Wilo SP Series Submersible Sewage Pumps WCC
WCC17-20.50
Installation and operating instructions
Page 1: ...Wilo SP Series Submersible Sewage Pumps WCC WCC17 20 50 Installation and operating instructions...
Page 2: ...nol etc Do not use in the presence of flammable or explosive vapors Using this pump with or near flammable liquids can cause explosion or fire resulting in serious personal injury or death and or prop...
Page 3: ...personal injury and or property damage 6 Check that all hose connections are tight to minimize leaks 7 Connect the pump DIRECTLY to a grounded GFCI outlet 8 Extension cords may not deliver sufficient...
Page 4: ...he pump is not running Check valve should be a free flow valve that will easily pass solids NOTICE For best performance of check valve when handling solids do not install it with discharge angled more...
Page 5: ...shut off the pump before it is damaged When the motor has cooled sufficiently the overload protector will reset and the motor will restart NOTICE If the overload protector stops the pump repeatedly di...
Page 6: ...ipped breaker 3 Plug disconnected 4 Corroded plug 5 Thermal overload 6 Clogged impeller 7 Motor failed 8 Float failed 9 Water level too low 10 Tangled switch 1 Replace fuse 2 Reset breaker 3 Secure pl...
Page 7: ...arge 5 Impeller broken 1 Clean out debris 2 Inspect check valve and make sure it s properly installed 3 Remove the blockage 4 Remove debris 5 Replace impeller Pump starts and stops too often 1 Backflo...