en
Installation and operating instructions • Wilo-Control MS-L • Ed.02/2022-05
25
3
Control MS-L2...
SSM
Alarm
16
15
14
13
12
11
Fig. 15:
Terminal strip sensors: external alarm
signal for high water
An external alarm signal (horn, flashing light, etc.) can be connected for the high water alarm:
•
Contact type: potential-free changeover contact
•
Contact load:
–
Minimum: 12 VDC, 10 mA
–
Maximum: 250 VAC, 1 A
Insert the connection cables laid by the customer through the threaded cable glands and se-
cure. Connect the wires to the terminal strip according to the connection diagram.
Switchgear
Normally open contact (NO) Normally closed contact
(NC)
Control MS-L1...
−
−
Control MS-L2...
Terminal 15/16
Terminal 14/15
6.6
Functions
The switchgear is equipped with the following functions. All functions are switched off at
the factory. The functions must be switched on as required.
Inputs/outputs
Control MS-L 1...
Control MS-L 1...-O
Control MS-L 1...-LS
Control MS-L 2...
Control MS-L 2...-O
Control MS-L 2...-LS
Internal buzzer
•
•
•
•
•
•
Pump kick
•
•
•
•
•
•
Service interval indicator
−
−
−
•
•
•
Monitoring operating parameters
−
−
−
−
−
•
Follow-up time
•
•
•
•
•
•
Adjustable switching points for pump ON and high water*
−
−
•
−
−
•
Key
• = available, − = not available
* The switching points can be selected from eight sets of parameters for the respective lift-
ing unit.
6.6.1
Internal buzzer
ON
DIP
1 2 3 4 5 6 7
8
Fig. 16:
DIP switch 1: internal buzzer
The internal buzzer can also issue audible warning messages in addition to the visual indic-
ator. Switch the internal buzzer on/off via DIP 7 on DIP switch 1:
•
“ON” position: Buzzer on
•
“OFF” position: Buzzer off
6.6.2
Pump kick
ON
DIP
1 2 3 4 5 6 7
8
Fig. 17:
DIP switch 1: Pump kick
To prevent prolonged standstill periods for the connected pumps, a periodic test run can be
performed (pump kick function). A 2 s test run takes place after a standstill period of 24 h for
the respective pump.
Switch the pump kick on/off via DIP 6 on DIP switch 1:
•
“ON” position: Pump kick on
•
“OFF” position: Pump kick off
6.6.3
Service interval indicator
A service interval indicator can be switched on to increase operational reliability. The time is
recorded continuously when the mains voltage is switched on. After the interval has
elapsed, a visual signal is emitted by means of the yellow LED on the front.
NOTICE! There
is no audible signal and the collective fault signal is not activated!
ON
DIP
1 2 3 4 5 6 7
9
Fig. 18:
DIP switch 2: Service interval indicator
Switch the desired interval on and off via DIPs 4 and 5 on DIP switch 2:
•
DIP 4 and 5 “OFF”: Service interval off
•
DIP 4 “ON”: ¼ year service interval
•
DIP 5 “ON”: ½ year service interval
•
DIP 4 and 5 “ON”: 1 year service interval
Contact customer service to reset the counter.
Summary of Contents for Control MS-L
Page 2: ...Control MS L https qr wilo com 1393...
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......