White Rodgers Electro-Air 10C27S-010 Owner'S Manual Download Page 11

11

TECHNICAL REPAIR GUIDE

All voltage measurements indicated can be made with a
high voltage D.C. probe and a general purpose volt ohm
meter. For example: Simpson 260 or equivalent.

NOTE: All tests to be performed with the Ozone Reduc-
tion Jumper intact.

NOTE: When servicing the power pack components, all
wiring must be routed to factory specifications.

WARNING

!

Do not attempt installation of this unit unless you
are familiar with the necessary tools, equipment,
utility connections and potential hazards.

Installation should be performed only by a quali-
fied service provider.

Failure to do so could result in reduced perfor-
mance of the unit, serious personal injury or
death.

This guide contains service checks to assist service
personnel in locating and correcting any malfunction that
might occur to render the air cleaner ineffective or inop-
erative. The air cleaner has been designed with replace-
able components, such as the high-voltage power supply
and air flow switch. This allows the serviceman to replace
a faulty component rather than attempt repairs of such
components in the field.

The solid-state power supply is not 
designed for individual component part 
replacement and must be replaced as 
a complete "snap-in" unit.

Input voltage: 240 VAC 50/60 Hz.
Output to light: 1.5 to 2.5 VDC
H.V. Output: 6450 VDC (nom)

Collecting Cell

Specifications

Power Supply

Specifications

1000 cfm - 1.0 Ma @ 6450VDC

1400 cfm - 1.2 Ma @ 6450 VDC

1600 cfm - 1.5 Ma @ 6450 VDC

2000 cfm - 1.7 Ma @ 6450 VDC

Operating
Light

Input

Transformer

Power
Supply

Cell Contact
& Insulator

ON/OFF
Switch

Cover Assembly

Power Pack
Assembly

L1

240 VAC
Connector

Wht

White

Orange

Gnd

Red

Wht/Brn
Blk

Blu

L2

Figure 23

Summary of Contents for Electro-Air 10C27S-010

Page 1: ...Service Guide Technical Repair Guide Repair Parts Part No 37 6123D Replaces 37 6123C 0032 Electronic Air Cleaner Printed In U S A UL Listed CSA Certified by White Rodgers Please read and familiarize y...

Page 2: ...it must comply with local electric codes or other applicable codes Review and understand local codes prior to in stallation Failure to do so could result in serious personal injury or death CAUTION CA...

Page 3: ...easy to operate and maintain Its basic components and their functions are as follows See Figure 2 Cabinet mounts to existing duct work and houses the collecting cells and pre filters Collecting Cells...

Page 4: ...ream from the air filter If your furnace duct system has a pre installed boot discard front cover of boot and slide the air cleaner component inside the boot Applies to 14C27S 010 and 20C27S 010 If fu...

Page 5: ...t offset to match air filter opening If duct connection to furnace allows less than nine inches for mounting the air cleaner shorten the lateral trunk or attach an offset fitting to the elbow HORIZONT...

Page 6: ...attached directly Figure 13 or a starting collar can first be fitted to the furnace inlet A butt or slip joint can be used Securely attach the cabinet to furnace inlet using at least two of the mount...

Page 7: ...t electrical connections to the air cleaner are installed properly see Figure 17 The air cleaner should not have power unless the furnace blower is on Floor Conduit Duct Electronic Air Cleaner Figure...

Page 8: ...r service problems see Basic SST UST Service Guide Operating Light On Off Switch 9 Remove junction box cover and install the required bushing into the 3 4 in Knock out With the supply voltage turned o...

Page 9: ...nd rinse thoroughly with clean water 6 Allow cell s and pre filter s to drip dry for a mini mum of 2 hours Cell s and pre filter s may be tipped at a slight angle to expedite the drip dry pro cess 7 R...

Page 10: ...loose ionizing wire s cracked insulator s etc 3 Collecting cells dirty A Clean cells as instructed in this manual 4 Faulty power supply see power supply checkout procedure BASIC SST UST SERVICE GUIDE...

Page 11: ...el in locating and correcting any malfunction that might occur to render the air cleaner ineffective or inop erative The air cleaner has been designed with replace able components such as the high vol...

Page 12: ...tact 4 Using an extension cord apply 240 VAC to power pack Turn power switch to ON position 5 Connect meter negative lead to metal frame of collecting cell Use high voltage probe to measure voltage at...