background image

English

8

WILO SE 10/2021

NOTE: If the pump is being operated with the 
wrong direction of rotation, a reduction in the 
volume flow occurs.
If the direction of rotation is incorrect, 2 phases of 
the mains connection (in the switchbox or on the 
contact maker) have to be changed.

8.2 Commissioning

CAUTION! Danger of material damage!
Danger of damage to the mechanical seal. Never 
allow the pump to run dry, even for a short time.

• Check all electrical connections, the electrical 

protection, and fuses once again.

• Check the current consumption intermittently 

and compare with the values on the name plate.

Never exceed the motor nominal current (In) 
permissible for the motor (see name plate)

• Check the voltage with the motor running.

Permissible tolerance: ± 10 %.

• Vent the pressure ports in order to avoid pressure 

surge during start-up.

• Close the valves during initial commissioning to 

minimise fluid hammers due to start-up and 
briefly increased amounts of sand in the fluid (dur-
ing initial use of the well).

• Do not start the pump more than 20 times an hour 

(danger of overheating).

• Ensure that the pump is only operated within the 

area printed in bold of the curve illustrated in the 
catalogue. Under no circumstances operate the 
pump to the right or left beyond the curve area 
printed in bold.

• Never operate the pump for an extended period 

with the valve closed.

8.3 Fluid temperature

Submersible pumps may, at nominal current, be 
operated between min. 3 °C and max. 30 °C. In 
order to guarantee effective cooling, the circula-
tion flow velocity of the cooling water over the 
surface of the motor must be at least 10 cm/sec. 
for 4" motors and 16 cm/sec. for 6" motors.

In order to guarantee motor cooling at higher 
temperatures, the flow rate must be reduced pro-
portionally to the motor power (see table above)
NOTE: Do not operate the motors where the fluid 
temperature exceeds 55 °C!

8.4 Checking and correcting the motor filling level 

(Fig. 6)

The checking and correction of the filling level of 
the motor fluid must be performed by qualified 
personnel. The TWI4 motor may only be refilled by 
the manufacturer. 
• Lie the motor horizontally with opening (C) fac-

ing upwards

• Insert the pin gauge into the drilling (E) on the 

diaphragm housing and check the diaphragm 
level (D) -see table 1-. The notch on the pin 
gauge must be level with the outer edge of the 
drilling.

• If the water lever is too low, remove the filter (C) 

(for TWI6 only).

• Place a filled syringe on the valve and inject 

water into the motor.

• To vent the valve, briefly press the valve in with 

the pin gauge until water that is free of bubbles 
emerges. Caution over pressure!

• Continue filling with water until the diaphragm 

level (D) has been reached.

• Re-insert the filter (C).

9 Maintenance

Maintenance and repairs may only be carried out 
by qualified experts!
DANGER! Risk of fatal injury!
When working on electrical equipment, there is 
a risk of a fatal shock.

• The pump should be electrically isolated and 

secured against unauthorised switch-on during 
any maintenance or repair work.

• Any damage to the connecting cable should 

always be rectified by a qualified electrician 
only.

NOTE: No particular maintenance necessary dur-
ing normal operation.

Min. required volume flow for motor cooling up to a water 
temperature of 30 °C

Inside diameter of the 
side of the well or cooling 
jacket pipe 

4" motor

6" motor

102 mm (4")

0.30 m³/h

--

127 mm (5")

1.60 m³/h

--

152 mm (6")

3.00 m³/h

2.10 m³/h

178 mm (7")

4.60 m³/h

6.00 m³/h

203 mm (8")

6.90 m³/h

10.30 m³/h

Fluid temperature

Water tempera-
ture

Adjustment (%) of the nominal cur-
rent from 0.37 kW to 5.5 kW

35 °C

95 %

40 °C

95 %

45 °C

90 %

50 °C

80 %

55 °C

70 %

Type of motor

Test dimen-
sion (D)

Tolerance

4" 10 mm

+/- 

2 mm

6" (AISI 304 SS)

59 mm

+/- 2 mm

6" (AISI 316 SS)

19 mm

+/- 2 mm

Summary of Contents for Sub TWI 4

Page 1: ...Wilo Sub TWI 4 6 Pioneering for You 4 069 717 Ed 04 2021 10 Wilo en Installation and operating instructions...

Page 2: ...Fig 1 Fig 2 Fig 3 M 1 L a b c d N M 3 U V W d b c a L 1 L 2 L 3 P E a d b c c a b M 3 Fig 4 Fig 5 Fig 6 0 30 1 00 m 1 6 7 5 4 3 2 8 9 10 11 12 13 Min 0 20 E E C D...

Page 3: ...blems 2 2 Personnel qualifications The installation personnel must have the appro priate qualifications for this work 2 3 Danger in the event of non observance of the safety instructions Non observanc...

Page 4: ...roduct The pumps are not suitable for water containing coarsecontaminantssuchasfibresorflammable liquids or for use in potentially explosive areas Correct use of the pump installation also includes fo...

Page 5: ...formation The ramp time for the start stop procedures between 0 and 30 Hz should be set to maximum 1 sec The ramp time between 30 Hz and the nominal frequency should be set to maximum 3 sec During sta...

Page 6: ...al non return valve and shut off valve on the borehole output CAUTION Danger of material damage When the water pressure is raised 180 m Ws a non return valve must be installed directly at the pump out...

Page 7: ...55 92 147 30 00 67 108 37 00 89 45 00 73 Cable weight kg m 0 20 0 25 0 30 0 40 0 65 0 85 Diameters and max lengths of the cable 6 motors for star delta start Motor version Motor Cable kW 4 x 1 5 mm 4...

Page 8: ...rtionally to the motor power see table above NOTE Do not operate the motors where the fluid temperature exceeds 55 C 8 4 Checking and correcting the motor filling level Fig 6 The checking and correcti...

Page 9: ...e switch setting of the triggering current strength and compare it with the nominal current being drawn The pump starts too often Reduce the number of starting procedures danger of motor overheating a...

Page 10: ......

Page 11: ......

Page 12: ...Pioneering for You WILO SE Wilopark 1 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com Local contact at www wilo com contact...

Reviews: