EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
106
Error
Possible cause
Possible remedy
LED /ACT
Yellow
MS LED
Green
The SP-COP2-ENI / the
samosPRO system is in the
“Critical error” state.
• The SP-COP2-ENI module is
not properly connected to
the samosPRO modules.
• The module connection
plug is dirty or damaged.
• Another samosPRO module
has an internal critical er-
ror.
• Insert the I/O module correctly.
Clean the connection plug and
socket.
• Switch on the power supply
again.
• Check the other samosPRO
modules.
80809739
LINK
The SP-COP2-ENI module possesses a green LED with the designation
LINK
. If there is no Ethernet
connection, it stays dark. If there is a connection, it switches on.
80821131
ACT (Activity Status)
The SP-COP2-ENI module possesses a green LED with the designation
ACT
. If no port activity can be
detected, it stays dark. If port activity is detected, it switches on.
Diagnostic functions in the configuration software
80832139
Additional diagnostic functions are available on the SD card using a log file with the name histo-
ry.csv. In addition, the last entries are available in samosPLAN
6 in the
Diagnostics
view. The ti-
mestamp in the
Local time
column provides information about how long the device has been swit-
ched on in total.
Synchronize time
With the safety controller connected you can synchronize the time on the safety controller with the
time on the connected diagnostics computer. Even if you disconnect the connection to the control-
ler, the
Diagnostics
view remains active, as long as the associated samosPLAN
6 project is open.
NOTICE
Instructions in software manual
You can find step-by-step instructions on how to synchronize the time here:
Software manual, chapter "Synchronize time for diagnostic purposes"
8.9.2.3
8.9.2.4
8.9.3