6 Operation

System filling and venting

The pump may need venting e.g. if the
heating and pump are working but the
heating element remains cold. If there
is air in the pump chamber, the pump
will not pump water. 
Carefully fill the unit with water. 
Solar thermal systems must be filled
with ready for use mixtures. The pump
must not be used to mix the medium
in the system.
The pump is normally vented automa-
tically after a short operatinal period.
Short-term dry running will not dama-
ge the pump. If it becomes necessary
to vent the pump, please observe the
following procedure:
– Switch off pump,

Risk of burning if the pump
is touched!

Depending on the operating
condition of the pump and/or
installation (fluid temperature)
the pump/motor can become
very hot.

– Close the valve on the discharge

side.

Risk of scalding!

Depending on the fluid tem-
perature and the system pres-
sure, if the vent screw is com-
pletely loosened hot liquid or
vapour can escape or even
shoot out at high pressure.

– Carefully loosen and fully remove

the vent plug with a suitable 
screwdriver (Fig. 9).

– Carefully push pump shaft back

several times with screwdriver.

– Protect all electrical parts against

the leaking water.

– Switch-on pump.

It is possible that the
pump blocks with the
vent plug open, de-
pending on the system
pressure.

– After 15...30 s tighten the vent plug. 
– Re-open isolating valve,

Speed setting

If the rooms cannot be sufficiently
heated, the speed of the pump may be
too low. In this case you will need to
switch to a higher speed. 
If, on the other hand, the pump is set
at too high a speed, flow noise may
occur in the lines and in particular at
throttled thermostatic valves. This can
be rectified by switching to a lower
speed. 
The speed is changed by means of 
a rotary button at the terminal box.
3 represents the lowest and 1 the 
highest speed. 

7 Maintenance

Prior maintenance or repair
work switch off the pump and
secure against unauthorized
switching.

ATTENTION!

Summary of Contents for Star AC Series

Page 1: ...taggio uso e manutenzione E Instrucciones de instalaci n y funcionamiento S Installations och sk tselinstruktioner FIN Huolto ja k ytt ohje H Be p t si s zemeltet si utas t s PL Instrukcja monta u i o...

Page 2: ......

Page 3: ......

Page 4: ...N L N L N L N L 1 230 V 50 Hz a b c N L...

Page 5: ......

Page 6: ...instalaci n y funcionamiento 44 S Installations och sk tselinstruktioner 52 FIN Huolto ja k ytt ohje 59 H Be p t si s zemeltet si utas t s 66 PL Instrukcja monta u i obs ugi 74 CZ N vod k mont i a ob...

Page 7: ...SG for geothermal systems Type AC for air conditioning units and cold water distribution Terms Fig 1 1 Suction joint 2 Condensate outlet 3 Pump housing 4 Pressure joint 5 Terminal box 6 Cable entry 7...

Page 8: ...strictly adhe red It is therefore imperative for the installer and operator to carefully read these instructions prior to installation and commissioning Please observe not only the safety directions u...

Page 9: ...e use of any other parts may invalidate claims invoking the liability of the manufactu rer for any consequences Unauthorised operating methods The operating safety of the pump or installation supplied...

Page 10: ...water distribution In the AC I I inline pump the pump housing is designed inline i e suction and pressure connections are in line The AC O O offline pump is equipped with axial suction and radial disc...

Page 11: ...e switch The width of the contact gap must be at least 3 mm To guarantee protection against dripping water and the strain relief of the PG screwed joint a connec ting cable of suitable external dia me...

Page 12: ...res sure if the vent screw is com pletely loosened hot liquid or vapour can escape or even shoot out at high pressure Carefully loosen and fully remove the vent plug with a suitable screwdriver Fig 9...

Page 13: ...the slotted end of the shaft with a screwdriver Fig 9 At high water temperatures and system pressure close isolating valves before and after the pump First allow pump to cool down Noisy pump operatio...

Page 14: ...154...

Page 15: ...06 95 EG Low voltage directive Directive basse tension und entsprechender nationaler Gesetzgebung and with the relevant national legislation et aux l gislations nationales les transposant Angewendete...

Page 16: ...sk kompatibilitet 2004 108 EG EG Lavspenningsdirektiv 2006 95 EG Anvendte harmoniserte standarder s rlig 1 FIN CE standardinmukaisuusseloste Ilmoitamme t ten ett t m laite vastaa seuraavia asiaankuulu...

Page 17: ...il wilo lt The Netherlands WILO Nederland b v 1551 NA Westzaan T 31 88 9456 000 info wilo nl Norway WILO Norge AS 0975 Oslo T 47 22 804570 wilo wilo no Poland WILO Polska Sp z o o 05 090 Raszyn T 48 2...

Page 18: ...d T 0231 4102 7900 T 01805 W I L O K D 9 4 5 6 5 3 F 0231 4102 7126 kundendienst wilo com Erreichbar Mo Fr von 7 17 Uhr Wochenende und feier tags 9 14 Uhr elektro nische Bereitschaft mit R ckruf Garan...

Reviews: