Winco PSS21F4/1 Installation And Operator'S Manual Download Page 11

11

OPM-146/D

NG/LP FUEL CONVERSION

This generator set was tested on both LP and NG at the 

factory. Ensure proper fuel configuration before operating. 

These engine/generator sets are easy to convert between 

LP or NG. As the engine timing is controlled by the ECU on 

the engine you only need to tell it what fuel you want to 

operate on. A small rocker switch has been provide on the 

underside of the engine control cabinet for this purpose.

Opening the rocker switch will tell the ECU mounted on 

the engine that you are operating on NG Fuel. Closing the 

rocker switch will tell the ECU that the fuel being supplied is 

LP. The Advance Power Controller has an indicator light for 

LP. When this light is on, the engine is set-up for LP, when 

the LP light is out the engine is set up for NG. The ECU will 

then reprogram the engine to operate on the proper fuel.

LUBRICATION & COOLANT

Before starting the engine, check the oil level in the 

crankcase. If it is low, refill to the full mark with the proper 

weight/grade of oil as recommended by the engine 

manufacturer’s maintenance instructions. The necessity of 

using the correct oil and keeping the crankcase full cannot 

be over emphasized. Failure to do so will cause excessive 

engine wear and shorten its useful life. 

Winco recommends our 5W-30 fully synthetic heavy duty 

engine oil to give you maximum cold weather protection 

while maintaining excellent performance in warmer 

weather. We have partnered with a national lubrication oil 

manufacturer to give you access to Winco private branded 

premium oil available at comparable prices to conventional 

oils. See your dealer for additional information.

Before starting the engine, Check the coolant level in 

the radiator. If it is low, refill as specified in the engine 

manufacturer’s maintenance instructions. The radiator 

should be filled to about 1 inch below the filler neck. 

ELECTRICAL CONNECTIONS

NOTICE: CLASS 1 WIRING METHODS ARE TO BE USED FOR 

ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A 

CLASS 2 CIRCUIT

NOTE: The symbol            always indicates ground where 

shown. All wiring must be completed in accordance with 

the National Electric Code as well as any state and local 

codes.

You must pay particular attention to wire size requirement 

for the amperage of service you are dealing with. The table 

below provides you guidance on wire sizing based on 

both wire type and amperage. Wire amperages have been 

derated for 40° C ambient temperatures operation.

CAUTION: EQUIPMENT DAMAGE

Do not make any fuel adjustments or governor 

adjustments until all pressure readings are in 

compliance with specification. 

The following diagram is of a natural gas (NG) installation.

Reference numbers 2 through 4 in the previous diagram 

are system parts supplied by the customer. Reference 

number 4 is on the generator.

FUEL PRESSURE TABLES

The following tables are the fuel pressure readings at each 

reference in the system.

SINGLE LOW PRESSURE REGULATOR (LP vapor only)

Ref#

1

3

4

Unit off

Line PSI

7-11 in
4-6 oz

7-11 in 
4-6 oz

Starting

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

TWO REGULATOR SYSTEM (LP vapor only)

Ref#

1

2

3

4

Unit off

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

Starting

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

Line PSI

10-15 lbs

7-11 in
4-6 oz

7-11 in
4-6 oz

NATURAL GAS

Ref#

2

3

4

Unit off

2 PSI

7-11 in
4-6 oz

7-11 in 
4-6 oz

Starting

2 PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

2 PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

2 PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Summary of Contents for PSS21F4/1

Page 1: ...ould ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _______________________________________...

Page 2: ...E MAINTENANCE SCHEDULE 23 TROUBLE SHOOTING TABLES 24 ENGINE HARNESS SCHEMATIC 25 ENGINE CONTROLS 26 POWER DISTRIBUTION STARTING SYSTEM IGNITION SYSTEM CHARGING SYSTEM SENSORS ACTUATOR DATA LINK CONNEC...

Page 3: ...lert against unsafe practices A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or use open flame near the generator set or fuel tank D K...

Page 4: ...1 0 0 8 0 8 0 8 0 8 Amps 88 76 66 36 29 Hertz 60 60 60 60 60 ENGINE Model FORD MSG 425 Starting System 12 Volt Fuel Consumption LP NG 3 6 Gal HR 277 600 BTU HR 306 3 FT3 HR 321 576 BTU HR Oil Type Se...

Page 5: ...0 8 Amps 105 87 75 38 30 Hertz 60 60 60 60 60 NG Watts 24 300 24 300 24 300 24 300 24 300 Volts 120 240 120 208 120 240 277 480 346 600 Phase Single Three Three Three Three PF 1 0 0 8 0 8 0 8 0 8 Amp...

Page 6: ...y records Several of the major components also have their own individual data plates providing additional information to document build data for warranty and replacements parts Be sure to have the mai...

Page 7: ...TING THE GENERATOR SET Due to the different designs configurations options weights site conditions and available material handling equipment specific lifting instructions are not provided for each ind...

Page 8: ...oceeding with the installation be sure the engine control is in the stop position and the emergency stop depressed Also be sure the generator MLCB main line circuit breaker in is the off position and...

Page 9: ...t your local fuel supplier for your exact requirements The appropriate line size from the following table is then installed from the low pressure regulator to the generator set WARNING FIRE HAZARD All...

Page 10: ...t 10 feet from the engine generator set any closer installation will require a larger line be installed to provide a fuel reservoir If this is not done the demand regulator on the unit and the pressur...

Page 11: ...it is low refill as specified in the engine manufacturer s maintenance instructions The radiator should be filled to about 1 inch below the filler neck ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING ME...

Page 12: ...anel must be installed All selected emergency circuits are removed from main distribution panels and installed in the emergency distribution panel The ATS is then installed between the main panel and...

Page 13: ...cy Stop Emergency Stop Remote Start Remote Start Ground Ground Battery Battery E Stops C Ground Lug These ground lugs are bonded to ground and are provided for you to connect your ground wire from the...

Page 14: ...of the highest CCA rated battery within the correct BCI group will increase cold weather starting performance BATTERY REQUIREMENTS Voltage BCI Group Min CCA Rating 12 24 650 Installation and servicin...

Page 15: ...all DC battery connections are tight and clean Follow battery manufacturer s recommendations This charger is mounted under the customer connection on the control side of the generator The charger will...

Page 16: ...g them will cause damage to the engine control module STARTING PROCEDURE LUBRICATION Before starting the engine check the oil level in the crankcase If it is low refill to the full mark with the prope...

Page 17: ...approximate voltage should be found between terminals G3 and G N 120 volts AC On three phase panels the G2 voltage level should also be checked ON 240 VOLT DELTA SYSTEMS BE SURE YOU KNOW WHERE THE HIG...

Page 18: ...rvicing the unit For standby operation press the AUTO button on the front of the control The green light should light up next to the AUTO button NOTE For setting the exerciser circuit for all ATS see...

Page 19: ...to reduce the amount of dust and debris entering the housing and generator components COLD WEATHER OPERATIONS The minimum starting temperature with block heater is 13 F The degree of fluidity of the e...

Page 20: ...r allow oil to seep into the ground or sewer systems doing so will cause environmental damage WARNING PERSONAL INJURY EQUIPMENT DAMAGE Place controller in manual mode e stop applied first If an auto s...

Page 21: ...level is very low this could cause serious engine damage WARNING EQUIPMENT DAMAGE Never operate the engine with the air cleaner element removed This may allow foreign material to enter the engine and...

Page 22: ...mended engine oil and one part Stoddard Solvent or equivalent 4 Check coolant protection Store indoors in dry area Infinite period 1 Perform the next Preventive Maintenance procedure For example if th...

Page 23: ...ry 250 hours ENGINE OIL FREQUENCY Check engine oil Daily Drain and fill engine Every 400 hours Replace engine oil Every 400 hours ENGINE SPEED CONTROL FREQUENCY Check and adjust governor lever Daily E...

Page 24: ...e Ancillary components binding Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water temperature Engine has overspeed Engine has gone into overcrank No out...

Page 25: ...NESS SCHEMATIC 6 1 6 1 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 1 1 51 66 8 211 5 9 51 3 6 5 1 02 00 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 3...

Page 26: ...26 OPM 146 D Power Distribution POWER DISTRIBUTION ENGINE CONTROLS...

Page 27: ...27 OPM 146 D STARTING SYSTEM...

Page 28: ...28 OPM 146 D MSG 425 Engine Controls Ignition System IGNITION SYSTEM...

Page 29: ...29 OPM 146 D MSG 425 Engine Controls Charging System CHARGING SYSTEM...

Page 30: ...30 OPM 146 D Engine Controls Sensors 1 of 2 SENSORS...

Page 31: ...31 OPM 146 D SENSORS Engine Controls Sensors 2 of 2...

Page 32: ...32 OPM 146 D Engine Controls Actuator Data Link Connector DLC ACTUATOR DATA LINK CONNECTOR...

Page 33: ...33 OPM 146 D MSG 425 Engine Controls 08 23 Engine Controls Dry Fuel DEPR DRY FUEL DEPR...

Page 34: ...5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 56 6 2 1 29...

Page 35: ...35 OPM 146 D THREE PHASE AC WIRE HIGH WYE THREE PHASE AC WIRE LOW WYE THREE PHASE AC WIRING DELTA SINGLE PHASE 311 WINDING WIRING DIAGRAMS...

Page 36: ...ld liable for any special indirect consequential or liquidated damages WINCO Inc shall not be liable for any claim that requires replacement of engine part or component of the product that is no longe...

Reviews: