background image

Dortmund, 

WILO SE

44263 Dortmund - Germany

(Die Seriennummer ist auf dem Typenschild des Produktes nach Punkten b) & c) von §1.7.4.2 
und §1.7.3 des Anhanges I der Maschinenrichtlinie angegeben. / The serial number is marked 
on the product site plate according to points b) & c) of §1.7.4.2 and §1.7.3 of the annex I of 
the Machinery directive. / Le numéro de série est inscrit sur la plaque signalétique du produit 
en accord avec les points b) & c) du §1.7.4.2 et du §1.7.3 de l’annexe I de la Directive 
Machines.)

Yonos ECO … BMS

Division HVAC
Quality Manager - PBU Circulating Pumps
WILO SE

D-44263 Dortmund

and with the relevant national legislation,

EN 16297-2

Bevollmächtigter für die Zusammenstellung der technischen Unterlagen ist:

EN 16297-1

et aux législations nationales les transposant,

EU/EG KONFORMITÄTSERKLÄRUNG

EU/EC DECLARATION OF CONFORMITY
DECLARATION DE CONFORMITE UE/CE

Als Hersteller erklären wir hiermit, dass die Nassläufer-Umwälzpumpen der Baureihe

We, the manufacturer, declare that these glandless circulating pump types of the series
Nous, fabricant, déclarons que les types de circulateurs de la série

in der gelieferten Ausführung folgenden einschlägigen Bestimmungen entsprechen :

In their delivered state comply with the following relevant directives : 
dans leur état de livraison sont conformes aux dispositions des directives suivantes :

und entsprechender nationaler Gesetzgebung,

_ Maschinenrichtlinie 2006/42/EG

EN 809+A1

sowie auch den Bestimmungen zu folgenden harmonisierten europäischen Normen :

comply also with the following relevant harmonized European standards :
sont également conformes aux dispositions des normes européennes harmonisées suivantes :

EN 61800-3+A1:2012

EN 60335-2-51

N°2118033.02

(CE-A-S n°4146382)

H. HERCHENHEIN

Person authorized to compile the technical file is :

Personne autorisée à constituer le dossier technique est :

Senior Vice President - Group ITQ

_ Machinery 2006/42/EC
_ Machines 2006/42/CE

und gemäss Anhang 1, §1.5.1, werden die Schutzziele der Niederspannungsrichtlinie 2014/35/EU ab 20 April 2016 eingehalten

and according to the annex 1, §1.5.1, comply with the safety objectives of the Low Voltage Directive 2014/35/EU from April 20th 2016
et, suivant l'annexe 1, §1.5.1, respectent les objectifs de sécurité de la Directive Basse Tension 2014/35/UE à partir du 20/04/2016

_ Produits liés à l'énergie 2009/125/CE

Nach den Ökodesign-Anforderungen der Verordnung 641/2009 für Nassläufer-Umwälzpumpen , die durch die Verordnung 622/2012 geändert wird

This applies according to eco-design requirements of the regulation 641/2009 for glandless circulators amended by the regulation 622/2012
suivant les exigences d'éco-conception du règlement 641/2009 pour les circulateurs, amendé par le règlement 622/2012

_ Elektromagnetische Verträglichkeit-Richtlinie 2014/30/EU ab 20 April 2016

_ Electromagnetic compatibility 2014/30/EU from April 20th 2016
_ Compabilité électromagnétique 2014/30/UE à partir du 20 avril 2016

_ Richtlinie energieverbrauchsrelevanter Produkte 2009/125/EG

_ Energy-related products 2009/125/EC

(MKMXEPYRXIVWGLVMIFIR

ZSR

LSPKIVLIVGLIRLIMR$[MP

SGSQ

(EXYQ

Summary of Contents for Wilo-Yonos ECO BMS

Page 1: ...ng en Installation and operating instructions fr Notice de montage et de mise en service nl Inbouw en bedieningsvoorschriften it Istruzioni di montaggio uso e manutenzione sv Monterings och skötselanvisning no Monterings og driftsveiledning fi Asennus ja käyttöohje pl Instrukcja montażu i obsługi ...

Page 2: ...Fig 1 Fig 2a Fig 2b ...

Page 3: ...Fig 3a Fig 3b Fig 3c Fig 3d Fig 3e Fig 4 PE N L ...

Page 4: ...Fig 5 Fig 6 H max H H min Hs Q Hs 1 2 H max H H min Hs Q Fig 7 nmax n 1 min nmin Off 1 2 3 10 U V ...

