GASOLINE

When using gasoline, always use fresh, clean, 
unleaded fuel.  This engine is certifi ed to operate on 
unleaded gasoline with a minimum octane rating of 
86 or higher.  Gasoline containing no more than 10% 
ethanol is acceptable. 

CAUTION:  EQUIPMENT DAMAGE

Do not use unapproved gasoline, such as E15 or 
E85.  Do not mix oil in the gasoline.  Use of unap-
proved fuels will damage the engine components 
and void the engine warranty.

Use of fuels with content of ethanol greater than 
shown above may cause starting and/or perfor-
mance problems.  Always ensure that the fuel is 
clean and free of all impurities.

WARNING:  FIRE DANGER

    Gasoline and its fumes are VERY explosive when 
proper precautions are not taken.

Never use gasoline that has been stored for an ex-
tended period of time as the fuel will lose its volatile 
properties and you will be left with varnish residue.  
The varnish like substance will clog the carburetor 
and will not burn properly.

The use of fuel additives, such as STA-BIL, or an 
equivalent will minimize the formation of fuel gum 
deposits.  If a unit has been out of operation for an 
extended period of time, it is best to drain old fuel 
from the engine and replace with fresh fuel before 
attempting to start.

BATTERY INSTALLATION

The DL6000H generator set is shipped with a battery 
tie down kit for customer installation. This kit consists 
of a battery tie down and hardware for installation of 

the customer supplied battery on the unit. 
If you intend to use the power plant’s electric start 
system, you will need to purchase and install a bat-
tery to operate it.  Units equipped with a recoil or rope 
start will operate satisfactorily without a battery.

WARNING:  EQUIPMENT DAMAGE

    The battery positive (+) cable is shipped with a 
plastic protective cap.  When starting manually, this 
protective cap must remain in place to avoid pos-
sible damage to the engine electrical system and/or 
generator end.

A 12-volt powersports (motorcycle/atv/snowmo-
bile) battery,

 

BCI group 20 or 24HL rated at 300 

CCA

 or larger is recommended for this electric start 

engine generator set.  Maximum length:  8 1/8”, Maxi-
mum width:  3 9/16”, Height range:  5 3/4” - 7”.  Amp 
Hours:  15AH or greater.  Follow the battery manufac-
turers recommendations for servicing and charging 
prior to use.  Connect the battery to the electric start 
system using the cables provided..

CAUTION: EQUIPMENT DAMAGE

    These electric start engines are NEGATIVE 
GROUND. Use extreme caution when connecting the 
battery. Connect the NEGATIVE battery terminal to 
GROUND.

For your safety always connect the positive battery 
cable to the “bat+” terminal fi rst.  Then connect the 
negative battery cable to the “bat-” terminal.  Make 
sure all connections are clean and tight.  Reverse the 
sequence when disconnecting, disconnect the nega-
tive cable fi rst.  These engines produce enough direct 
current to keep a battery charged under normal oper-
ating conditions, but were not intended to be used as 
a battery charger.

AMBIENT TEMPERATURE

Use 4-stroke motor oil that meets or exceeds the requirements for
API service classification SJ or later (or equivalent). Always check
the API service label on the oil container to be sure it includes the
letters SJ or later (or equivalent).

SAE 10W-30 is recommended for general use. Other viscosities
shown in the chart may be used when the average temperature in
your area is within the indicated range.

Summary of Contents for 15041-006

Page 1: ...INSTALLATION AND OPERATORS MANUAL PORTABLE GENERATORS DL5000H D DL6000H F WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 wincogen com...

Page 2: ...ing 8 Electric Starting 8 Stopping Storage 9 Operating Speed 9 CONNECTING THE LOADS 10 Wiring 10 ENGINE CARE 11 GENERATOR CARE 12 TROUBLESHOOTING 13 CONTROL PANEL WIRING DIAGRAM 14 WARRANTY INFORMATIO...

Page 3: ...dren c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel on...

Page 4: ...3rd party companies making enclosures for generators that have been properly engineered The use of these 3rd party enclosures is acceptable as long as they have been certified and meet current code DO...

Page 5: ...s in good order when shipped Inspect the generator set promptly after receiving it If any damage is noted notify the trans portation company immediately request proper pro cedures for filing a conceal...

Page 6: ...perate it Units equipped with a recoil or rope start will operate satisfactorily without a battery WARNING EQUIPMENT DAMAGE The battery positive cable is shipped with a plastic protective cap When sta...

Page 7: ...ed inside the engine If the oil level drops below a certain point the low oil module on the engine will shut it down This low oil warning system will automatically stop the engine before the oil level...

Page 8: ...ith time to cool off between cranking cycles Do not operate the starter more than 5 seconds and wait at least 10 seconds before operating the starter again Repeat cycle if necessary 6 When the engine...

Page 9: ...chart Although individual units and models vary slightly the normal voltage and frequency of the engine gen erator described in this manual are approximately as follows under varying loads LOAD VS OUT...

Page 10: ...ll state and local codes and regulations Check with local authorities before proceeding WARNING PERSONAL DANGER A fully isolated double pole double throw manual transfer switch must be installed any t...

Page 11: ...The oil level must al ways be checked before the engine is started Take care to remove any dirt or debris from around the oil fill plug before removing Be sure the oil level is maintained Fill to the...

Page 12: ...tion or replacement of parts should be performed only by a qualified electrical service technician USE ONLY FACTORY APPROVED REPAIR PARTS a Bearing The bearing used in these generators is a heavy duty...

Page 13: ...Shorted capacitor Shorted diodes on rotor GFCI Receptacle tripped SPECIFICATIONS DL5000H D Generator manufacturer WINCO Inc Part number 15359 039 Rotor resistance 0 83 Ohms Stator resistance G1 N 0 6...

Page 14: ...3310 00 14 60707 126 WIRING DIAGRAMS...

Page 15: ...e repaired or replaced For warranty service return the product within 24 months from the date of purchase transportation charges prepaid to your nearest WINCO Authorized Service Center or to WINCO Inc...

Page 16: ...RER S WARRANTY COVERAGE The evaporative emission control system is warranted for two years If any evaporative emission related parts on your equipment are defective the parts will be repaired or repla...