Winco PSS12H2E Installation And Operator'S Manual Download Page 14

14

REV F

60706-209

Function

Factory 

Setting

Dip 

Switch

Dip 

Actuator

Actuator Position

Clock Battery Off

S2

10

On (up)

Off (down)

Exerciser

Off

S1

7

On (up)

Off (down)

With load or 

without load

Without 

Load

S1

8

With (up) 

Without (down)

SETTING THE EXERCISER

Press and hold (5 seconds) the Set Engine Exerciser button. The 

exercise period occurs immediately and at the same time weekly 

thereafter. The status light below the button blinks during the exercise 

period (including cool down). The light stays on to indicate that the 

exerciser has been set. If the light is off, the exerciser has not been set.

CANCELING AN ACTIVE EXERCISE PERIOD 

Press the Bypass Time Delay button to stop an exercising generator. If 

exercise with load is set, the ATS retransfers the load to the utility, then 

stops the generator after cooldown.

WARNING:

With a total power failure (utility power fails and the generator fails to 

start and run), the exerciser must be reset after the power is restored.

The ASCO 185 has settings that can be changed for various 

applications. The dipswitch options are explained in the ASCO 185 

Operator’s Manual.

This completes your installation and unit testing. ALWAYS leave the 

system in automatic mode unless servicing the unit. For automatic 

operation, the auto mode icon must be displayed on the engine control

module display.

by default. Changing the exercise without a load will be discussed later. 

Be sure that conditions are safe to do this operation. 

BYPASS TIME DELAY

Use this button to cancel the active time delay or exercise period (stops 

the generator after cool-down).

SET ENGINE EXERCISER

Use this button to set the automatic exerciser. 

INDICATOR LIGHTS

On the front control display are five lights that indicate the status of the 

sources and the ATS.

UTILITY ACCEPTABLE

This light indicates that the utility voltage is acceptable for connection 

to the loads.

GENERATOR ACCEPTABLE

This light indicates that the generator voltage and frequency is 

acceptable for connection to the load.

LOAD ON UTILITY

This light indicates that the generator voltage is acceptable for 

connection to the load.

AUTOMATIC GENERATOR EXERCISER

This light indicates the status of the generator exerciser:

  • Blinks during the exercise period (including cool down)

  • Stays on when the exerciser has been set.

  • Is off when the exerciser has not been set.

GENERATOR STARTING CONTACTS

Disconnect the generator battery. Connect the generator starting wires 

#1 (battery -) to terminal 4; wire #23 (start) to terminal 5 of the TB7 

terminal block. This is removable for convenient connections.  

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to automatically 

exercise the generator for 20 minutes once every week.

In order to set and test the exercise circuit the AUTO button on the 

generator control panel must be on.

EXERCISE WITH OR WITHOUT LOAD

The transfer switch can be set up to exercise the generator with or 

without a load transfer. Normally, WINCO generators exercise without 

a load transfer. This is because you may not with to have a momentary 

interruption of power. Turn the exerciser dip switch on. Then set the 

“with load” or “without load”. See the following table.

Summary of Contents for PSS12H2E

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS PSS12H2W E F GENERATOR MANUAL...

Page 2: ...GER SOLAR CHARGER OPTION 10 AC ELECTRICAL CONNECTIONS 11 GENERATOR CONNECTIONS WINCO UL ATS ASCO 185 DC ELECTRICAL INTERCONNECTION 12 ASCO 185 UL SWITCH INITIAL START UP 12 START UP PROCEDURE CUSTOMER...

Page 3: ...xpect from WINCO should you need service assistance in the future COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact...

Page 4: ...the earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C...

Page 5: ...recommended The transfer switch is UL1008 approved A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing circuitry...

Page 6: ...isfactory system installation The information in this manual is offered only as a guide to finalizing your installation plans ENGINE GENERATOR SET MOUNTING WARNING PERSONAL INJURY The enclosures on th...

Page 7: ...ng located on the left side of the engine generator set This fitting is shipped with a plastic plug installed to insure the fuel system stays clean For all vapor fuel systems the delivery pressure of...

Page 8: ...load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Natural gas Ref 2 3 4 Unit off 2 PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Starting 2 PSI 7 11...

Page 9: ...charger has an indicator light on it Red indicates it is charging and green indicates it is in storage mode float charge This charger is INSTALLING THE BATTERY CAUTION In the following battery install...

Page 10: ...not intended to recharge a battery which has become completely discharged It is designed to produce enough current to recharge a slightly low battery and maintain a fully charged battery SOLAR CHARGER...

Page 11: ...ed emergency distribution panel must be installed All selected emergency circuits are removed from main distribution panels and reinstalled in the emergency distribution panel Suggested circuits freez...

Page 12: ...GRZQ OHDUDQFH IRU VHUYLFH DQG PDLQWHQDQFH RQ DOO VLGHV 3URSHU IXHO OLQH PDWHULDO DQG VL H OO IXHO OLQH FRQQHFWLRQV WLJKW XHO OLQH SURWHFWHG DQG D PRLVWXUH WUDS LQVWDOOHG PD EH required for NG 3 1 SUH...

Page 13: ...DAMAGE SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED SERVICE TECH NOTICE If for any reason during the check out procedures the Voltage and frequency are not correct press the red Stop Reset but...

Page 14: ...utton to cancel the active time delay or exercise period stops the generator after cool down SET ENGINE EXERCISER Use this button to set the automatic exerciser INDICATOR LIGHTS On the front control d...

Page 15: ...ITY LINE TO POWER BATTERY TENDER AND OPTIONAL ENGINE HEATER CUSTOMER GENERATOR OUTPUT CONNECTIONS TO EMERGENCY TRANSFER SWITCH EMERGENCY STOP CONTACTS PROVIDED FOR REMOTE EMERGENCY STOP SWITCH UNIT WI...

Page 16: ...16 REV F 60706 209 SEQUENCE OF OPERATION UTILITY FAILURE...

Page 17: ...CODES Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The modu...

Page 18: ...ENTATIVE MAINTENANCE Reasonable care in preventative maintenance will ensure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any typ...

Page 19: ...8 Locked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty...

Page 20: ...20 REV F 60706 209 PAD LAYOUT DRAWING 21 11075 01 60706 209 ENGINE GENERATOR SET PAD LAYOUT...

Page 21: ...TIONS ASCO 165 SERIES TRANSFER SWITCH 9 8 7 6 5 4 3 2 1 TB7 L6 NEUTRAL T B 4 3 2 1 L2 GROUND T B 9 POSITION CONNECTOR G1 N G3 GND N L1 GND 1 5 24 23 ES ES 2 4 1 24 22 1 23 CONTROL TOWER ENGINE CONTROL...

Page 22: ...22 REV F 60706 209 SOLAR CONTROL PANEL IF EQUIPPED EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED N N GND GND G1 G1 G3 G3 G3 G3...

Page 23: ...23 REV F 60706 209 SOLAR PANEL ASSEMBLY IF EQUIPPED...

Page 24: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some s...

Reviews: