Winco WL18000VE Installation And Operator'S Manual Download Page 8

3110-00

8

60706-39

4.  Rotate the key switch (Ref “C”) briefly to the 

 

START position.  The starter life is improved by  

 

using shorter starting cycles with time to cool off  

 

between cranking cycles.  Do not operate the  

 

starter more than 15 seconds during each  

 

minute.  Repeat if necessary.

5.  When the engine starts, open the choke  

 

gradually.

6.  The engine should promptly come up to  

 

operating speed.

CAUTION:  EQUIPMENT DAMAGE

    

Never permit the choke to remain on after the 

engine has run for a short time.  It is not necessary to 

choke the engine when it is warm.  Avoid over-chok-

ing.

STARTING HINTS

1.  

Cold weather

a.  Use the proper oil for the temperature expected.  

b.  Use fresh winter grade fuel.  Winter grade 

 

     gasoline is blended to improve starting.  Do not    

     use summer grade gasoline.

.  

Hot weather

a.  Use the proper oil for the temperature expected.

b.  Use only summer blended gasoline.  Using gaso- 

     line left over from winter may cause the unit to  

     vapor lock. 

STOPPING AND STORAGE

1.  Move the on/off switch to the “OFF” position.

 

2.  Before extended storage (over 30 days) certain 

precautions must be taken to ensure the fuel doesn’t 

deteriorate and clog the fuel system.   

Note: 

 The use of a fuel additive, such as Briggs & 

Stratton Advanced Fuel Treatment & Stabilizer or an 

equivalent will minimize the formation of gum depos-

its during storage.  The additive may be added to 

gasoline in the engines fuel tank or to gasoline in a 

storage container.

a.  Add the fuel stabilizer to the fuel in the tank and  

  run the unit for  minutes to circulate the  

  stabilizer throughout the fuel system.  

b.  If you choose to remove the remaining fuel from  

  the fuel tank, it must be drained into an approved  

  container.

c.  Start the engine and allow it to run until all the   

  fuel in the carburetor and the fuel lines has been  

  used up and the engine stops. 

Note: 

 Running the engine to use up the fuel in the 

lines and carburetor will still leave a small amount of 

fuel in the carburetor.  It is best for extended storage 

to treat the fuel before draining.

d.  While the engine is warm, drain the oil and refill  

  with fresh oil.

e  Clean dirt and chaff from cylinder, cylinder head  

  fins, blower housing, screen and muffler areas.

f.  Store in a clean and dry area.

OPERATING SPEED

The engine-generator must be run at the correct 

speed in order to produce the proper electrical volt-

age and frequency.

CAUTION:  EQUIPMENT DAMAGE

  The output voltage should be checked to insure 

the generator is working properly prior to connecting 

a load to the generator.  Failure to do so could result 

in damage to equipment plugged into the unit and 

possible injury to the individual.

All engines have a tendency to slow down when a 

load is applied.  When the electrical load is connected 

to the generator, the engine is more heavily loaded, 

and as a result the speed drops slightly.  This slight 

decrease in speed, together with the voltage drop 

within the generator itself, results in a slightly lower 

voltage when the generator is loaded to its full capac-

ity than when running no load.  The slight variation 

in speed also affects the frequency of the output 

current.  This frequency variation has no appreciable 

effect in the operation of motors, lights and most ap-

pliances.  However, electronic equipment and clocks 

will be affected if correct RPM is not maintained.  See 

Load vs. Output chart.

Although individual units and models vary slightly, the 

normal voltage and frequency of the engine-genera-

tor described in this manual are approximately as 

follows, under varying loads:

Summary of Contents for WL18000VE

Page 1: ...INSTALLATION AND OPERATORS MANUAL INDUSTRIAL PORTABLE WL18000VE N WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com ...

Page 2: ...eparation 5 Battery Installation 6 Basic Operation 7 INITIAL START UP 7 Electric Starting 8 Stopping Storage 9 Operating Speed 9 CONNECTING THE LOADS 9 Wiring 10 ENGINE CARE 11 GENERATOR CARE 12 TROUBLESHOOTING 13 CONTROL PANEL WIRING DIAGRAM 14 WARRANTY INFORMATION 15 PROPER USE AND INSTALLATION You must be sure your new engine generator set is Properly serviced before starting Operated in a well...

Page 3: ...dren c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel only in an approved container and only in a well ventilated area f Follow local codes for closeness to combustible material 3 DEADLY EXHAUST GAS Exhaust fumes from any gasoline engine contain carbon mon...

Page 4: ...are third party companies making enclosures for generators that have been properly engineered The use of these third party enclosures is acceptable as long as they have been certified and meet current code DO NOT attempt to operate at 50 cycles These units are designed and governed to operate at 60 cycles only UNIT CAPABILITIES GENERATOR CONNECTIONS WL180000VE 120 volt and 240 volt receptacles are...

Page 5: ...en filling the crankcase the first time use the dipstick ref A to ensure that you do not over fill the crankcase Reference B shows the full oil level mark on the dipstick Oil is added to the engine by removing the oil fill cap ref C and adding oil at this point After filling the crankcase to the proper level be sure you properly tighten the oil fill cap NOTE This engine generator must be on a leve...

Page 6: ...ll not burn properly The use of fuel additives such as STA BIL or an equivalent will minimize the formation of fuel gum deposits If a unit has been out of operation for an extended period of time it is best to drain old fuel from the engine and replace with fresh fuel before attempting to start See the engine manual for special instruction for operating this unit at over 5000 feet BATTERY INSTALLA...

Page 7: ... before operating the generator Failure to properly restrict unit movement will allow the unit to move causing damage to the unit drop cords or loads OIL ALERT SYSTEM This WINCO Industrial generator is equipped stan dard with low oil shutdown systems The Briggs and Stratton engine uses an oil pressure switch system This low oil warning system will automatically stop the engine before the oil level...

Page 8: ...an approved container c Start the engine and allow it to run until all the fuel in the carburetor and the fuel lines has been used up and the engine stops Note Running the engine to use up the fuel in the lines and carburetor will still leave a small amount of fuel in the carburetor It is best for extended storage to treat the fuel before draining d While the engine is warm drain the oil and refil...

Page 9: ...o circu late throughout the engine A short warm up time will permit the engine to work more efficiently when the load is applied and will reduce the wear in the engine extending its life Receptacles have been provided to allow loads to be connected to the generator The loads should be added one at a time If a large motor is being started or multiple motors are being started they should be started ...

Page 10: ...e are two hot leads and a ground wire but no neutral connection in the 3 wire 240 volt receptacle A 4 wire receptacle two hot one ground and one neutral has been provided on the control panel for use in temporary power ap plications requiring 120 240 volt power Consult a licensed electrician for wiring the TemPower plug and connecting it as temporary service To connect these units directly to an u...

Page 11: ...e oil level is maintained Fill to the FULL mark on the dipstick 3 Dual Element Air Filter Clean and or replace foam pre cleaner and air filter annually or every 100 hours Service more often under dusty conditions WARNING EQUIPMENT DAMAGE Never start or run the engine with the air filter re moved a Loosen snaps Ref A and remove cover Ref B VanguardEngines com sengaged osition Figure 4 Operate the e...

Page 12: ...ry out any moisture that has accumulated in the windings If left this moisture can cause corrosion in the winding Frequent operation of the engine generator set will also insure that the set is operating properly should it be needed in an emergency 2 Generator Maintenance Any major genera tor service including the installation or replacement of parts should be performed only by a qualified electri...

Page 13: ...Defective receptacle No residual magnetism in generator Defective stator Defective rotor field Shorted capacitor Shorted diodes on rotor GFCI Receptacle tripped GENERATOR SPECIFICATIONS Generator manufacturer MECC Alte Spa Generator model number S20F 230A Part number 16428 002 Rotor resistance 8 04 Ohms Stator resistance 0 056 Ohms Cap winding resistance 0 41Ohms Capacitors 2 35 mF 1 31 5 mF Capac...

Page 14: ...3110 00 14 60706 239 CONTROL PANEL WIRING DIAGRAM ...

Page 15: ...t WINCO Authorized Service Center or to WINCO Inc at Le Center Minnesota THERE IS NO OTHER EXPRESS WARRANTY To the extent permitted by law any and all warranties including those of merchantability and fitness for a particular purpose are limited to 24 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the dur...

Page 16: ...URER S WARRANTY COVERAGE The evaporative emission control system is warranted for two years If any evaporative emission related parts on your equipment are defective the parts will be repaired or replaced by WINCO OWNER S WARRANTY RESPONSIBILITIES As the generator owner you are responsible for performance of the required maintenance listed in your owner s manuals WINCO recommends that you retain a...