SPECIFICATIONS
GENERATOR
Fuel
Watts*
Volts
Amps
HZ
PH
RPM
LP
8,400
120/240 35
60
1
3600
NG
7,600
120/240 32
60
1
3600
*Continuous rating.
Derate 3.5% per 1000 feet elevation above sea level. For
prime power option, derate 30% and note the circuit
breaker derates to 25 Amp.
FUEL CONSUMPTION
Natural Gas
1000 BTU/FT³
LP Vapor
2520 BTU/FT³
CF/HR*
132
63
BTU/HR*
132,000
158,760
GAL/HR*
N/A
1.6
*Based on full load operation.
LP TANK SIZING
Tank Temperature
Tank Size
60° F (16° C)
150 Gallons
32° F (0° C)
150 Gallons
0° F (18° C)
250 Gallons
-20° F (-29° C)
500 Gallons
ENGINE
Make Briggs
&
Stratton
Model
Vanguard
Displacement 570
CC/OHV
Cylinders/Sleeves
V-Twin/Cast Iron
Ignition
Electronic
Governor
Mechanical
Exhaust
Critical
Grade,
Glass-pack
See engine manual for additional information
INTRODUCTION
PRODUCT DESCRIPTION
The package standby system is designed to automatically
provide standby power to unattended loads during
electrical outages. Upon interruption of normal electrical
service, the packaged standby system electrical control
circuits will automatically start the engine. The generator
will produce electrical power and the Automatic Transfer
Switch (ATS) will automatically transfer the electrical loads
to the
engine-generator set. Upon restoration of normal electrical
service the emergency transfer switch will sense return of
the normal commercial power. The Automatic Transfer
Switch will transfer the load back
to the normal commercial power source. The engine
control circuits will begin a cool-down cycle, after which the
fuel supply will be shut off and the engine ignition system
disabled.
AUTOMATIC TRANSFER SWITCH (not included)
A wall mounted ASCO 185 Automatic Transfer Switch (ATS)
designed for inside or outside installation is recommended.
The transfer switch is UL1008 approved. A seven day
electronic exerciser circuit is installed
in the ATS as standard equipment. The ATS also contains
the power failure sensing circuitry necessary to start and
stop the engine generator set. The transfer switch is also
equipped standard with a 3 second start delay, and a 15
second transfer delay to allow the engine to warm up
before transferring the load to the generator. When the
line power is restored the ATS has a 5 minute transfer delay
to allow the incoming utility to stabilize before transferring
back to line power and then an additional 2 minute engine
cool down delay before the engine shuts down. Read
and understand the ATS owners manual before installing,
servicing or operating the transfer switch.
UL Automatic Transfer Switch Sizes
UNIT
LINE SIDE
CONTACTOR
GENERATOR SIDE
CONTACTOR
ULPSS8H2W
100-400 AMPS
100-400 AMPS
The ASCO185 100-400 Amp Switches are available in single
phase only.
ENGINE / GENERATOR
The engine generator set consists of a Briggs & Stratton
Vanguard, twin cylinder, four cycle air cooled engine. The
engine is factory equipped to run on LP or NG fuel. The
engine operates at 3600 rpm and frequency regulation
is maintained by the engine governor within 4 cycles
variation (62.5 Hz - 58.5 Hz) from no load to rated load. The
generator is a brushless, single bearing, direct drive, rotating
field design. The generator is connected to the engine’s
tapered (quill) crankshaft extension. The engine generator
is mounted in a drip-proof enclosure for outside installation.
Connection boxes and terminal blocks are provided for all
customer connections (both AC output and DC control). A
customer supplied 12 volt 500 CCA (BCI group 26) battery
is required to complete the installation.
NOTICE:
This unit will automatically transfer if a power outage occurs
while running in an exercise mode.
TESTING POLICY
Before any generator is shipped from the factory, it is fully
checked for performance. The generator is loaded to its
full capacity, and the voltage, current, and frequency are
carefully checked.
Rated output of generator is based on engineering tests
of typical units, and is subject to, and limited by, the
temperature, altitude, fuel, and other conditions specified
by the manufacturer of applicable engines.
Summary of Contents for PSS8B2W/F
Page 14: ...14 60706 211 F SEQUENCE OF OPERATION UTILITY FAILURE...
Page 19: ...19 60706 211 F 36 50 28 00 29 75 36 00 27 375 28 375 OUTLINE DRAWING...
Page 22: ...22 60706 211 F EXTERNAL RECEPTICAL ASSEMBLY IF EQUIPPED SOLAR CONTROL PANEL IF EQUIPPED...
Page 23: ...23 60706 211 F SOLAR PANEL ASSEMBLY IF EQUIPPED...