CNT
14
Wieland Electric GmbH | BA000917 | 01/2019 (Rev. B)
Address
Access
Description
0x0500
R/W
Upper 16 bits of counter CNT1 value
0x0501
R/W
Lower 16 bits of counter CNT1 value
0x0502
R/-
Prompt frequency CNT1
0x0503
R/-
Average frequency CNT1
0x0504
R/-
Minimal frequency CNT1
0x0505
R/-
Maximal frequency CNT1
0x0601
R/W
Upper 16 bits of counter CNT2 value
0x0601
R/W
Lower 16 bits of counter CNT2 value
0x0602
R/-
Prompt frequency CNT2
0x0603
R/-
Average frequency CNT2
0x0604
R/-
Minimal frequency CNT2
0x0605
R/-
Maximal frequency CNT2
0x0F00
R/-
0x0000 always
0x0F01
R/-
0x0000 always
0x0F02
R/-
Upper 16 bits of seconds number from 1.1.1970
0x0F03
R/-
Lower 16 bits of seconds number from 1.1.1970
0x0F04
R/-
Alarms status
•
bit 0 – active level on input BIN1
•
bit 1 – active level on input BIN2
•
bit 2 – active level on input BIN3
•
bit 3 – active level on input BIN4
•
bit 4 – analogy input lower limit overrun AN1
•
bit 5 – analogy input upper limit overrun AN1
•
bit 6 – analogy input lower limit overrun AN2
•
bit 7 – analogy input upper limit overrun AN2
•
bit 8 – limit frequency overrun CNT1
•
bit 9 – limit frequency overrun CNT2
0x0F05
R/-
Binary inputs status
•
bit 0 – level on input BIN1
•
bit 1 – level on input BIN2
•
bit 2 – level on input BIN3
•
bit 3 – level on input BIN4
•
bit 6 – level on output BOUT1
0x0F06
R/-
Recalculate AN1 value (with sign)
0x0F07
R/-
Recalculate AN2 value (with sign)
0x0F08
R/-
Upper 16 bits CNT1
0x0F09
R/-
Lower 16 bits CNT1