background image

Attention

LCD display indicators

NOTE: All signs shown in the display is for the purpose of clear presentation. But during the actual 
operation only the relative functional signs are shown on the display panel.

15

16

17

18

19

20

21

LOCK Indicator:

 LOCK display is 

displayed by pushing the LOCK 
button. Push the LOCK button to 
clear display.

OPERATION MODE INDICATOR:

 

When press the MODE button, it 
shows the current operating mode: 
AUTO, COLD, DRY, HEAT (Only for 
cooling and heating models) or 
FAN mode.

TRANSMISSION INDICATOR:

 

This indicator flashes one time 
when remote controller transmits 
signals to the indoor unit.

DIGITAL DISPLAY: 

This area will 

show the set temperature and, if in 
the TIMER mode, will show the ON 
and OFF settings of the TIMER. If in 
the FAN mode, nothing is 
appeared.

ON/OFF INDICATOR: 

This 

symbol appears when the unit is 
turned on by the remote controller, 
and disappear when the unit is 
turned off.

FAN SPEED INDICATOR: 

Press 

the FAN SPEED button to select the 
desired fan speed setting (Auto-
Low-Med-High). You selection will 
be displayed in the LCD window 
except the Auto fan speed.

TIMER DISPLAY INDICATOR: 

This 

display area shows the settings of 
the TIMER. That is, if only the 
starting time of operation is set, it 
will display the TIMER ON. If only 
the turning off time of operation is 
set, it will display the TIMER OFF. If 
both operations are set, it will show 
TIMER ON-OFF which indicates 
you have chosen to set both the 
starting time and off time.

17

16

18

20

21

19

15

How the air conditioner works

Automatic operation

When the Air Conditioner is ready for use, switch on the power and the 
OPERATION indicator lamp on the display panel of the indoor unit starts 
flashing.

1. Use the MODE .select button to select AUTO.
2. Push the TEMP button to set the desired room temperature. The most 

comfortable temperature setting are between 21ºC o to 28ºC.

3. Push the ON/OFF button to start the air conditioner. The OPERATION lamp 

on the display panel of the indoor unit lights. The

operating mode is AUTO FAN SPEED is automatically set and there are no 

indicators shown on the display panel of the remote controller.

4. Push the ON/OFF button again to stop the unit operation.

COLD / HEAT and FAN ONLY operation

1. If the AUTO mode is not comfortable, you may manually override the 

settings by using COLD, HEAT* or FAN** ONLY modes.

2. Push the TEMP button to set the desired room temperature. When in COLD 

mode, the most comfortable settings are 21ºC or above. When in HEAT 
mode, the most comfortable settings are 28 C or b elow.

3. Push the FAN SPEED to select the FAN mode of AUTO, HIGH, MED or LOW.
4. Push the ON/OFF button, the operation lamp lights and the air conditioner 

start to operate as your settings. Push the ON/OFF button again to stop this 
unit operation.

  * Nota: Only for heating and cooling models
  **Note: The FAN ONLY mode can not be used to control the temperature. 

While in this mode, only steps 1,3 and 4 may be performed.

1.  When you set the air conditioner in AUTO mode, it will automatically select 

cooling, heating(cooling/heating models only), or fan only operation 
depending on what temperature you have selected and the room 
temperature.

2.  The air conditioner will control room temperature automatically round the 

temperature point set by you.

3.  If the AUTO mode is uncomfortable, you can select desired conditions 

manually.

37

LCD display indicators

38

How the air conditioner works

Summary of Contents for E)24C6CHLW

Page 1: ...INSTRUCTIONS MANUAL SPLIT TYPE ROOM AIR CONDITIONER INVERTER TYPE Models S5 21 22 W_R22_ENGLISH_130705A WAS C E 12P5CHLWP WAS C E 18P5CHLWP...

Page 2: ...If you need to dispose of this appliance in the future do NOT throw it away with the rest of your domestic garbage Instead please take the appliance to the nearest WEEE collection point where availab...

Page 3: ...p firearms away It may cause fire 6 Do not operate or stop the unit by switching on or off the power It may cause electric shock or fire due to heat generation 7 Do not operate with wet hands or in da...

Page 4: ...ean the air conditioner with water Water may enter the unit and degrade the insulation It may cause an electric shock 20 Ventilate the room well when used together with a stove etc An oxygen shortage...

Page 5: ...beforehand 1 Site with machine oil 2 Sites with a high concentration of salinity such as coastal areas 3 Sites with sulfuric gas such as hot water springs 4 Sites with high frequency equipment such a...

Page 6: ...than 5 meters 16 feet and for pipes measuring at least 10 meters 33 feet in length 7 The site must provide enough space around the unit as shown in the diagram 8 Children must not be able to access t...

Page 7: ...ion purposes only 2 Copper lines must be insulated independently 7 8 5 4 2 3 1 Indoor unit Outdoor unit 6 6 More than 12cm More than 12cm Air filter More than 200cm More than 60cm More than 30cm More...

Page 8: ...install the drain hose as illustrated below 2 When connecting extension drain hose insulate the connecting part of extension drain hose with a shield pipe do not let the drain hose slack Connective p...

Page 9: ...ntly windy 4 If the installation site is exposed to heavy winds such as in coastal areas place the unit along the widest part of the wall or use protective plates 7 If need suspending installation the...

Page 10: ...le longer than the measured distance D Cut the cable 1 5m longer than the pipe length 2 Burr removal A Completely remove all burrs from the cut cross section of pipe tube B Put the end of the copper t...

Page 11: ...air conditioner is grounded well 5 According to the attached Electrical Connection Diagram located on the panel of the outdoor unit to connect the wire 6 All wiring must comply with local and national...

Page 12: ...ording to the attached Electrical Connection Diagram located on the panel of the outdoor unit to connect the wire 6 All wiring must comply with local and national electrical codes and be installed by...

Page 13: ...l work Electrical work Wire connector of outdoor unit 1 Remove the electrical control board cover from the outdoor unit by loosening the screw 2 Connect the connective cables to the terminals as ident...

Page 14: ...Operating current rises 3 Cooling or heating efficiency drops 4 Moisture in the refrigerant circuit may freeze and block capillary tubing 5 Water may lead to corrosion of Air purging with vacuum pump...

Page 15: ...cuation is complete fully close the handle Lo of the manifold valve and stop the operation of the vacuum pump Make evacuation for 15 minutes or more and check that the compound meter indicates 76cmHg...

Page 16: ...itioner may attract condensation Please sets the vertical air flow louver to its maximum angle vertically to the floor and set HIGH fan mode Optimum performance will be achieved within these operating...

Page 17: ...erature sensor inside front panel Panel Infra red signal receiver Drain hose connector and refrigerant gas connector Remote control Connector cable Detection valve Drain hose and refrigerant connectin...

Page 18: ...vate the programs To replace batteries 1 Slide out the battery compartment cover located in the back part of the remote control 2 Install the two AAA batteries in the compartment indicated in the draw...

Page 19: ...door temperature setting FAN SPEED This button is used for setting Fan Speed in the sequence that goes from AUTO LOW MED to HIGH then back to Auto ON OFF Push this button to start the unit operation P...

Page 20: ...ower and the OPERATION indicator lamp on the display panel of the indoor unit starts flashing 1 Use the MODE select button to select AUTO 2 Push the TEMP button to set the desired room temperature The...

Page 21: ...tion movement would alter automatically SLEEP mode Press the sleep button to activate the sleep mode To deactivate press the button again Cold only mode The indoor unit fan operates at a low velocity...

Page 22: ...g operation and the signal h will be shown on the DIGITAL DISPLAY area You are now ready to reset the time of the STOP operation 2 Push the TIMER OFF button again to set the time you want to stop the...

Page 23: ...HEATING performance may be impaired due to too restricted air flow area Do not operate unit with horizontal louver in closed position When the air conditioner is connected to power initial power the h...

Page 24: ...lean the fresh air filter at least once a month and replace every 4 to 5 months Use a vacuum cleaner then dry 6 Clean the support frame using a vacuum cleaner or water After dry air filter air filter...

Page 25: ...t is blown out from the indoor unit This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit A peculiar smell comes out from the indoor uni...

Page 26: ...indicator or other indicator flash 5 times per second and the flashing is not stop by disconnecting and connecting the unit 2 Frequent change of fuses and malfunctions in the switch circuit 3 Water sp...

Page 27: ...Notes Notes 52 Notes Notes 51...

Reviews: