• Shut-off devices must always be installed in front of and behind the 

pump in order to avoid having to drain the complete system when the 
pump is inspected or replaced.

NOTE
A settling section must be provided before and after the pump, in the 
form of a straight pipe. The length of this settling section should be at 
least 5 x DN of the pump flange (Fig. 10). This measure serves to avoid 
flow cavitation.

• The lantern has an opening on the underside which allows a drain pipe 

for condensation water/condensate to be connected (e.g. when used 
in air-conditioning or cooling systems). The condensate generated 
can then be effectively drained.

• The pipes and pump must be free of mechanical stress when installed. 

The pipes must be fastened in such a way that the pump does not 
bear the weight of the pipes.

• The bleed valve (Fig. 1/2/3, Item 1.31) must always face upwards.
• All installation positions except for “motor facing down” are allowed.

NOTE
The installation position with horizontal motor shaft is permitted 
for the IL and DL series only up to a motor power of 15 kW (Fig. 11). 
A motor support is not necessary. Only the installation position with 
vertical motor shaft is intended for a motor power >15 kW. BL series 
monobloc pumps are to be mounted on a sufficiently strong base or 
mounting brackets (Fig. 12).

NOTE
The motor terminal box must not face downward. If necessary, the 
motor or motor impeller unit can be rotated once the hexagon head 
bolts have been loosened. While rotating the motor or motor impeller 
unit, ensure that the housing O-ring seal does not become damaged.

NOTE
When pumping out a tank, ensure that the fluid level is always high 
enough above the suction port of the pump so that the pump never 
runs dry. The minimum intake pressure must be maintained.

NOTE
In the case of insulated systems, only the pump housing may be insu-
lated, not the lantern, motor and motor (Fig. 1/2/3, Item 1.3 to 2).

7.2

Electrical connection

Safety

DANGER! Risk of fatal injury!
A fatal shock may occur if the electrical connection is not made 
correctly.

• Only allow the electrical connection to be made by an electrician 

approved by the local electricity supplier and in accordance with 
the local regulations in force.

• Observe the installation and operating instructions for the acces-

sories!

Fig. 10: Settling section before and after the pump

r

5 x DN

d

s

 2,5 · (d · 2s)

Fig. 11: IL/DL

DL

IL

Fig. 12: BL

Summary of Contents for Wilo-CronoBloc-BL

Page 1: ...Twin DL Wilo CronoBloc BL Pioneering for You 2 136 319 Ed 02 2013 11 Wilo de Einbau und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service nl Inbou...

Page 2: ......

Page 3: ...Fig 1 IL Fig 2 DL...

Page 4: ...Fig 3 BL...

Page 5: ...de Einbau und Betriebsanleitung 3 en Installation and operating instructions 22 fr Notice de montage et de mise en service 41 nl Inbouw en bedieningsvoorschriften 60...

Page 6: ...Shipping 24 3 2 Attachment 24 4 Intended use 25 5 Product information 25 5 1 Type key 25 5 2 Technical data 26 5 3 Scope of delivery 27 5 4 Accessories 27 6 Description and function 27 6 1 Description...

Page 7: ...oses its validity 2 Safety These operating instructions contain basic information which must be adhered to during installation and operation For this reason these operating instructions must without f...

Page 8: ...lack of expe rience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Childrenshould be supervised to ensur...

Page 9: ...proper transport can lead to personal injury The pump must be transported using approved load bearing equip ment This is to be attached to the pump flanges and if necessary to the outer motor diameter...

Page 10: ...on is only possible with the corre sponding special versions motor with standby heating and fan cover protective roof see section 7 3 on page 32 CAUTION Risk of damage Impermissible substances in the...

Page 11: ...class F Protection class 55 Pipe and pressure measurement connec tions Flange PN 16 in accordance with DIN EN 1092 2 with pressure measure ment connections Rp 1 8 in accordance with DIN 3858 Approved...

Page 12: ...p operation IL The pump housing has an INLINE construction i e the flanges on the suction and pressure sides lie along a centre line Fig 6 All pump housings are provided with a pump base Mounting on a...

Page 13: ...rallel operation 0 55 51 54 54 57 0 5 51 54 60 63 1 1 53 56 60 63 1 5 55 58 67 70 2 2 59 62 67 70 3 59 62 67 70 4 59 62 67 70 5 5 63 66 71 74 7 5 63 66 71 74 11 65 68 74 77 15 65 68 74 77 18 5 71 74 7...

Page 14: ...y 10 of the maximum flow rate must be ensured at all times 7 1 Installation The motor terminal box must not face downward If necessary the motor or motor impeller unit can be rotated once the hexagon...

Page 15: ...r support is not necessary Only the installation position with vertical motor shaft is intended for a motor power 15 kW BL series monobloc pumps are to be mounted on a sufficiently strong base or moun...

Page 16: ...Position the threaded cable connec tion or lay the cables accordingly to ensure that no drips can run into the module Non assigned threaded cable connections must remain sealed with the plugs provided...

Page 17: ...used to protect the motor windings against con densation water inside the motor The standby heating is connected to the terminals HE HE in the ter minal boxes connection voltage 1 230 V 50 Hz NOTE Th...

Page 18: ...en opening the vent screw WARNING Risk of burns or freezing to the pump when body parts come into contact with the pump Depending on the pump or system operating conditions fluid tem perature the enti...

Page 19: ...be reinstalled WARNING Risk of injury due to the weight of the pump The pump itself and the parts of pump can be extremely heavy Falling parts pose a risk of cuts crush injuries bruises or impacts wh...

Page 20: ...3 Item 5 on the motor flange and lift the drive off the pump with suitable hoisting gear On BL pumps the adapter ring comes loose Fig 3 Item 8 By loosening the lantern fastening screws Fig 1 2 3 Item...

Page 21: ...opening the vent screw Fig 1 2 3 Item 1 31 DANGER Risk of scalding Due to high fluid temperatures there is a risk of scalding If the fluid is hot allow it to cool down before performing any work NOTE...

Page 22: ...m 10 Installation instructions Impeller Shaft M10 M12 M16 30 60 100 Pump housing Lantern M16 100 Tighten evenly and diagonally Lantern Motor M10 M12 M16 35 60 100 Coupling M6 10 9 M8 10 9 M10 10 9 M12...

Page 23: ...o customer service or a spe cialised service centre and serviced if necessary Motor protection switch has triggered Throttle the pump to the rated volume flow on the pressure side Motor protection swi...

Page 24: ...No Part Details No Part Details 1 Exchange set complete 1 1 Impeller set with 1 5 Coupling complete 1 11 Nut 2 Motor 1 12 Spring washer 3 Pump housing set with 1 13 Impeller 1 14 O ring 1 14 O ring 3...

Page 25: ......

Page 26: ......

Page 27: ...chkeit Richtlinie 2004 108 EG Electromagnetic compatibility directive Directive compatibilit lectromagn tique Richtlinie energieverbrauchsrelevanter Produkte 2009 125 EG Energy related products direct...

Page 28: ...dla produkt w zwi zanych z energi 2009 125 WE 2009 125 Pou it 50Hz t f zov induk n motory s klecov m rotorem jednostupJov vyhovuj po adavkQm na ekodesign dle na zen 640 2009 Stosowane elektryczne sil...

Page 29: ...20 27442100 Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 Ireland WILO Ireland T 353 61 227566 Italy Borromeo Milano T 39 25538351 Kazakhstan WILO Central Asia 050002 Almaty T 7...

Page 30: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: