background image

Electrical safety

Perform the electric safe check after completing installation:

Gas leak check

Soap water method

Apply a soap water or a liquid neutral 
detergent on the indoor unit 
connection or outdoor unit connections 
by a soft brush to check for leakage of 
the connecting points of th piping. If 
bubbles come out, the pipes have 
leakage.

Leak detector

Use the leak detector to check for 
leakage.

Caution

A: Lo packed valve, B: Hi packed valve 
C and D are ends of indoor unit 
connection.

Outdoor unit
check point

Cover

indoor unit
check point

 

When using the vacuum pump

For method of using a manifold valve, refer to its operation manual.

1.  Completely tighten the flare 

nuts, A, B, C, D, connect the 
manifold valve charge hose to a 
charge port of the low-pressure 
valve on the gas pipe side.

2.  Connect the charge hose 

connection to the vacuum pump.

3.  Fully open the handle Lo of the 

manifold valve.

4.  Operate the vacuum pump to 

evacuate. After starting 
evacuation, slightly loose the 
flare nut of the Lo valve on the 
gas pipe side and check that the 
air is entering (Operation noise 
of the vacuum pump changes 
and a compound meter indicates 
0 instead of minus)

5.  After the evacuation is complete, 

fully close the handle Lo of the 
manifold valve and stop the 
operation of the vacuum pump. 
Make evacuation for 15 minutes 
or more and check that the 
compound meter indicates -
76cmHg (-1x10 Pa).

6.  Turn the stem of the packed 

valve B about 45o 
counterclockwise for 6~7 
seconds after the gas coming 
out, then tighten the flare nut 
again. Make sure the pressure 
display in the pressure indicator 
is a little higher than the 
atmosphere pressure.

7.  Remove the charge hose from the 

Low pressure charge hose.

8.  Fully open the packed valve stems 

B and A.

9.  Securely tighten the cap of the 

packed valve.

1. Insulated resistance: The insulated resistance must be more than 2M    .
2. Grounding work: After finishing grounding work, measure the grounding 

resistance by visual detection and grounding resistance tester. Make sure the 
grounding resistance is less than 4    .

3. Electrical leakage check (performing during test running): During test operation 

after finishing installation, the serviceman can use the electroprobe and 
multimeter to perform the electrical leakage check. Turn off the unit 
immediately if leakage happens. Check and find out the solution ways till the 
unit operate properly.

27

Air purging

28

Electrical safety and gas leak check

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Low pressure valve

Summary of Contents for E)24C6CHLW

Page 1: ...INSTRUCTIONS MANUAL SPLIT TYPE ROOM AIR CONDITIONER INVERTER TYPE Models S5 21 22 W_R22_ENGLISH_130705A WAS C E 12P5CHLWP WAS C E 18P5CHLWP...

Page 2: ...If you need to dispose of this appliance in the future do NOT throw it away with the rest of your domestic garbage Instead please take the appliance to the nearest WEEE collection point where availab...

Page 3: ...p firearms away It may cause fire 6 Do not operate or stop the unit by switching on or off the power It may cause electric shock or fire due to heat generation 7 Do not operate with wet hands or in da...

Page 4: ...ean the air conditioner with water Water may enter the unit and degrade the insulation It may cause an electric shock 20 Ventilate the room well when used together with a stove etc An oxygen shortage...

Page 5: ...beforehand 1 Site with machine oil 2 Sites with a high concentration of salinity such as coastal areas 3 Sites with sulfuric gas such as hot water springs 4 Sites with high frequency equipment such a...

Page 6: ...than 5 meters 16 feet and for pipes measuring at least 10 meters 33 feet in length 7 The site must provide enough space around the unit as shown in the diagram 8 Children must not be able to access t...

Page 7: ...ion purposes only 2 Copper lines must be insulated independently 7 8 5 4 2 3 1 Indoor unit Outdoor unit 6 6 More than 12cm More than 12cm Air filter More than 200cm More than 60cm More than 30cm More...

Page 8: ...install the drain hose as illustrated below 2 When connecting extension drain hose insulate the connecting part of extension drain hose with a shield pipe do not let the drain hose slack Connective p...

Page 9: ...ntly windy 4 If the installation site is exposed to heavy winds such as in coastal areas place the unit along the widest part of the wall or use protective plates 7 If need suspending installation the...

Page 10: ...le longer than the measured distance D Cut the cable 1 5m longer than the pipe length 2 Burr removal A Completely remove all burrs from the cut cross section of pipe tube B Put the end of the copper t...

Page 11: ...air conditioner is grounded well 5 According to the attached Electrical Connection Diagram located on the panel of the outdoor unit to connect the wire 6 All wiring must comply with local and national...

Page 12: ...ording to the attached Electrical Connection Diagram located on the panel of the outdoor unit to connect the wire 6 All wiring must comply with local and national electrical codes and be installed by...

Page 13: ...l work Electrical work Wire connector of outdoor unit 1 Remove the electrical control board cover from the outdoor unit by loosening the screw 2 Connect the connective cables to the terminals as ident...

Page 14: ...Operating current rises 3 Cooling or heating efficiency drops 4 Moisture in the refrigerant circuit may freeze and block capillary tubing 5 Water may lead to corrosion of Air purging with vacuum pump...

Page 15: ...cuation is complete fully close the handle Lo of the manifold valve and stop the operation of the vacuum pump Make evacuation for 15 minutes or more and check that the compound meter indicates 76cmHg...

Page 16: ...itioner may attract condensation Please sets the vertical air flow louver to its maximum angle vertically to the floor and set HIGH fan mode Optimum performance will be achieved within these operating...

Page 17: ...erature sensor inside front panel Panel Infra red signal receiver Drain hose connector and refrigerant gas connector Remote control Connector cable Detection valve Drain hose and refrigerant connectin...

Page 18: ...vate the programs To replace batteries 1 Slide out the battery compartment cover located in the back part of the remote control 2 Install the two AAA batteries in the compartment indicated in the draw...

Page 19: ...door temperature setting FAN SPEED This button is used for setting Fan Speed in the sequence that goes from AUTO LOW MED to HIGH then back to Auto ON OFF Push this button to start the unit operation P...

Page 20: ...ower and the OPERATION indicator lamp on the display panel of the indoor unit starts flashing 1 Use the MODE select button to select AUTO 2 Push the TEMP button to set the desired room temperature The...

Page 21: ...tion movement would alter automatically SLEEP mode Press the sleep button to activate the sleep mode To deactivate press the button again Cold only mode The indoor unit fan operates at a low velocity...

Page 22: ...g operation and the signal h will be shown on the DIGITAL DISPLAY area You are now ready to reset the time of the STOP operation 2 Push the TIMER OFF button again to set the time you want to stop the...

Page 23: ...HEATING performance may be impaired due to too restricted air flow area Do not operate unit with horizontal louver in closed position When the air conditioner is connected to power initial power the h...

Page 24: ...lean the fresh air filter at least once a month and replace every 4 to 5 months Use a vacuum cleaner then dry 6 Clean the support frame using a vacuum cleaner or water After dry air filter air filter...

Page 25: ...t is blown out from the indoor unit This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit A peculiar smell comes out from the indoor uni...

Page 26: ...indicator or other indicator flash 5 times per second and the flashing is not stop by disconnecting and connecting the unit 2 Frequent change of fuses and malfunctions in the switch circuit 3 Water sp...

Page 27: ...Notes Notes 52 Notes Notes 51...

Reviews: