Winco PSS12H2E Installation And Operator'S Manual Download Page 13

13

REV F

60706-209

STOP/RESET (red button) - This button places the 

module into its Stop/Reset mode. This will clear any 

alarm conditions for which the triggering criteria have 

been removed. The fuel supply de-energizes and the 

engine comes to a standstill. Should a remote start 

signal be present while operating in this mode, a 

remote start WILL NOT occur.
AUTO (white button) - This button places the module 

into its Automatic mode. This mode allows the module 

to control the function of the generator automatically. 

The module will monitor the remote start input 

and once a start request is made, the set will be 

automatically started and placed on load. The module  

will then wait until the next start event.
START (green button) - Pressing this button from 

STOP/RESET will start the engine and run the load. 

PAGE - Pressing this button scrolls the display to show 

the various instruments. 

With the engine running soothly, check the no load voltage and 

frequency wire #1 and #4 on the generator terminal block in the ATS 

(L2 and L6 in the ASCO ATS). The voltage should be 240 Volts plus 

or minus nominal. The frequency should be between 61.5 to 62 Hertz 

(Hz). The Voltage should also be checked between the hot terminals 

(L2 and L6) and the neutral connection. The Voltage should be about 

one half of the line to line Voltage. 

OPERATING SPEED

The engine-generator must be run at the correct speed in order to 

produce the proper electrical voltage and frequency.

The speed of the engine was carefully adjusted at the factory so that 

the generator produces the proper voltage and frequency. For normal 

usage, the speed setting should not be charged. If the generator is 

being run continuously on a very light load, it is often advisable to lower 

the operating speed slightly. 

CAUTION: EQUIPMENT DAMAGE

SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED 

SERVICE TECH. 

NOTICE:

If for any reason during the check out procedures the Voltage and

frequency are not correct, press the red Stop/Reset button and correct

the trouble before proceeding.

After verifying the Voltage and frequency are not correct, press the 

Stop/Reset button. This will shut off the engine immediately.

TRANSFER SWITCH & ENGINE-GENERATOR

Automatic (remote) Operation

This procedure checks the electrical operation of the automatic transfer 

switch. If the actual operation does not follow procedure, consult the 

trouble-shooting section in the transfer switch manual.
  1. Turn on the preferred source (utility) circuit breaker. The Utility 

    Acceptable Light should now come on, as well as the Load on 

    Utility Light. If those lights fail to come on, recheck your incoming 

    power to ensure you have 240 Volts nominal. If not, troubleshoot 

    your utility source before continuing.
  2. Press and release the Auto button on the engine control module 

    (ECM). The auto mode icon will appear on the screen. The unit is 

    now ready to be operated from the Automatic Transfer Switch.
  3. Turn on the alternate source (generator) circuit breaker.

WARNING: PERSONAL INJURY HAZARD:

Install front cover in transfer switch before operation. An electrical 

system fault could cause a flash and severe personal injury.

The digital controller provides sensing, timing, and control functions for 

the ATS. This micro-processor-based controller includes built-in control 

buttons and status lights for control of the ATS and the generator. 

PUSH BUTTONS

On the front control display are the three push buttons that control the 

operation of the generator and the ATS.

CAUTION:

Before using the transfer test button, be sure that conditions are safe 

for running the generator and for load tester.

TRANSFER TEST

Use this button to test the system. This operation starts the generator 

and transfers the load. The controller is shipped with a load transfer set 

Summary of Contents for PSS12H2E

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS PSS12H2W E F GENERATOR MANUAL...

Page 2: ...GER SOLAR CHARGER OPTION 10 AC ELECTRICAL CONNECTIONS 11 GENERATOR CONNECTIONS WINCO UL ATS ASCO 185 DC ELECTRICAL INTERCONNECTION 12 ASCO 185 UL SWITCH INITIAL START UP 12 START UP PROCEDURE CUSTOMER...

Page 3: ...xpect from WINCO should you need service assistance in the future COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact...

Page 4: ...the earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C...

Page 5: ...recommended The transfer switch is UL1008 approved A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing circuitry...

Page 6: ...isfactory system installation The information in this manual is offered only as a guide to finalizing your installation plans ENGINE GENERATOR SET MOUNTING WARNING PERSONAL INJURY The enclosures on th...

Page 7: ...ng located on the left side of the engine generator set This fitting is shipped with a plastic plug installed to insure the fuel system stays clean For all vapor fuel systems the delivery pressure of...

Page 8: ...load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 10 15 lbs 7 11 in 4 6 oz 7 11 in 4 6 oz Natural gas Ref 2 3 4 Unit off 2 PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Starting 2 PSI 7 11...

Page 9: ...charger has an indicator light on it Red indicates it is charging and green indicates it is in storage mode float charge This charger is INSTALLING THE BATTERY CAUTION In the following battery install...

Page 10: ...not intended to recharge a battery which has become completely discharged It is designed to produce enough current to recharge a slightly low battery and maintain a fully charged battery SOLAR CHARGER...

Page 11: ...ed emergency distribution panel must be installed All selected emergency circuits are removed from main distribution panels and reinstalled in the emergency distribution panel Suggested circuits freez...

Page 12: ...GRZQ OHDUDQFH IRU VHUYLFH DQG PDLQWHQDQFH RQ DOO VLGHV 3URSHU IXHO OLQH PDWHULDO DQG VL H OO IXHO OLQH FRQQHFWLRQV WLJKW XHO OLQH SURWHFWHG DQG D PRLVWXUH WUDS LQVWDOOHG PD EH required for NG 3 1 SUH...

Page 13: ...DAMAGE SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED SERVICE TECH NOTICE If for any reason during the check out procedures the Voltage and frequency are not correct press the red Stop Reset but...

Page 14: ...utton to cancel the active time delay or exercise period stops the generator after cool down SET ENGINE EXERCISER Use this button to set the automatic exerciser INDICATOR LIGHTS On the front control d...

Page 15: ...ITY LINE TO POWER BATTERY TENDER AND OPTIONAL ENGINE HEATER CUSTOMER GENERATOR OUTPUT CONNECTIONS TO EMERGENCY TRANSFER SWITCH EMERGENCY STOP CONTACTS PROVIDED FOR REMOTE EMERGENCY STOP SWITCH UNIT WI...

Page 16: ...16 REV F 60706 209 SEQUENCE OF OPERATION UTILITY FAILURE...

Page 17: ...CODES Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The modu...

Page 18: ...ENTATIVE MAINTENANCE Reasonable care in preventative maintenance will ensure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any typ...

Page 19: ...8 Locked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty...

Page 20: ...20 REV F 60706 209 PAD LAYOUT DRAWING 21 11075 01 60706 209 ENGINE GENERATOR SET PAD LAYOUT...

Page 21: ...TIONS ASCO 165 SERIES TRANSFER SWITCH 9 8 7 6 5 4 3 2 1 TB7 L6 NEUTRAL T B 4 3 2 1 L2 GROUND T B 9 POSITION CONNECTOR G1 N G3 GND N L1 GND 1 5 24 23 ES ES 2 4 1 24 22 1 23 CONTROL TOWER ENGINE CONTROL...

Page 22: ...22 REV F 60706 209 SOLAR CONTROL PANEL IF EQUIPPED EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED N N GND GND G1 G1 G3 G3 G3 G3...

Page 23: ...23 REV F 60706 209 SOLAR PANEL ASSEMBLY IF EQUIPPED...

Page 24: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some s...

Reviews: