PL512/PL506

Modular Power Supply System

Technical Manual

Summary of Contents for PL506

Page 1: ...28 May 2013 1 00679 A4 PL512 PL506 Modular Power Supply System Technical Manual...

Page 2: ...50 IEC 60950 UL 60950 All devices are intended for operation in control cabinets or in closed areas The LAN connection and all wire connections between the different system parts must be done via shie...

Page 3: ...gen harmonics EN 61 000 3 3 1995 Corr 1997 A1 2001 Spannungsschwankungen flicker 3 EN 61 000 6 2 2001 St rfestigkeit EMB immunity EN 61 000 4 6 1996 A1 2001 HF Einstr mung injected HF currents EN 61 0...

Page 4: ...Connections PL512 9 2 11 Power Output and Sense Connections PL506 10 3 PL512 PL506 Control and Setup via USB 10 3 1 Installation 11 3 2 The Main Window 12 3 3 Description of the Menu Items 12 3 3 1 R...

Page 5: ...n 17 Figure 7 2 PBN506 3U RASO Power Bin with PL506 Power Supply inserted 18 Figure 7 3 Current Bar Dimensions 26 Figure 7 4 Two Channels Parallel 28 Figure 7 5 Three Channels Parallel 28 Figure 7 6 F...

Page 6: ...oftware Ethernet connection IEEE 802 3 10BASE T and IEEE 802 3u 100BASE TX WWW Server integrated full control via SNMP protocol OPC server available Three different voltage regulation modes programmab...

Page 7: ...le plug STAK3N with the locking retainer STASI3 AC Input Pin Signal Comment 1 Phase 2 Return Neutral Cable wire color black or brown wire Cable wire color blue 3 unused Earth Protective Earth Safety G...

Page 8: ...ector RJ45 Socket Pin Signal Comment 1 TX 2 TX 3 RX 4 GND 1 5 GND 1 6 RX 7 GND 2 8 GND 2 Table 3 Ethernet Connector Pin Assignment This is the standard NIC configuration You need a 1 1 cable to connec...

Page 9: ...erved 10 NC reserved 23 NC reserved 11 NC reserved 24 NC reserved 12 NC reserved 25 GND Ground of the aux supply connected to USB ground 13 POWER_INHIBIT Inhibit input Table 4 Global Reset Connector P...

Page 10: ...Interlock U9 23 Interlock U9 11 Interlock U10 24 Interlock U10 12 Interlock U11 25 Interlock U11 13 reserved Table 5 Channel Wise Interlock Connector Pin Assignment Each interlock input is galvanical...

Page 11: ...The input has an internal 330 pull up resistor to 5V and an input impedance of 1 k Signal Functionality STOP If this signal is connected to GND dry contact close all power supply outputs are switched...

Page 12: ...6 Symbol Description Remarks P Push Power switch up ON Main power supply is off Switch the power supply on All power channels are off Display shows a switched off channel Switch this channel on Submen...

Page 13: ...Change the value M or M 196 168 91 94 Accept change to next item P 196 168 91 94 Accept change to next item P 196 168 91 94 Accept change to next item P 196 168 91 94 Ready back to submenu selection...

Page 14: ...MAC This address is written at the type plate too TCPIP MAC Addres 0050 C22D C231 Change the TCP IP port of the web server HTTP Port 80 Change the TCP IP port of the SNMP server SNMP Port 161 Restore...

Page 15: ...arranged from left to right starting with U0 Positive output is up and negative output is down The sense lines are routed to three DSUB connectors 2 channels each DSUB9 male Pin Left Connector U0 U3...

Page 16: ...before connecting the power supply to the USB The necessary USB driver is included in the installation After downloading and executing the software Windows may complain that the supplier of the softwa...

Page 17: ...king with the right mouse button opens the output configuration menu of this channel 3 3 Description of the Menu Items File Read Power Supply Configuration from File Opens the Read Power Supply Data F...

Page 18: ...s dialog can be used to copy a XML configuration file from disk to the PL512 PL506 It is possible to copy each configuration file channel to its corresponding power supply channel e g U0 U0 U1 U1 or t...

Page 19: ...is connected with really long or high inductance cable the Slow Regulation check box should be checked additionally This increases the time constant of the I Regulator The Control and Status group has...

Page 20: ...ers of your local network here Please contact your network administrator for details HTTP and SNMP port numbers should only modified if you know what you do Setting any port to 0 disables the server I...

Page 21: ...gative outputs down Each sense connector of four output channels are connected to an eightfold plug able terminal row For the PL 506 Starting from left with U0 and right U0 Each sense line of two outp...

Page 22: ...s follows from left to right U0 U1 U2 U3 and so on Fig 4 5 shows load and sense connections for U0 Use remote sense for load lines greater than 1m Use internal sense for testing and setup only Once yo...

Page 23: ...nes use twisted cable to cancel EMI not shown in picture Size the load lines appropriately for V drop and loads 4 4 MUSEControl 28 May 2013 18 00679 A4 Fig 4 7 Typical PS output wiring diagram Fig 4 8...

Page 24: ...on without setting up the parameters correctly Supervision Decide what is the permissible range of Sense Voltage V Enter those values here Eg 3 130V and 3 470V respectively Enter the maximum Terminal...

Page 25: ...Voltage V It must be in range of the Supervision values entered previously Set the Current Limit A as needed for your application See the 00679 A3 manual for more details regarding Ramp Up Down Regula...

Page 26: ...otocol Please see http net snmp sourceforge net for more details Please install netSNMP from the CD ROM or downloaded from the WIENER file server http file wiener d com on the control computer In orde...

Page 27: ...CRATE MIB This parameter tells the command to look at the WIENER CRATE MIB to resolve the OID name c public This specifies which community of values can be accessed ip This should be replaced with the...

Page 28: ...R CRATE MIB outputMeasurementSenseVoltage u4 Opaque Float 0 000000 V WIENER CRATE MIB outputMeasurementSenseVoltage u5 Opaque Float 0 000000 V WIENER CRATE MIB outputMeasurementTerminalVoltage u0 Opaq...

Page 29: ...TE MIB outputSupervisionMinSenseVoltage u1 Opaque Float 22 799805 V WIENER CRATE MIB outputSupervisionMinSenseVoltage u2 Opaque Float 3 129883V WIENER CRATE MIB outputSupervisionMinSenseVoltage u3 Opa...

Page 30: ...utSupervisionMaxPower u4 Opaque Float 600 000000 W WIENER CRATE MIB outputSupervisionMaxPower u5 Opaque Float 550 000000 W WIENER CRATE MIB outputRegulationMode u0 INTEGER moderate 1 WIENER CRATE MIB...

Page 31: ...E MIB c guru ip name index format value The most common kind of call you will want is to get data from the power supply This is easily done via the snmpget command The example below retrieves informat...

Page 32: ...age Float R Actual channel Voltage mesaured at sense line outputSwitch Integer R W Turns channel ON OFF outputStatus Bits R Channel Status information outputMeasurementTerminalVoltag e Float R Actual...

Page 33: ...snmpCommunityName WIENER CRATE MIB snmpCommunityName public STRING public WIENER CRATE MIB snmpCommunityName private STRING private WIENER CRATE MIB snmpCommunityName admin STRING admin snmpwalk v 2c...

Page 34: ...ovide often a simple GUI and allow SNMP calls Following is a list of some free or open source MIB browsers http www ireasoning com mibbrowser shtml http www serverscheck com mib_browser http www mibbl...

Page 35: ...dows XP operating system enables access to all controllers which are connected to the network TCP IP It is possible to access from any OPC Client application to the data of one or more servers encapsu...

Page 36: ...s MULTICONTACT The arrangement is the same as at the power box Starting from left with U0 and positive outputs up negative outputs down Each sense lines of four output channels are connected to an eig...

Page 37: ...28 May 2013 32 00679 A4 Figure 8 2 PBN506 3U RASO Power Bin with PL506 Power Supply inserted...

Page 38: ...8 V 100 mV 50 75 load change other 0 7 50 75 load change Recovery Time MDC M 2 8V 1 0 2 ms 0 1 0 5 ms 50 75 load change MDC M 5 16V 7 24V 1 0 0 ms 0 1 1 0 ms 50 75 load change MDC M 30 60V 1 0 5 ms 0...

Page 39: ...programmable after overload overheat overvoltage undervoltage Interlock input optional Efficiency per Module 65 2V 81 5V 85 7V 87 12V 90 48V at nominal input voltage M T B F cooled by Water 30 C infl...

Page 40: ...rrents 3 x 9pin Sub D for sensing each for 4 channels Dimensions w h d 434 mm x 132 mm x 325 mm Weight 31 5 kg Accessories 19 Power Bins PBN506 PBN512 for plug in PL506 PL512 power supplies power cont...

Page 41: ...dules can be used without external ventilation integrated fans Module Type Channels per Module Optimal Voltage Range Peak Output Current Continuous Output Power MDH 2 2V 7V 8V 2 30A 2 210W MDH 2 5 7V...

Page 42: ...general definition usable for different types of crates some items may be not implemented in the real hardware Here the not relevant parts are omitted The wiener OID is located at iso 1 org 3 dod 6 i...

Page 43: ...GER outputAdjustVoltage 11 Range 128 127 RW Opaque outputCurrent 12 Textual Convention Float Size 7 RW INTEGER outputSupervisionBehavior 15 Range 0 65535 RW Opaque outputSupervisionMinSenseVoltage 16...

Page 44: ...es public 1 private 2 admin 3 guru 4 RW String snmpCommunityName 2 Size 0 14 RW INTEGER snmpPort 2 powersupply 6 R String psSerialNumber 2 Textual Convention DisplayString Size 0 255 R INTEGER psOpera...

Page 45: ...n one contact pair use the current bars to connect each option For best operation it is necessary to connect the parallel outputs together as near as possible at the power supply site For 200A 4 fold...

Page 46: ...28 May 2013 41 00679 A4 Figure 8 4 Two Channels Parallel Figure 8 5 Three Channels Parallel Figure 8 6 Four Channels Parallel...