background image

8

REV B

60706-232

OPERATING SPEED

The engine-generator must be run at the correct speed in order to 

produce the proper electrical voltage and frequency.

CAUTION: EQUIPMENT DAMAGE

The output voltage should be checked to ensure the generator is 

working properly prior to connecting a load to the generator. Failure to 

do so could result in damage to equipment plugged into the unit and 

possible injury to the individual.

All engines have a tendency to slow down when a load is applied. 

When the electrical load is connected to the generator, the engine is 

more heavily loaded, and as a result, the speed drops slightly. This 

slight decrease in speed, together with the voltage drop within the 

generator itself, results in a slightly lower voltage when the generator 

is loaded to its full capacity than when running no load. The slight 

variation in speed also affects the frequency of the output current. 

This frequency variation has no appreciable effect in the operation of 

motors, lights, and most appliances. However, electronic equipment 

and clocks will be affected if correct RPM is not maintained. See Load 

vs. Output chart.

Although individual units and models vary slightly, the normal voltage 

and frequency of the engine-generator described in this manual are 

approximately as follows, under varying loads:

LOAD vs. OUTPUT

Generator 

Load

Speed 

(RPM)

Frequency 

(Hz)

Voltage

None

3690

61.5

125V

Half

3600

60.0

120V

Full

3510

58.5

115V

The speed of the engine was carefully adjusted at the factory so that 

the generator produces the proper voltage and frequency. For normal 

usage, the speed setting should not be charged. If the generator is 

being run continuously on a very light load, it is often advisable to lower 

the operating speed slightly. 

Reference “D” in the following image is the speed adjustment for this 

engine.

CAUTION: EQUIPMENT DAMAGE

SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED 

SERVICE TECH. 

Whenever making any speed adjustments, check the 

unit with a voltmeter and a frequency meter or a tachometer and be 

sure the voltage and speed are correct.

Lower voltage may damage both the generator and any load connected 

D

to it. Running the engine at excessively high speeds results in high 

voltage, which may significantly shorten the life of appliances being 

used.

Output voltage should be checked periodically to ensure continued 

proper operation of the generating plant and appliances. If the 

generator is not equipped with a voltmeter, it can be checked with a 

portable meter.

CONNECTING THE LOADS

APPLYING THE LOADS

Allow the engine to warm up for two or three minutes before applying 

any load. This will allow the engine to reach normal operating 

temperature and oil to circulate throughout the engine. A shot warm-up 

time will permit the engine to work more efficiently when the load is 

applied and will reduce the wear in the engine, extending its life.

Receptacles have been provided to allow loads to be connected to the 

generator. The loads should be added one at a time. If a large motor 

is being started: or multiple motors are being started, they should be 

started individually and the largest should be started first.

CAUTION: EQUIPMENT OVERLOAD

Keep the generator load within in the generator and receptacle 

nameplate rating. Overloading may cause damage to the generator 

and/or the loads.

Most electric tools and appliances will have the voltage and amperage 

requirements on their individual nameplates. When in doubt, consult 

the manufacturer or a local electrician. The nameplate amperage rating 

for electric motors can be misleading. See “Starting Electric Motors” in 

the Unit Capabilities. 

These engine-generator sets are inherently self regulating based on 

engine speed. The engine governor will automatically adjust itself to 

the load. No harm to the generator will result if it is operated with no 

load connected. Proper utilization of the receptacles located on the 

control panel is necessary to prevent damage to either the receptacles 

or the generator. The generator is a limited source of electrical power, 

therefore, pay special attention to the receptacle and generator ratings. 

The nameplate rating can be obtained through a single receptacle as 

long as the receptacles amperage rating is not exceeded.

GROUNDING

All units must be grounded. Drive a 3/4 or 1” copper pipe or rod into 

the ground close to the engine-generator set. The pipe must penetrate 

moist earth. Connect an approved ground clamp to the pipe. Run a 

no. 10 Awg wire from the clamp to the generator ground lug on the 

receptacle panel. Do not connect to a water pipe or to a ground used 

by a radio system. The engine-generators covered in this manual were 

designed primarily for portable use. If you are connecting into a building 

wiring system that is already grounded using the 14-60 4 wire plug, you 

do not have to ground the unit.

Summary of Contents for WC10000VE

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS WC10000VE E G GENERATOR MANUAL...

Page 2: ...ou have selected a high quality precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is important that yo...

Page 3: ...d know its proper use Fire extinguishers rated ABC by NFPA are appropriate E Store fuel only in an approved container and only in a well ventilated area F Follow local codes for closeness to combustib...

Page 4: ...this 9 600 watt rated output generator A B represent the 120 volt output legs of this generator Up to 4 800 watts at 120 volts 40 Amps can be drawn from the receptacles attached to either A or B outp...

Page 5: ...system The necessity of using the correct oil and keep ing the crankcase full cannot be overemphasized Engine failures resulting from inadequate or improper lubricant are considered abuse and not cove...

Page 6: ...an 5 to 10 Watts they will not turn the Conserv R off resulting in low voltage being supplied to them This low voltage can do permanent damage to these appliances BATTERY INSTALLATION This engine gene...

Page 7: ...TICE ENGINE START LOCKOUT This unit will not start if it is low on oil The lu bricating oil level must be at the full mark before the engine will start and run BASIC OPERATION MANUAL STARTING Refer to...

Page 8: ...odically to ensure continued proper operation of the generating plant and appliances If the generator is not equipped with a voltmeter it can be checked with a portable meter CONNECTING THE LOADS APPL...

Page 9: ...d by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergency panel Keep in mind only a limited amount...

Page 10: ...dual oil may have remained in the engine Always use the dipstick when lling the engine with oil to prevent over lling h Replace ller plug I Start the engine and warm it up J After warming up the engin...

Page 11: ...ufflers equipped with spark arresters the spark arrester must be removed every 50 hours for cleaning and inspection Replace if damaged TROUBLESHOOTING Problem Possible Causes Won t start Low oil level...

Page 12: ...rticular purpose are limited to 24 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied...

Reviews: