WIKA operating instructions models TR30, TR31
GB
The permissible load depends on
the loop supply voltage.
Voltage U
B
in V
Load R
A
in
Ω
0
10
24
30
36
1182
909
636
Load diagram
3. Specifications
For setting the measuring range see chapter 7 "Configuration of models TR30-W and
TR31-W".
■
Output signal 0 ... 10 V, model TR30-V
Measuring element and measuring insert
The Pt100 measuring element is located in the thermometer‘s probe tip.
The 0 … 10 V transmitter is mounted in the tubular body of the thermometer.
Output signal 0 ... 10 V, model TR30-V
Temperature range
Measuring range without neck tube -50 ... +150 °C,
with neck tube -50 ... +200 °C
2)
, measuring ranges are not adjustable
Measuring element
Pt100 (measuring current: 0.5 mA)
Sensor tolerance value
1)
per DIN EN 60751
Class B
Measuring span
minimum 50 K, maximum 250 K
Basic configuration
Measuring range 0 ... 100 °C
Measuring ranges
-50 ... +50, 0 ... 50, 0 ... 80, 0 ... 100, 0 ... 120, 0 ... 150, 0 ... 200 °C
Analogue output
0 ... 10 V, 3-wire
Overall measuring error
3)
< 0.5 % of span
Power supply
DC 12 ... 30 V
Max. permissible residual ripple
10 %
Electromagnetic compatibility
(EMC)
2004/108/EC, EN 61326 emission (Group 1, Class B) and interference
immunity (industrial application)
4)
Electrical connection
Angular DIN connector Form A, M12 x 1 circular connector, 4-pin
Readings in % refer to the measuring span
For a correct determination of the overall measuring error, both sensor and transmitter measuring deviations have to
be considered.
1) For detailed specifications for Pt100 sensors, see Technical Information IN 00.17 at www.wika.com.
2) The temperature transmitter should therefore be protected from temperatures over 85 °C
3) For measuring spans smaller than 50 K additional 0.1 K
4) Use resistance thermometers with shielded cable, and ground the shield on at least one end of the lead, if the cables are longer than
30 m or leave the building.
For further specifications on the TR30 see WIKA data sheet TE 60.30.