SPECIFICATIONS

GENERATOR

Fuel

Watts*

Volts

Amps

HZ 

PH

RPM

LP

8,400

120/240 35

60

1

3600

NG

7,600

120/240 32

60

1

3600

*Continuous rating.

Derate 3.5% per 1000 feet elevation above sea level. For 

prime power option, derate 30% and note the circuit 

breaker derates to 25 Amp.

FUEL CONSUMPTION

Natural Gas

1000 BTU/FT³

LP Vapor

2520 BTU/FT³

CF/HR*

132

63

BTU/HR*

132,000

158,760

GAL/HR*

N/A

1.6

*Based on full load operation.

LP TANK SIZING

Tank Temperature

Tank Size

60° F (16° C)

150 Gallons

32° F (0° C)

150 Gallons

0° F (18° C)

250 Gallons

-20° F (-29° C)

500 Gallons

ENGINE

Make    Briggs 

Stratton  

Model 

   Vanguard

Displacement   570 

CC/OHV

Cylinders/Sleeves 

 

V-Twin/Cast Iron

Ignition 

   Electronic

Governor 

   Mechanical

Exhaust 

   Critical 

Grade, 

Glass-pack

See engine manual for additional information

INTRODUCTION

PRODUCT DESCRIPTION

The package standby system is designed to automatically 

provide standby power to unattended loads during 

electrical outages. Upon interruption of normal electrical 

service, the packaged standby system electrical control 

circuits will automatically start the engine. The generator 

will produce electrical power and the Automatic Transfer 

Switch (ATS) will automatically transfer the electrical loads 

to the

engine-generator set. Upon restoration of normal electrical 

service the emergency transfer switch will sense return of 

the normal commercial power. The Automatic Transfer 

Switch will transfer the load back

to the normal commercial power source. The engine 

control circuits will begin a cool-down cycle, after which the 

fuel supply will be shut off and the engine ignition system 

disabled.

AUTOMATIC TRANSFER SWITCH (not included)

A wall mounted ASCO 185 Automatic Transfer Switch (ATS) 

designed for inside or outside installation is recommended. 

The transfer switch is UL1008 approved. A seven day 

electronic exerciser circuit is installed

in the ATS as standard equipment. The ATS also contains 

the power failure sensing circuitry necessary to start and 

stop the engine generator set. The transfer switch is also 

equipped standard with a 3 second start delay, and a 15 

second transfer delay to allow the engine to warm up 

before transferring the load to the generator. When the 

line power is restored the ATS has a 5 minute transfer delay 

to allow the incoming utility to stabilize before transferring 

back to line power and then an additional 2 minute engine 

cool down delay before the engine shuts down. Read 

and understand the ATS owners manual before installing, 

servicing or operating the transfer switch.

UL Automatic Transfer Switch Sizes 

UNIT 

LINE SIDE

CONTACTOR

GENERATOR SIDE 

CONTACTOR

ULPSS8H2W 

100-400 AMPS

100-400 AMPS

The ASCO185 100-400 Amp Switches are available in single 

phase only.

ENGINE / GENERATOR

The engine generator set consists of a Briggs & Stratton 

Vanguard, twin cylinder, four cycle air cooled engine. The 

engine is factory equipped to run on LP or NG fuel. The 

engine operates at 3600 rpm and frequency regulation 

is maintained by the engine governor within 4 cycles 

variation (62.5 Hz - 58.5 Hz) from no load to rated load. The 

generator is a brushless, single bearing, direct drive, rotating 

field design. The generator is connected to the engine’s 

tapered (quill) crankshaft extension. The engine generator 

is mounted in a drip-proof enclosure for outside installation. 

Connection boxes and terminal blocks are provided for all 

customer connections (both AC output and DC control). A 

customer supplied 12 volt 500 CCA (BCI group 26) battery 

is required to complete the installation. 

NOTICE: 

This unit will automatically transfer if a power outage occurs 

while running in an exercise mode.

