15
60706-236/J
panel. Keep in mind only a limited amount of amperage is
available from the generator set. Some circuit breakers may
still have to be turned off to prevent an overload on the
generator during the initial start up. See the nameplate on
your generator for the amperage capabilities of your unit.
CAUTION: EQUIPMENT DAMAGE
Failure to properly limit and balance the load applied
to the generator will cause the generator to produce
low voltage and may damage the engine generator
set. It may also cause severe damage to the loads con-
nected to the generator at that time. Improper loading
of the generator set constitutes abuse and will not be
covered by warranty.