14
60706-229/F
the transfer switch can be wired in directly after the watt-
hour meter and the service entrance, providing the service
entrance ampere rating is within the transfer switch’s rated
capability.
If only specific circuits are to be powered under emergency
power failure conditions, an additional distribution panel
designated “emergency distribution panel” must be
installed.
All selected emergency circuits are removed from main
distribution panels and reinstalled in the emergency
distribution panel. Suggested circuits: freezer, refrigerator,
furnace, emergency lights, sump pump, emergency outlet
circuits, etc. Total running load must not exceed generator
rating.