English
Installation and operating instructions Wilo-VeroLine-IP-E, VeroTwin-DP-E
87
8.7
Menu elements reference
The following table gives an overview of the available elements of all
menu levels. The menu number and the element type are designated
separately, and the function of the element is explained. If applicable,
there is information about the setting options of the individual elements.
NOTE:
A few elements are hidden under certain conditions and are therefore
skipped in the menu navigation.
If, for example, the external setpoint adjustment under menu number
<5.4.1.0> is set to “OFF”, the number <5.4.2.0> will be hidden. Menu
number <5.4.2.0> will only be visible if menu number <5.4.1.0> has
been set to “ON”.
No.
Designation
Type
Symbol Values/explanations
Display conditions
1.0.0.0
Setpoint
Setting/display of the setpoint
(for further information, see
chapter 8.6.1 “Adjusting the
setpoint” on page 83)
2.0.0.0
Control mode
Setting/display of the control
mode
(for further information, see
chapters 6.2 “Control modes” on
page 65 and 9.4 “Setting the
control mode” on page 95)
Constant speed control
Constant control
Δ
p-c
Variable
Δ
p-v control
PID control
2.3.2.0
Δ
p-v gradient
Setting the gradient of
Δ
p-v
(value in %)
Not displayed for all pump
types.
3.0.0.0
Pump on/off
ON
Pump switched on
OFF
Pump switched off
4.0.0.0
Information
Information menus
4.1.0.0
Actual values
Display of current actual values
4.1.1.0
Actual values sen-
sor (In1)
Depending on current control
mode
Δ
p-c,
Δ
p-v: Value H in m
PID control: Value in %
Not displayed for manual
control mode
4.1.3.0
Power
Current power input P
1
in W
4.2.0.0
Operating data
Display of operating data
The operating data refer to
the electronic module cur-
rently being operated
4.2.1.0
Operating hours
Sum of the pump's active hours
of operation
(meter can be reset by infrared
interface)
4.2.2.0
Consumption
Energy consumption in
kWh/MWh
±
±
±