Product description
en
Installation and operating instructions Wilo-DrainLift SANI-L
11
If the water drops below the high water level, the pump is deactivated once the follow-
up time has elapsed. The alarm signal is acknowledged automatically.
4.4
Operating principle
The sewage produced is channelled into the collection reservoir via the inlet pipe,
where it collects. When the water level reaches the switch-on level, the pump is
switched on. The collected sewage is pumped into the connected pressure pipe. When
the switch-off level is reached, the pump is deactivated after the set follow-up time. A
pump cycling occurs each time the pump is switched off.
When the high water level is reached, both pumps are switched on (forced switch-on).
The high water LED or display shows an alarm signal. Additionally, an audible alarm sig-
nal can be output via the internal buzzer. Furthermore, the output for the collective
fault signal (SSM) is activated.
4.5
Operation with frequency con-
verter
Operation on the frequency converter is not permitted.
4.6
Type key
Example:
DrainLift SANI-L.17T/4C
DrainLift
Product family
SANI
Sewage lifting unit
L
Size
17
Max. delivery head
T
Mains connection:
ƒ
M = 1~
ƒ
T = 3~
4
Version motor and switchgear:
ƒ
1 = operating mode: S3, switchgear: Control MS-L
ƒ
2 = operating mode: S1, switchgear: Control MS-L
ƒ
3 = operating mode: S3, switchgear: Control EC-L
ƒ
4 = operating mode: S1, switchgear: Control EC-L
C
Version for aggressive fluids
4.7
Technical data
Approved field of application
Max. intake per hour
7200 l (1902 US.liq.gal)
Max. pressure in the pressure
pipe
6 bar (87 psi)
Max. delivery head
See rating plate
Max. volume flow
See rating plate
Max. positive suction head
5 m (16.5 ft)
Fluid temperature
3 ... 40 °C (37 ... 104 °F), max. 65 °C (149 °F) for
5 min
Ambient temperature
3 ... 40 °C (37 ... 104 °F)
Motor data
Mains connection
ƒ
SANI-L...M/...: 1~230 V, 50 Hz
ƒ
SANI-L...T/...: 3~400 V, 50 Hz
Power consumption [P
1
]
See rating plate
Rated power [P
2
]
See rating plate
Rated current [I
N
]
See rating plate
Speed [n]
See rating plate
Activation type
Direct
Operating mode
(based on one pump)
ƒ
SANI-L.../
1
...: S3 10%/60 s
–
Cycle duration: 60 s
–
Activation period: 6 s
–
Downtime: 54 s
ƒ
SANI-L.../
4
...: S1
Protection class
IP68
Cable length to plug
1.5 m (5 ft)