Universal Pressure Transmitter UniTrans
Installation
Subject to change due to technical modifications.
© Copyright WIKA Alexander Wiegand GmbH & Co. KG / BRD
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg ·
(09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de
56
4.4
Electrical Connection
The supply voltage is between 12 and 36 V DC. The power supply and the output sig-
nal are transmitted via a two-wire cable (max. 12 mm outer diameter, max. 14 AWG)
and connected in accordance with the pin configuration.
Supply voltage can be supplied by a power unit, a transmitter power supply or by
means of a PLC connection.
It is suggested to use a model with integrated lightning protection for preventing dam-
age due to voltage peaks.
Please observe local installation regulations (Germany: VDE-Standard).
The terminal voltage should not exceed 36 V.