O p e r a t i n g - a n d I n s t a l l a t i o n M a n u a l B 3 8 0 - H a n s W i l m s G m b H & C o . K G
Fault
Cause
Remedy
Device starts, flame is formed,
control goes to fault after a few
seconds
Flame too dark, irregular or poor
combustion
Check the setting, check the filter
and nozzle for dirt
Photocell dirty, flame is not
detected
Clean photocell
Device starts, no flame formation,
control goes after a few seconds
on fault
Tank empty
Check tank level, refuel
Unclean, restless combustion,
smoke formation
Filter/nozzle dirty
Clean or replace the filter and
nozzle
Unsuitable or polluted fuel
Check the tank, empty and clean,
fill with clean heating oil EL
Device goes on fault after a long
runtime
Filters, oil pipes or tank ventilation
clogged
Check and clean
Lack of oxygen due to lack of
ventilation
Ensure sufficient ventilation, check
room size
Overheating of the device
Keep supply and exhaust air paths
clear, check fan and grille for
contamination, as well as setting
oil pressure / air volume and
nozzle size
Please note that maintenance and repair work may only be carried out by experts with appropriate
expertise. If in doubt, contact your dealer, your customer service center or the manufacturer!
Technical specifications are subject to changes without prior notice!
14. Technical Data
Type:
B 380
Order number:
1081380
Capacity:
111,0 kW / 95460 kcal/h / 379.000 BTU/h
Air volume:
3300 m³/h
Fuel consumption:
8,83 kg/h
Burner nozzle:
2,0 GpH 80°H Danfoss
Pump pressure:
13 bar
Voltage:
230 V / 50 Hz
Power consumption:
4,6 A
Rated current:
1,06 kW
Weight:
82 kg
Tank capacity:
105 l
Dimensions:
1605 x 685 x 930 mm
Diameter air outlet:
400 mm
Protection class:
IP 44
Page 10 of 15