5 Product data
5.1 Type key
COHe - 2 MHI 2 04 - CE - T - 10
COHe = Boosting system with horizontal pumps
Operating mode of the boosting system :
2 = 2 pumps in cascade
3 = 3 pumps in cascade
Pump type :
MHI : Horizontal pump
Nominal flow per pump (m3/h)
Quantity of stages
Automatism :
CE : Electronic control
Power supply :
T : AC 3 phase 400V
Maximum working pressure :
10 : PN10 bars
5.2 Technical data
Maximum operating pressure
: 10 bars
Maximum water temperature
: +70°C
Maximum ambient temperature : +40°C
Three-phase voltage
: 50 Hz 230/400V
5.3 Scope of delivery
-
Booster
-
Control box or cabinet (separate from the booster set according to the type and power)
-
Installation instructions: booster, pump and automatism.
5.4 Accessories (compulsory).
- Diaphragm pressure tank must be sized according to installation
- Dry running sensor:
-
On a collection tank > float switch.
-
On public water mains > pressure switch.