Page 5: ... instructions contain basic information which must be adhered to during installation operation and maintenance For this reason these operating instructions must without fail be read by the service technician and the responsible specialist operator before installation and commissioning It is not only the general safety instructions listed under the main point safety that must be adhered to but also...

Page 6: ...ntended for use by persons including children with reduced phys ical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person respon sible for their safety Children should be supervised to ensure that they do not play with the appliance If hot or cold components on the product the unit lead...

Page 7: ...t and interim storage can cause damage to the product and injury to personnel The pump and its packaging must be protected against moisture frost and mechanical damage during transport and interim storage Packaging that has become weakened loses its strength and call allow the product to fall out causing injury to personnel When the pump needs to be transported it may be carried only by the motor ...

Page 8: ...mixtures with glycol the conveying data of the pump should be cor rected to those for the higher viscosity depending on the percentage mixing ratio Only use brand name goods with corrosion protection inhibi tors comply with the manufacturer s specifications and safety data sheets The pump manufacturer s approval must be obtained for the use of other fluids Ethylene propylene glycol with corrosion ...

Page 9: ... the pump suction port in order to avoid cavitation noises at fluid temperature TMed The values apply up to 300 m above sea level addition for higher locations 0 01 bar 100 m increase in height 5 3 Scope of delivery Pump assembly 2 gaskets Control cable 1 5 m for SSM and 0 10V connection connected to pump at the factory Wilo Connector included Two piece thermal insulation shell Material EPP polypr...

Page 10: ...1 item 3 The control mode Dp v is active Constant differential pressure setting range Dp c Fig 1 item 2 The control mode Dp c is active Setting range Ext In Fig 1 item 1 External speed adjustment by 0 10V analogue input 6 2 2 Differential pressure control modes Variable differential pressure Dp v The electronics change the differential pressure setpoint to be maintained by the pump in linear form ...

Page 11: ...rce on the control module of the pump is to be avoided The mains and control cable of the Yonos ECO BMS series can only be connected at the factory Subsequent installation is not possible Never pull on the pump cable Do not kink the cable Do not place any objects on the cable 7 1 Installation WARNING Risk of injury Incorrect installation can result in personal injury There is a crushing hazard The...

Page 12: ... is horizontal and not under strain see the installation positions shown in Fig 2a 2b Make sure that it is possible to install the pump with the correct flow direction cf Fig 2a 2b The flow direction symbol on the pump housing indicates the direction of flow Make sure that it is possible to install the pump in the permitted installation position cf Fig 2a 2b If required turn the motor including co...

Page 13: ...ump may only be started after 5 minutes have elapsed due to the dan gerous residual contact voltage Check whether all connections including potential free contacts are voltage free If the control module cable is damaged do not operate the pump If setting and operating elements are improperly removed from the control module there is a danger of electric shock if interior electrical components are t...

Page 14: ...nt device consider the number of pumps con nected and their rated motor currents All connection cables must be installed so that they do not touch the pipe and or the pump or motor housing Earth the pump installation in accordance with the regulations L N Mains supply voltage 1 230 VAC 50 60 Hz DIN IEC 60038 7 2 1 Installation dismantling of the Wilo Connector Disconnect the connecting cable from ...

Page 15: ...500 000 switching cycles during the serv ice life 80 000 operating hours 8 Commissioning Do not fail to observe the danger information and warnings in Chapters 7 8 4 and 9 Prior to commissioning the pump check that it was installed and connected correctly 8 1 Filling and venting NOTE Incomplete venting will result in noises in the pump and unit Prime and vent the unit correctly The pump rotor room...

Page 16: ...oiler refriger ating machine any heat exchanger distri bution line up to 1st branch 2 Primary circuits with high pressure loss Dp v Heating ventilation air condi tioning systems with resistance in the generator distribution circuit 25 of the resistance in the transfer section room radiator thermostatic valve 1 Two pipe system with thermostatic zone valves and high user authority HN 2 m Converted g...

Page 17: ...on the system disconnect the pump from the power supply and make sure it cannot be switched back on by unauthorised persons Work on the pump may only be started after 5 minutes have elapsed due to the dan gerous residual contact voltage Check whether all connections including potential free contacts are voltage free The pump may still be live even in voltage free state The drive rotor induces a da...

Page 18: ...age to property in the event of incorrect dismantling It is not permitted to remove the rotor unit comprising the separating can bearing plate rotor and impeller from the motor housing If the unit consisting of impeller bearing plate rotor and separating can is pulled out of the motor without permission persons with medical aids such as cardiac pacemak ers insulin pumps hearing aids implants or si...

Page 19: ...f and restart the motor Motor blocking e g due to deposits Motor restarts after a delay After 5 unsuccessful starts the motor is switched off perma nently If the motor is blocked a maxi mum of 5 restarts are initiated at 30 second intervals If the motor is still blocked it is switched off permanently This can only hap pen if the power is disconnected for longer than 30 seconds and then switched on...

Page 20: ...ails themotorisshutoff A restart is initiated after 30 sec onds After it has been switched off fivetimesthemotoris shutoff permanently This can only be reset if the power is disconnected for 30 seconds The SSM relay is active as long as the internal error counter is not ZERO Dry run Venting faulty Motor restarts after a delay After being exposed to dry run ning conditions for a certain time frame ...

Page 21: ...y occurs once n 1 N Allowed number of faults If there is a restricted fault rate the counter is only reset if a fault no longer occurs within 30 seconds tn Otherwise the mains voltage must be disconnected for 30 seconds in order to restart the pump Auto reset Yes the number of allowed faults is unrestricted The software ensures a restart of the pump after the delay time No the number of allowed fa...

Page 22: ...dervoltage 100 ms 20 ms no restrictions yes 30 s open Response time 1 35 s Mains overvoltage 100 ms 20 ms no restrictions yes 30 s open Motor blocking 10 s 30 s 5 no 30 s open Defective syn chronous run 10 s 5 s no restrictions yes 30 s open Motor overload 60 s 30 s no restrictions yes 30 s open Short circuit earth leakage 6 μs 1 s 25 no 30 s open Contact winding error 10 s 30 s 5 no 30 s open Dry...

Page 23: ...the packaging or the accompanying documentation It means that the electrical and electronic products in question must not be disposed of along with domestic waste To ensure proper handling recycling and disposal of the used products in question please note the following points Only hand over these products at designated certified collecting points Observe the locally applicable regulations Please ...

Page 24: ...zu folgenden harmonisierten europäischen Normen comply also with the following relevant harmonized European standards sont également conformes aux dispositions des normes européennes harmonisées suivantes EN 61800 3 A1 2012 EN 60335 2 51 N 2118033 02 CE A S n 4146382 H HERCHENHEIN Person authorized to compile the technical file is Personne autorisée à constituer le dossier technique est Senior Vic...

Page 25: ...t ovat seuraavien eurooppalaisten direktiivien määräysten sekä niihin sovellettavien kansallisten lakiasetusten mukaisia WILO SE izjavljuje da su proizvodi navedeni u ovoj izjavi u skladu sa sljede im prihva enim europskim direktivama i nacionalnim zakonima WILO SE parei kia kad ioje deklaracijoje nurodyti gaminiai atitinka i Europos direktyv ir jas perkelian i nacionalini statym nuostatus WILO SE...

Page 26: ...eskrivs i följande intyg överensstämmer med bestämmelserna i följande europeiska direktiv och nationella lagstiftningar som inför dem WILO SE WILO SE estne prehlasuje e výrobky ktoré sú predmetom tejto deklarácie sú v súlade s po iadavkami nasledujúcich európskych direktív a odpovedajúcich národných legislatívnych predpisov 2006 42 2004 108 2009 125 Strojových zariadeniach 2006 42 ES Elektromagnet...

Page 27: ...6HJUDWH 0 7 ZLOR LWDOLD ZLOR LW D DNKVWDQ 2 HQWUDO VLD OPDW 7 LQIR ZLOR N RUHD 2 3XPSV WG DQJVHR XVDQ 7 ZLOR ZLOR FR NU DWYLD 2 DOWLF 6 5LJD 7 LQIR ZLOR OY HEDQRQ 2 121 6 5 GHLGHK HEDQRQ 7 LQIR ZLOR FRP OE LWKXDQLD 2 LHWXYD 8 9LOQLXV 7 PDLO ZLOR OW 0RURFFR 2 0DURF 6 5 DVDEODQFD 7 FRQWDFW ZLOR PD 7KH 1HWKHUODQGV 2 1HGHUODQG 9 1 HVW DDQ 7 LQIR ZLOR QO 1RUZD 2 1RUJH 6 2VOR 7 ZLOR ZLOR QR 3RODQG 2 3RO...

Page 28: ...WILO SE Nortkirchenstraße 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com Pioneering for You ...

Reviews: