SYSTEM LOCKOUT AND

DIAGNOSTIC FEATURES

SYSTEM LOCKOUT FEATURES

When system lockout occurs, the gas valve is de-energized, the
circulator blower is energized at heat speed, and, if flame is
sensed, the inducer blower is energized. The diagnostic indica-
tor light will flash or glow continuously to indicate system status.
(System lockout will never override the precautionary fea-
tures.)

To reset the control after system lockout, do one of the
following:

1.

Interrupt the call for heat or cool at the thermostat for at least
one second but less than 20 seconds (if flame is sensed
with the gas valve de-energized, interrupting the call for
heat at the thermostat will not reset the control).

2.

Interrupt the 24 VAC power at the control for at least one
second. You may also need to reset the flame rollout sensor
switch.

3.

After one hour in lockout, the control will automatically reset
itself.

DIAGNOSTIC FEATURES

The 50A65-843 control continuously monitors its own operation
and the operation of the system. If a failure occurs, the LED will
indicate a failure code as shown below. If the failure is internal
to the control, the light will stay on continuously. In this
case, the entire control should be replaced, as the control
is not field-repairable
.

If the sensed failure is in the system (external to the control), the
LED will flash in the following flash-pause sequences to indicate
failure status (each flash will last approximately 0.25 seconds,
and each pause will last approximately 2 seconds).

1 flash, then pause

System lockout

2 flashes, then pause

Pressure switch stuck closed

3 flashes, then pause

Pressure switch stuck open

4 flashes, then pause

Open limit switch

5 flashes, then pause

Open rollout switch

6 flashes, then pause

115 Volt AC power reversed/Im-
proper ground

7 flashes, then pause

Low flame sense signal

8 flashes, then pause

Check ignitor

Continuous flashing

Flame has been sensed when

(no pause)

no flame should be present (no
call for heat)

The LED will also flash once at power-up.

Summary of Contents for UNIVERSAL INTEGRATED FURANCE CONTROL 50A65-843

Page 1: ...flame sensing element initiate automatic ignition of the burner sensing of the flame and system shut off during normal operation These controls incorporate system fault analysis for quick gas flow sh...

Page 2: ...ponse Time 2 0 sec At 50 Hz all timing specifications should be increased by 20 Gases Approved Natural Manufactured Mixed Liquified Petroleum and LP Gas Air Mixtures are all approved for use TIMING SP...

Page 3: ...lowappliancemanufacturer s recommended installation or service instructions to ensure proper operation The 50A65 has only one serviceable part an automotive type fuse which protects the low voltage tr...

Page 4: ...S VALVE HIGH LIMIT N C AUX HIGH LIMIT N C PRESSURE SWITCH N O FLAME SENSOR PROBE COMPRESSOR CONTACTOR ELECTRONIC AIR CLEANER HUMIDIFIER INDUCER CIRCU LATOR BLOWER 50A65 843 24 VAC 120 VAC 24 VAC CLASS...

Page 5: ...ent low voltage thermostat Y terminal or equivalent 2nd wire from Y terminal goes to 24 VAC HOT side of compressor contactor coil 24 VAC COMMON side of compressor contactor coil gas valve both gas sol...

Page 6: ...delay to fan off period ends the circulator fan and electronic air cleaner are de energized If flame is not detected both valves are de energized the ignitor is turned off and the 50A65 control goes i...

Page 7: ...TURES The 50A65 843 control continuously monitors its own operation and the operation of the system If a failure occurs the LED will indicate a failure code as shown below If the failure is internal t...

Page 8: ...MOUNTING HOLE TEMPLATE FOR MOUNTING HOLE LOCATIONS 4 172 007 2 plcs 6 402 010 2 plcs Refer to page 3 of the installation instructions for proper installation MOUNTING HOLE TEMPLATE...

Reviews: