background image

 

Introduction 

 
 

 

Introduction – 5 

 

The  following  steps  are  all  needed  for  proper  installation  and  safe  operation  of  your  furnace.    If  you  have  any  doubts  as  to  any 
requirements, check with local authorities.  Obtain professional help where needed.  All of the checks and adjustments in the Start-Up 
Procedures  are  vital  to  the  proper  and  safe  operation  of  the  furnace.    Please  read  the  instructions  before  you  install  and  use  your 
furnace.  This will help you obtain the full value from this furnace.  It could also help you avoid needless service costs if the answer to 
the problem is found within this instruction manual. 
Always  consult  your  local  heating  or  plumbing  inspector,  building  department  or  gas  utility  company  regarding  regulations  codes  or 
ordinances which apply to the installation of a vented wall furnace. 
Check the furnace nameplate, located in the burner compartment, to make sure your furnace is equipped to operate on the type of gas 
available (either natural or L.P. gas).  DO NOT convert the furnace from natural gas to L.P. gas or from L.P. gas to natural gas without 
the proper manufacturer’s gas conversion kit.   
Combustion air is drawn in from the room where the furnace is located and is vented out of the top of the furnace vertically through vent 
piping in the stud space to a roof vent top.  Vent material is not supplied with the furnace.     
This  furnace  is  equipped  with  a  vent  safety  shutoff  system  designed  to  protect  against  improper  venting  of  combustion  products.  
Operation of this wall furnace when not connected to a properly installed and maintained venting system or tampering with the vent 
safety shutoff system can result in carbon monoxide (CO) poisoning and possible death. 
The efficiency rating of this furnace is a product thermal efficiency rating determined under continuous operating conditions and was 
determined independent of any installed system. 

Basic Materials Needed

Pipe and fittings to make gas connections to the furnace.   

Vertical venting materials.  See page 14, Figure 8.  

Pipe Joint Compound resistant to L.P. Gases.  

Electrical wiring supplies as needed.  Minimum wire size is #14 
gauge copper. 

Basic Tools Needed

Hand drill or properly grounded electric drill 
Expansion bit 1/2” to 1-5/8” or 1/2” and 1-1/2” blade bits 
1/8” and 3/16” drill bit (metal) 
6 ft. folding rule or tape measure 
Screwdriver (medium blade) 
Screwdriver (Phillips head) 
Pliers (wire cutting) 

 

Hammer 
Stud Locator or small finishing nails 
Tin Snips 
8” adjustable wrench 
12” adjustable wrench 
Two, 10” or 12” pipe wrenches 
Gloves and safety glasses

Helpful Installation Information

The following booklets will help you in making the installation: 
ANSI/NFPA 70, or current edition “National Electrical Code”.  In Canada:  CSA C22.1 Canadian Electrical Code. 
American National Standard Z223.1 or current edition of the “National Fuel Gas Code.” 
Obtain from the American National Standard Institute, Inc., 1430 Broadway, New York, NY  10018.  In Canada, CAN/CGA B149. 

 

Optional Accessories 

Blower Accessories 2901, 2907 - 

May be used on all models and mounts on top of a furnace. This blower increases circulation of 

warm air through the heated space.   A 115V outlet adjacent to the furnace is required. 

Trim Strip Kit 4701 - 

Provides a finished edge for sides of the wall furnace.  

 

Free Standing Accessory 4901 - 

May be used with single-sided models.  This accessory allows the furnace to be mounted on the 

surface of a wall. 

 

Vent Adapter Kit 9902,

 

9910 - 

Optional vent adapter, typically used when the furnace is vented into a properly lined chimney.

 

Rear Outlet Registers 6901, 6919, 6920 - 

May be used with single-sided models when recessed into a standard 2x4 inch interior stud 

partition.  This accessory directs some of the heated air into the room opposite the one in which the furnace is installed. 

 

Oval B/W Vent Kit 9901 - 

This U.L. listed B/W vent kit contains four feet of oval, double-walled vent pipe, plate spacers and base or 

hold-down plate that starts the venting from the top of furnace.  See Vent Installation on page 14 for additional items you will need. 