TESTING POLICY

Before any generator is shipped from the factory, it is fully 

checked for performance. The generator is loaded to its 

full capacity, and the voltage, current, and frequency are 

carefully checked.

Rated output of generator is based on engineering tests 

of typical units, and is subject to, and limited by, the 

temperature, altitude, fuel, and other conditions specified 

by the manufacturer of applicable engines.

Summary of Contents for PSS8B2W/F

Page 1: ...contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURCHAS...

Page 2: ...TOMATIC TRANSFER SWITCH ENGINE GENERATOR SET ENGINE MAINTENANCE 17 CHECKING THE OIL LEVEL CHANGING THE OIL MAINTENANCE SCHEDULE TROUBLE SHOOTING 18 OUTLINE DRAWING 19 PAD LAYOUT DRAWING 20 AC WIRING S...

Page 3: ...he earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C D...

Page 4: ...r failure sensing circuitry necessary to start and stop the engine generator set The transfer switch is also equipped standard with a 3 second start delay and a 15 second transfer delay to allow the e...

Page 5: ...tween the base frame and the pad Engine vibration will be transmitted to the control panel causing erroneous start stop cycles and premature control failure These units should be mounted a minimum of...

Page 6: ...require a larger line be installed to provide a fuel reservoir If this is not done the demand regulator on the unit and the pressure regulator in the fuel line will interfere with each other This reg...

Page 7: ...unit that has been operating on Liquid Propane vapor and you now want to operate it on Natural Gas all that you will need to do is unplug this connector LUBRICATION Before starting the engine fill the...

Page 8: ...wear which can be cumulative 2 Where electrolyte contacts skin wash off immediately with water 3 If electrolyte contacts the eyes flush immediately and thoroughly with water Seek immediate medical at...

Page 9: ...ounted on the generator set which is located behind an access cover in the rear of the unit The battery tender receptacle is to be powered by a GFCI circuit and installed in accordance with the United...

Page 10: ...in rigid or flexible conduit Because of the many different types of service feeder and distribution equipment no specific wiring instructions can be provided It is however recommended that copper wire...

Page 11: ...eep Sea Electronics Model 3110 is used on this generator set See following picture and look for more information stated within this manual MANUAL OPERATION Press and release the red Stop Reset button...

Page 12: ...hanging the exercise without a load will be discussed later Be sure that conditions are safe to do this operation BYPASS TIME DELAY Use this button to cancel the active time delay or exercise period s...

Page 13: ...art and run the exerciser must be reset after the power is restored The ASCO 185 has settings that can be changed for various applications The dipswitch options are explained in the ASCO 185 Operator...

Page 14: ...14 60706 211 F SEQUENCE OF OPERATION UTILITY FAILURE...

Page 15: ...Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The module has...

Page 16: ...ATIVE MAINTE NANCE Reasonable care in preventative maintenance will ensure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any type...

Page 17: ...ghtly lubricate the oil gasket with fresh clean oil E Install the oil filter by hand until the gasket contacts the oil filter adapter then tighten the oil filter 1 2 to 3 4 turns F Remove the dipstick...

Page 18: ...cked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Def...

Page 19: ...19 60706 211 F 36 50 28 00 29 75 36 00 27 375 28 375 OUTLINE DRAWING...

Page 20: ...20 60706 211 F PAD LAYOUT DRAWING 11075 00 20 60706 211 ENGINE GENERATOR SET PAD LAYOUT AC WIRING SCHEMATIC...

Page 21: ...21 60706 211 F 11075 00 22 60706 211 AC AND DC GENERATOR SCHEMATIC AC AND DC GENERATOR SCHEMATIC...

Page 22: ...22 60706 211 F EXTERNAL RECEPTICAL ASSEMBLY IF EQUIPPED SOLAR CONTROL PANEL IF EQUIPPED...

Page 23: ...23 60706 211 F SOLAR PANEL ASSEMBLY IF EQUIPPED...

Page 24: ...ance consumables or labor This warranty does not cover travel time mileage or labor for removal or re installation of WINCO product from its application Normal wear and tear Costs of rental equipment...

Reviews: