16
WIKA operating instructions Ultra High Purity transducer, model WUD-2x
11611057.05 08/2021 EN/DE
EN
Relationship between power supply and load (R
A
)
Current output (3-wire)
4 ... 20 mA:
R
A
≤ (U+ – 10 V) / 0.02 A
Voltage output (3-wire)
DC 0 ... 5 V: R
A
> 5 kΩ
DC 0 ... 10 V: R
A
> 10 kΩ
with R
A
in Ω and U+ in Volt
permissible range
U+
4 ... 20 mA, 3-wire
5.2.2 Making the electrical connection
▶
Screw the connector in hand-tight. The ingress protection is only ensured if the installation
instructions for the seals are followed.
▶
Ensure that no moisture can enter at the cable end.
▶
The transducer must be grounded via the process connection.
▶
Use a shielded cable, if the line is longer than 30 m or leaves the building.
▶
Do not connect the cable shield on the instrument side.
5. Commissioning, operation