Installation and electrical connection
16
WILO SE 2020-05
6.4.5
Placing the lifting unit
1
1
Fig. 2:
Lifting unit top view
1
Fastening grooves for floor anchoring
Install lifting unit so as to protect against buoyancy and twisting. Anchor the lifting unit
to the floor for this.
‡
Preparatory tasks have been completed.
‡
Installation location prepared according to consulting documents.
‡
Suitable fixation material provided for the existing building ground.
NOTICE! Ob-
serve the information on the fixation material!
1. Place the lifting unit at the installation location and align to the pipework.
CAUTION! Secure the switchgear to the lifting unit to prevent it from falling
down. The switchgear may be destroyed if it falls down!
NOTICE! Lifting unit must be standing level!
2. Mark out the boreholes of the fastening grooves.
3. Place the lifting unit to one side.
4. Drill and clean the boreholes. Insert the dowels.
5. Lay out and align the insulation mat.
6. Position and align the lifting unit to the insulation mat.
7. Guide the fastening screw and disc through the fastening groove. Screw the
fastening screw into the dowel.
8. Attach the lifting unit to the floor.
9. Attach the switchgear to the wall so as to be overflow-proof (see switchgear in-
structions).
10.Lay the connection cable in accordance with regulations.
▶ Lifting unit installed so as to protect against buoyancy and twisting. Next step:
Connect the pressure pipe.
6.4.6
Connecting the pressure pipe
40...60 mm 1.5...2.4 in
1
2
3
4
5
6
7
8
Fig. 3:
Fit pressure connection
1
Lifting unit
2
Swing check valve with ventilation device
3
Pressure connection
4
Gate valve
5
Flange connector
6
Connecting hose, flexible
7
Pipe clamps
8
Pressure pipe
Observe the following information when connecting the pressure pipe:
ƒ
Pressure pipe must be DN 80 or DN 100!
ƒ
Flow rate in the pressure pipe: 0.7 m/s (2.3 ft/s) to 2.3 m/s (7.5 ft/s)!
ƒ
Reducing the pipe diameter is not permitted!
ƒ
All connections must be completely tight!
ƒ
Install the pressure pipe as a “pipe loop” to avoid backflow from the main public
sewer.
At its highest point, the bottom edge of the pipe loop must be above the locally de-
termined backflow level!
ƒ
Install the pressure pipe so that it is protected from frost.
ƒ
Install the gate valve.
‡
Lifting unit installed properly.
‡
Pressure pipe installed correctly according to consulting documents and perpen-
dicular to the pressure port.
‡
Assembly materials provided:
1x gate valve
1x connecting hose
4x pipe clamps
1. Install the gate valve on the pressure port.