Installation and operating instructions Wilo-IF-Modules Modbus, BACnet
29
English
8 Commissioning / functional test
• The following sections describe testing the functioning of the inputs/outputs.
It is recommended to test together with the connected system. The pump's
installation and operating instructions are needed for some settings.
8.1 General settings
• Set the bus address in the pump menu 5.2.3.0
• Set baud rate with parameter A in the pump menu 5.2.4.0 in accordance with
the following table:
Additional baud rates may be defined in the relevant protocol description.
Parameter
A
Baud rate
0
300
1
600
2
1200
3
2400
4
4800
5
9600
6
19200
7
38400
8
57600
9
115200