 

Plaster Ground Kit 6905 - 

Used for 6901 or 6919 Rear Outlet Registers. 

Gas Conversion Kits - 

See page 16.

Summary of Contents for 2509821

Page 1: ...for additional information consult a qualified installer service agency or the gas supplier 50 000 Btu hr Model 25 000 and 35 000 Btu hr Model Do not store or use gasoline or other flammable vapors an...

Page 2: ...do not involve defective workmanship or materials DUTIES OF THE CONSUMER 1 The heating equipment must be installed by a qualified installer and operated in accordance with the installation and homeown...

Page 3: ...Installation 19 Start Up Procedure 20 21 Stay Safe 22 23 Operating Your Furnace 22 23 How to Care for Your Furnace 24 25 Installing Your Blower Accessory 25 26 Blower Accessory Replacement Parts 27 28...

Page 4: ...servicing this appliance must be replaced prior to operating the appliance to avoid property damage bodily injury or death 8 Vent the furnace directly to the outdoors so that harmful gases will not co...

Page 5: ...e Vertical venting materials See page 14 Figure 8 Pipe Joint Compound resistant to L P Gases Electrical wiring supplies as needed Minimum wire size is 14 gauge copper Basic Tools Needed Hand drill or...

Page 6: ...l the furnace where it could be isolated by closing doors to the heated space Do not locate the furnace where a door could swing over the front panel or where circulation could be retarded by furnitur...

Page 7: ...the house until fresh air may be sucked back into the house down a furnace flue or fireplace chimney Carbon monoxide can be the result Carbon monoxide CO is a colorless odorless gas produced when fuel...

Page 8: ...ans water heaters gas and electric 3 Turn on all vented gas appliances i e heating equipment includes any room heaters water heaters 4 Wait ten 10 minutes for drafts to settle 5 Check for draft hood s...

Page 9: ...NING Danger of property damage bodily injury or death The adjoining unconfined space must have adequate air infiltration B Air From Outdoors If confined space does not adjoin an unconfined space then...

Page 10: ...e and 66 inches high measured from the top of the floor plate Figure 5 All corners must be square INSTALLATION OF REAR OUTLET REGISTER The optional rear outlet register may be installed when the furna...

Page 11: ...Hold down plate is not included HEADER PLATE VENT SUPPORT Measure upward 62 inches from the top of the floor plate Place a mark on each stud at this distance Figure 5 Place the header plate between t...

Page 12: ...with the furnace to the side rails using four 4 8 screws Flanges of the header plate go against the wall Figure A 3 Install extension side rails as shown in Figure A by telescoping them inside the low...

Page 13: ...Installing Your Furnace Surface Mount Installation continued FIGURE B FIGURE C FIGURE D Vent Installed Front panel installed...

Page 14: ...urnace rests INSTALL FURNACE VENT Attach a 4 foot length of oval double wall vent pipe through the plate spacers to the hold down plate Push the vent pipe into the hold down plate until it is complete...

Page 15: ...TIONAL If a Rear Outlet Register Accessory is used the following procedure must be completed before placing furnace body into wall recess Figure 11 Attach speed nuts to outer shield and remove knockou...

Page 16: ...as Type Model Number Gas Supply and Piping continued FIGURE 12 Mounting Rear Outlet Register The gas control valve in the furnace is shipped with a seal over the gas inlet tapping Do not remove the se...

Page 17: ...only Leave the two end threads bare Figure 15 L P gas installations require a dope compound resistant to the action of liquefied petroleum gases Excess dope going into the valve may cause it malfuncti...

Page 18: ...igher pressures may damage the gas valve and cause over firing which may result in component s failure L P gas is heavier than air and may settle in any low area including open depressions and it will...

Page 19: ...tions packed in the thermostat carton if you have any doubt about the above procedures WALL MOUNTED THERMOSTAT INSTALLATION 1 To remove the thermostat cover squeeze both sides and lift 2 Connect the t...

Page 20: ...GAS PRESSURE A tapped opening is provided in the gas valve to facilitate measuring manifold gas pressure A water column manometer having a scale range from 0 to 12 inches of water column should be use...

Page 21: ...rticles burn in the flame This is normal No burner adjustment is provided or is necessary Figure 20 NORMAL APPEARANCE Natural Gas 1 Inner cone blue in color 3 8 to 5 8 inches above ports 2 Secondary i...

Page 22: ...Read the safety information above 2 Set the thermostat to lowest setting 3 If applicable turn off all electric power to the appliance 4 Open control access panel 5 Push in gas control knob slightly a...

Page 23: ...lit call your local gas utility or a qualified service person If furnace is equipped with a manual spark igniter follow these steps 1 Review the pilot lighting instructions 2 When instructed to Light...

Page 24: ...nd exposed air passages BURNER CLEANING If cleaning is required contact a qualified service technician to clean and service burner To remove burner s 1 Open burner compartment door 2 Shut off gas supp...

Page 25: ...unction box cover Remove the cover to gain access to the knockout located in the junction box 6 Locate the knockout and remove it using a hammer and screwdriver Use caution when handling sharp metal e...

Page 26: ...nstalling Your Blower Accessory 26 Blower Accessory 2901 and 2907 continued FIGURE D Wiring for Model 2907 FIGURE C Wiring for Model 2901 FIGURE A Install Electrical Outlet FIGURE B Install Blower Bod...

Page 27: ...Blower Accessory Replacement Parts Accessories 27...

Page 28: ...P321078 11 Strain Relief Bushing P012900 12 Fan Switch P323097 13 Screw 6 32 x 3 8 P029200 14 Motor P320905 15 Fan Blade P320907 16 Orifice Plate 9D12 1 17 Junction Box Cover 9B161 BLOWER ACCESSORY PA...

Page 29: ...all openings for the register 1 Measure and mark wall for opening as shown in Figure A Check the wall for any electrical wiring present before cutting the opening Reroute existing electrical if necess...

Page 30: ...orized Rear Outlet Accessory 30 Motorized Rear Outlet Register 6919 and 6920 continued FIGURE C Surfaced Mounted Installation FIGURE D Recessed Mounted Installation FIGURE F Wiring FIGURE E Surface Mo...

Page 31: ...Motorized Rear Outlet Replacement Parts Motorized Rear Outlet Models 6919 and 6920 and 6920...

Page 32: ...ief Bushing P500185 P500185 3 J Box Cover 9A427 9A427 4 Strain Relief Bushing P603108 P603108 5 Heat Sensor Switch P323172 P323172 6 Fan Switch P323080 P323080 7 Motor and Blower P323076 P323076 8 Mot...

Page 33: ...Furnace Replacement Parts Control Assembly 250 350 and 500 Series...

Page 34: ...Furnace Replacement Parts 34 Furnace Replacement Parts continued Cabinet and Body Parts 250 and 350 Series...

Page 35: ...Furnace Replacement Parts Furnace Replacement Parts continued Cabinet and Body Parts 500 Series...

Page 36: ...3648 9 Electrode P322155 P322155 10 Pilot Mounting Plate 9A409 9A409 REF NO DESCRIPTION 2509821 2519821 2539821 2559821 2509822 2519822 2539822 2559822 3509821 3519821 3539821 3559821 3509822 3519822...

Page 37: ...6 Deflector 2 Required 9B199 9B199 7 Header 5901 5901 8 Vent Limit Switch P321826 P321826 9 Draft Hood 2 Required 9C170 9C170 10 Non Vision Shield 9C157 9C157 11 Inner Shield Top 2 Required 9C158 9C15...

Page 38: ...nob to the ON b Set thermostat to a position calling for heat c Check clean or replace d Check connections at valve terminals If valve operates check thermostat wires e See 1a and 1c above f Replace g...

Page 39: ...venting d Use listed B W type vent pipe DO NOT use transite or any other type of ceramic pipe for venting DO NOT use single wall vent pipe When venting into a masonry chimney the chimney must be prope...

Page 40: ...exactly a fire or explosion may result causing property damage personal injury or loss of life Williams Furnace Company 250 West Laurel Street Colton CA 92324 909 825 0993 FAX 909 824 8009 www wfc fc...

Reviews: