Once the cover of the case has been removed, to configure the instrument
continue as follows:
■
To access the menu, while the actual value is displayed, press key 2 for 2
seconds until
"dP"
appears in the display.
■
To set the parameter values, press keys 2 and 3.
■
To save the set value, press key 1. The parameter name will then appear in
the display once more.
■
To switch to the next parameter, press key 1. The name of the parameter
will appear in the display.
If, during input, no key is pressed for 60 seconds, the configu
-
ration of the instrument will be interrupted. Previously-saved
values will not be lost.
Parameters of the A-IAI-1 attachable indicator
Parameters Values
Description
Key 1
Keys 2 and 3
dP
Position of the decimal point (decimal point)
----
Max. indication range: -1999 … 9999
---.-
Max. indication range: -199.9 … 999.9
--.--
Max. indication range: -19.99 … 99.99
-.---
Max. indication range: -1.999 … 9.999
di.Lo
Lower indication range limit (display low)
-1999 ... 9999
This value will be displayed when the input signal
= 4 mA
di.Hi
Upper indication range limit (display high)
-1999 ... 9999
This value will be displayed when the input signal
= 20 mA
Li
Measuring range limit (limit)
oFF
deactivated
Exceeding the measuring range limits is permitted
up to the measuring limit (see note)
on.Er
active, (error display):
The measuring range is limited exactly to the input
signal. When this exceeds or drops below it, a
corresponding error message is displayed.
6. Commissioning, operation