Installation and electrical connection
zh-CHS
安装及操作说明 Wilo-Atmos TERA-SCH
65
Storage for more than three months
Additional precautionary measures:
ƒ
All rotating parts must be coated with a suitable protective medium to protect them
from rust.
ƒ
If the pump is to be stored for more than a year, consult the manufacturer.
6
Installation and electrical
connection
6.1
Personnel qualifications
ƒ
Electrical work: A qualified electrician must carry out the electrical work.
6.2
Operator responsibilities
ƒ
Observe locally applicable accident prevention and safety regulations of professional
and trade associations.
ƒ
Observe all regulations for working with heavy loads and under suspended loads.
ƒ
Provide protective equipment and ensure that the protective equipment is worn by
personnel.
ƒ
Avoid pressure surges!
Pressure surges can occur in long pressure pipes. These pressure surges can lead to
the destruction of the pump!
ƒ
Structural components and foundations must be of sufficient stability in order to
allow the device to be fixed in a secure and functional manner. The operator is
responsible for the provision and suitability of the building/foundation!
ƒ
Check that the available consulting documents (installation plans, design of the
operating space, inflow conditions) are complete and correct.
6.3
Preparing the installation
警告
Risk of personal injury and property damage due to improper handling!
• Never set up the pump unit on unfortified surfaces or surfaces that cannot bear
loads.
• The pump should only be installed after completion of all welding and soldering
work.
• Flush the pipe system if required. Dirt can cause the pump to fail.
ƒ
The pumps (in the standard version) must be protected from the weather and
installed in a frost/dust-free, well-ventilated environment that is not potentially
explosive.
ƒ
Mount the pump in a readily accessible place. This makes it easier to complete
inspections, maintenance (e.g. mechanical seal change) or replacement in the future.
ƒ
A travelling crane or a device for attaching hoisting gear should be installed above
the set-up site of large pumps.
6.4
Setting up the pump by itself
(variant B, Wilo variant key)
When installing a pump by itself, the required coupling guard and base frame of the
pump manufacturer should be used. In any case, all components must meet the
CE regulations. The coupling guard must be compatible with EN 953.
6.4.1
Selecting the motor
Select a motor with sufficient power.
Shaft power
< 4 kW
4 kW < P
2
< 10 kW
10 kW < P
2
< 40 kW
40 kW < P
2
Required
additional
power to
determine
motor rating
value P
2
25 %
20 %
15 %
10 %
表 7:
Motor/shaft power
Example:
ƒ
Duty point water: Q = 100 m
3
/h; H = 35 m
ƒ
Efficiency: 78 %