![Wilo IF-Module Stratos Installation And Operating Instructions Manual Download Page 13](http://html1.mh-extra.com/html/wilo/if-module-stratos/if-module-stratos_installation-and-operating-instructions-manual_982786013.webp)
Installation and operating instructions Wilo-IF-Modules Stratos
27
English
5.2
Technical data
General data
Terminal cross-section
1.5 mm² finely stranded
Safety in accordance with
EN 60950
Up to mains voltage 230 V, configuration TN or TT
Contact input
Version
SELV, isolated
Earth reference
Shared with control input 0-10 V
Off-load voltage
Max. 10 V
Loop current
Approx. 10 mA
Contact output
Version
Potential-free
Load rating
30 V AC/60 V DC: 1 A AC1/DC1
Min. load
12 V DC, 10 mA
Control input 0-10 V
Version
SELV, isolated
Earth reference
Shared with contact input
Voltage range
0-10 V
Input resistance
> 100 k
Accuracy
5 % absolute
Dielectric strength
24 V DC