background image

3.  The furnace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any 

pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa). 

Attention

: If one of the above procedures results in pressures in excess of 1/2 psig (14” w.c.; 3.5 kPa) on the furnace gas valve, 

it will result in a hazardous condition. 

 

High Altitudes (US Only) 

For altitudes/elevations above 2,000 feet (610 m), ratings should be reduced at the rate of 4-percent for each 1,000 feet (305 m) 
above sea level by reducing the manifold pressure at 8% rate on the gas supply. Maximum altitude allowed for installation is 
5500 feet (1680 m). 

 

High Altitudes (Canada Only) 

The furnace is tested according to CGA 2.17 M91 for installation between 0 and 4500 ft (0 and 1370 m) altitude. For 
altitudes/elevations above 2,000 feet (610 m), ratings should be reduced at the rate of 4-percent for each 1000 feet (305 m) 
above sea level by reducing the manifold pressure at 8% rate on the gas supply.  Maximum altitude allowed for installation is 
5500 feet (1680 m).  

 

First Firing the Furnace 

Start the furnace following the instructions given in the “Operating Instructions”.  The first lighting can be difficult because of the 
air trapped in the gas lines.  During initial firing of the furnace, residual manufacturing grease will bake out and smoke will occur 
which is not a health danger. To prevent nuisance and operation of fire alarms, ventilate the room for the first two hours of 
operation. 

 

Checking the Gas Inlet Pressure 

The gas inlet pressure can be measured by connecting a test gauge to the connection provided on the gas valve.  (Figure 8 - A)  
Once installation is complete, the gas inlet pressure must be checked.  The minimum gas inlet pressure must be as shown in 
“Technical Data”.  After checking the gas inlet pressure, disconnect the test gauge and firmly tighten the screw of the gauge 
connection, then check for gas leaks. 

 
Checking the Gas Manifold Pressure 

The gas manifold pressure can be measured by connecting a test gauge to the connection provided on the gas valve. (Figure 8 - 
B).  The furnace comes set from the factory at the correct manifold gas pressure.  After the installation is completed, the gas 
manifold pressure must be checked both in Hi and Lo input. Turn the control knob to switch the unit from Hi to Lo input.  The 
position of the knob in which this occurs depends on the actual room temperature.  The gas manifold pressure must be as 
shown in “Technical Data”.  Differences of plus or minus 0.1 in. w.c. are accepted.  If the Hi or Lo gas manifold pressures are 
different from the values given in the “Technical Data” or are more than 0.1 in. w.c., shut off the furnace and contact a qualified 
service technician. 
 
For instructions about adjustment of the manifold Hi and Lo pressures, see the "Servicing” section.  After checking the gas 
manifold pressure, disconnect the test gauge and tighten firmly the screw of the gauge connection, then check for gas leaks 
from it. 

 

 

Figure 8 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 743511

Page 1: ...losion may result causing property damage personal injury or loss of life Williams Furnace Co 250 West Laurel Street Colton CA 92324 U S A MODEL Natural Gas Only 0743512 MODEL Propane Gas Only 0743511...

Page 2: ...to local codes or in the absence of local codes the installation must conform to the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code CSA B149 1 Mobile Manufacture...

Page 3: ...ce technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water Safety Information for Users of LP Gas Propane LP Gas is a flammable g...

Page 4: ...iff test of the LP Gas is a good safety measure under any condition If at any time you do not smell the LP Gas odorant and you should assume you have a leak Then take the same immediate action recomme...

Page 5: ...as equipment in residential garages must be installed so that all burners and burner ignition devices are located not less than 18 inches 460 mm above the floor Such equipment shall be located or prot...

Page 6: ...m 3 As specified in CGA B149 installation codes 1991 F Clearance to outside corner 12 inches 30 cm minimum Note Local codes or regulations may require different clearances G Clearance to inside corner...

Page 7: ...is horizontal 6 Remove the casing from the furnace body unscrewing the two mounting screws Figure 3 7 Mount the largest tube diameter 4 inches 101 6 mm and the gasket on the unit frame with the screws...

Page 8: ...Each furnace should have its own manual gas cock A manual main gas cock should be located in the vicinity of the unit Where none exists or where its size or location is not adequate contact your local...

Page 9: ...h danger To prevent nuisance and operation of fire alarms ventilate the room for the first two hours of operation Checking the Gas Inlet Pressure The gas inlet pressure can be measured by connecting a...

Page 10: ...rty damage personal injury or loss of life OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this labe 2 Turn gas control knob clockwise to OFF Do not force 3 Wait 5 minutes to clear...

Page 11: ...nnect the test gauge and tighten firmly the screw of the gauge connection then check for gas leaks from it The HI and LO pressures must be adjusted in the way explained above Never try to adjust them...

Page 12: ...06065 Sparking Candle Part Number JGLL064 Nozzle Natural Gas Part Number J12160880 Nozzle LPG Piezo Electric Button Part Number JPZO000 Thermocouple Part Number JTRM000D Burner Part Number J90021028 P...

Reviews: