smoke zones To configure the smoke zone press smoke zone Select the smoke zone to be configured The break glass unit has a buzzer which sounds in case of triggering or error Buzzer active during...

Page 16: ...the smoke zone alarm will be triggered whenever the unit detects en error Note If you have to choose Yes do it after you have finished configuring the unit and have resolved all errors indicated by i...

Page 17: ...1 but anyone of the local inputs on the Input output module WSA 5IO power supply module WSA 5PS or the standard module WSA 5SM can be used Set the control smoke zones Select the control smoke zone whi...

Page 18: ...different lines see the FlexiSmoke WSC 520 540 560 installation instruction section 13 5 Smoke zone In this set up Line B is selected Other priorities can be selected e g Line A if required Confirm w...

Page 19: ...ith which the comfort input S3 X2 1 is to be connected with In this set up select motor group 2 Confirm with check mark Press Function in controlled motor groups to select the function that will be ap...

Page 20: ...generate a Stop command by a short activation of the Input Press arrow down for further options Press short output function to select the function that will be applied to all motor lines in the motor...

Page 21: ...mands for motor group 2 Repeat the steps as just performed for S3 X2 1 for the other inputs Press Function in controlled motor groups to select the function that will be applied to all motor lines in...

Page 22: ...ve mentioned automatic mode If no function is being selected activating the input will only apply the function selected under Function in controlled motor groups independently of how long the input is...

Page 23: ...23 47 The Smoke panel is now configured according the above described specification and is ready for operation...

Page 24: ...The smoke zone fire alarm can be triggered from 2 break glass units with a smoke detector connected to each as well as from the BMS system Set up overview 1 Smoke zone 4 motor groups with 16 MotorLin...

Page 25: ...nnected it 2 3 Configuration See example A for login settings as well as configuration of the motor groups and the local input receiving the alarm signal from the BMS 2 3 1 Configuration of motor line...

Page 26: ...o error is detected FlexiSmoke will set the value of the parameter to the number of the expected motors If a discrepancy is detected between the expected and the found number of motors FlexiSmoke will...

Page 27: ...check mark To e g alter the speed press arrow down Alter the manual or automatic speed as required The faster motors are running the louder they sound WMa recommends running motors in Auto with 30 sp...

Page 28: ...Manual command auto off period if required This is the manual override time in which the FlexiSmoke ignores auto commands to the motor line In this set up we choose to set the manual command auto off...

Page 29: ...gets the motors to establish their Zero closed position Setting the parameter to 0 ensures that the motors will never change their Zero position and always report an error if they receive the command...

Page 30: ...All This configuration applies to all the break glass units and specifies weather all break glass units are connected in a bus topology or not In this setting we select No for the CAN bus technology...

Page 31: ...ass unit with smoke zone 1 Confirm with check mark Set the Use comfort inputs in SZ In this set up we choose not to associate the comfort input with the smoke zone We do not wish to operate all the mo...

Page 32: ...to Same smoke zone It means that both the smoke detector and the red key in the break glass unit are triggering the alarm in the same smoke zone In this set up there is only one smoke zone In this se...

Page 33: ...33 47 Configure break glass unit 2 with the same values as break glass unit 1 2 3 3 Configuration of smoke zone Press Smoke zone Select smoke zone 1 Press arrow down for further options...

Page 34: ...s must open 100 in Alarm but there are cases where window must be closed 0 when the smoke detectors trigger the alarm Reduce the Line B smoke detector smoke opening pos from 100 to 0 by pressing eithe...

Page 35: ...ecific topics are covered here 1 Import the ETS4 application of the FlexiSmoke WSA 5MC KNX knxprod as well as the ETS application of the push button of your choice into your ETS The ABB US U2 2 Univer...

Page 36: ...36 47 4 Set the parameters of the Push buttons corresponding to the following The device must be able to send values when keypads are pressed An Open Command 127 a Close command 129 a Stop Command 0...

Page 37: ...ect with the relevant push button device communication objects Depending on the push button device you use the populated Group Addresses for the 4 motor groups should look similar to this 6 Program th...

Page 38: ...e third motor group All 3 motor groups are associated with the same smoke zone and each motor group is controlled for comfort by a keypad The smoke zone fire alarm can be triggered from a break glass...

Page 39: ...al from the BMS and the Smoke Zone with its Break Glass Unit 3 3 1 Configuration of local output 3 3 1 1 Configuration of error signal to the BMS To start the configuration of the local output signal...

Page 40: ...a Safety signal to MotorGroup 3 the roof windows In the View all details Motor group 3 you can set the Comfort safety maximum position in Default position is 0 3 3 2 2 Configuration of smoke sensors...

Page 41: ...ciated with the fifth motor group The motor lines running the fa ade windows and the internal dampers are connected to section 1 of the WSC 540 panel The motor lines running the roof windows are conne...

Page 42: ...t the CAN bus mode Independent buses In section 2 Press Configuration arrow down CAN Set the MC ID 2 Set the CAN bus mode Independent buses 4 2 2 Configuration of Smoke area 1 In section 1 associate a...

Page 43: ...rs All weather station sensors are connected to the WSC 540 section 2 in this example 4 2 4 1 Configuration of the wind direction and wind speed sensors Consult paragraph 10 2 in the WSC 5xx installat...

Page 44: ...er smoke panel WSC2 which is located in the other side of the building We are using two pcs WSC 540 0SS0 0SS0 E3 to implement the required system Since the windows in the atrium are connected to two d...

Page 45: ...xamples In this example we will only go through what needs to be done in order to meet the system requirements and explain the reasons for the selected configuration 5 3 1 Configuration of the CAN bus...

Page 46: ...area 1 We call these zones virtual because they do not have any hardware associated with them They are only needed to be able to establish the Controlling Controlled relation between the fa ade smoke...

Page 47: ...47 47 6 List of abbreviations BGU Break glass unit BMS Building management system MG Motor group SZ Smoke zone ML Motor line...