24
WIKA operating instructions pressure sensor, model O-10
EN
11613017.05 09/2019 EN/DE/FR/ES
Circular connector M12 x 1
2-wire
3-wire
UB
1
1
0V
3
3
S+
-
4
4
3
1
2
Angular connector DIN 175301-803 A
2-wire
3-wire
1
2
3
UB
1
1
0V
2
2
S+
-
3
Angular connector DIN 175301-803 C
2-wire
3-wire
UB
1
1
0V
2
2
S+
-
3
Cable outlet, shielded
2-wire
3-wire
UB
brown
brown
0V
blue
blue
S+
-
black
Cable outlet, unshielded
2-wire
3-wire
UB
brown
brown
0V
green
green
S+
-
white
Metri-Pack series 150
2-wire
3-wire
UB
B
B
0V
A
A
S+
-
C
6. Commissioning, operation
■
With instruments with internally connected shields (only connector variants) the cable shield should be grounded
at one end. The simultaneous connection of the case and the cable shield to ground is only permitted if any
accidental energisation between the shield connection (e.g. at the power supply) and the case can be excluded
(see EN 60079-14).
■
For the output signals DC 0 ... 5 V, DC 1 ... 5 V, DC 0.5 ... 4.5 V and DC 0.5 ... 4.5 V ratiometric, the following
applies in addition: If the cable of the electrical connection is longer than 30 m or leaves the building, then the
pressure sensor should be used with a shielded cable. Earth the shield on at least one end of the lead.
Connection diagrams