DIAGNOSTIC TABLE

Green 

LED 

Flash

Amber 

LED 

Flash

Red LED 

Flash

Error/Condition

Comments/Troubleshooting

1

Flame sensed when no flame should 

be present

Verify the gas valve is operating and shutting down properly. Flame in 

burner assemble should extinguish promptly at the end of the cycle. 

Check orifices and gas pressure.

2

Pressure switch stuck closed/ inducer 

error

Pressure switch stuck closed. Check switch function, verify inducer is 

turning off.

3

1st-stage pressure switch stuck 

open/inducer error

Check pressure switch function and tubing. Verify inducer is turning on 

the pulling sufficient vacuum to engage switch.

4

Open limit switch

Verify continuity through rollout switch circuit.

5

Open rollout/open fuse detect

Verify continuity through rollout switch circuit, check fuse.

6

1st-stage pressure switch cycle 

lockout

if the first stage pressure switch cycles 5 times (open, closed) during 

one call for heat from the thermostat the control will lockout. Check 

pressure switch for fluttering, inconsistent closure or poor vacuum 

pressure.

7

External lockout (retries)

Failure to sense flame is often caused by carbon deposits on the 

flame sensor, a disconnected or shorted flame sensor lead or a poorly 

grounded furnace. Carbon deposits can be cleaned with emery cloth. 

Verify sensor is not contacting the burner and is located in a good 

position to sense flame. Check sensor lead for shorting and verify 

furnace is grounded properly.

8

External lockout (ignition recycles 

exceeded where flame is established 

and then lost)

Check items for exceeded retries listed above and verify valve is not 

dropping out allowing flame to be established and then lost.

9

Grounding or Reversed polarity

Verify the control and furnace are properly grounded. Check and 

reverse polarity (primary) if incorrect.

10

Module gas valve contacts energized 

with no call for heat

Verify valve is not receiving voltage from a short. If a valve wiring is 

correct and condition persists, replace module.

11

Limit switch open – possible blower 

failure overheating limit

Possible blower failure, restricted air flow through appliance or 

duct work. Verify continuity through limit switch circuit and correct 

overheating cause.

12

Module Ignitor contact failure

Fault code indicates the module ignitor contacts are not functioning 

properly. Replace module.

Solid

Module - internal fault condition

Module contacts for gas valve not operating or processor fault. Reset 

control. if condition persists replace module.

Rapid

Twinning error

Check wire connections. If condition persists, replace module.

double

2nd-stage Pressure Switch Stuck 

Open/Inducer Error

Check pressure switch function and tubing. Verify inducer is turning on 

and pulling sufficient vacuum to engage switch.

1

Normal Operation with call for first 

stage heat

Normal operation - first stage

2

Normal Operation with call for second 

stage heat

Normal operation - first stage

3

W2 present with no W1

Second stage call for heat on thermostat circuit with no call for first 

stage. Verify dip switches are set for two stage thermostat and check 

thermostat first stage circuit. Configured for a multi-stage thermostat 

the Module will not initiate heating unless first stage call from 

thermostat is received.

4

Y present with no G call

Module will allow cooling to operate with only a "Y signal from the 

thermostat but will also trigger this code. Verify thermostat is energizing 

both "Y" and "G" on call for cool. Check "G" terminal connections.

Rapid

Low flame sense current

Low flame sense current is often caused by carbon deposits on the 

flame sensor, a poorly grounded furnace or a mis-aligned flame sense 

probe. Carbon deposits can be cleaned with emery cloth. Check for 

improve furnace and module ground. Verify sensor is located in or very 

near flame as specified by the appliance manufacturer.

1

Standby or Call for Cool

Normal operation. Waiting for call from thermostat or receiving 

thermostat call for cool.

Solid

Standby

Rapid

Normal Operation with call for fan (G)

1

Normal Operation with call for Low 

stage cool (YLO + G)

2

Normal Operation with call for 

High stage cool/or single stage 

cooling(YLO + G)

TROUBLESHOOTING 

White-Rodgers is a business 
of Emerson Electric Co.

The Emerson logo is a  
trademark and service mark 
of Emerson Electric Co.

www.white-rodgers.com

www.emersonclimate.com

Summary of Contents for 50M58-289

Page 1: ...s recommended installation service instructions to ensure proper operation 50M58 289 2 Stage X 13 Style Hot Surface Ignition Control INSTALLATION INSTRUCTIONS FAILURETO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND OR PROPERTY DAMAGE PRECAUTIONS CONTENTS Description 1 Precautions 1 Specifications 2 Installation 3 Mounting Wir...

Page 2: ...period of time between energizing the main gas valve and deactivation of the ignition means prior to the end of TFI 3 Retries The additional attempts within the same thermostat cycle for ignition when the supervised main burner flame is not proven within the first trial for ignition period 2 times Valve Sequence period Valve sequence period equals 5 seconds trial for ignition period x 1 initial tr...

Page 3: ...nnections UL approved 105o C rated 16 gauge min stranded 1 16 thick insulation wire is recommended for all line voltage connections Afterinstallationorreplacement followappliancemanufacturer s recommended installation or service instructions to insure proper operation The 50M58 has only one serviceable part an automotive type fuse which protects the low voltage transformer from damage if its outpu...

Page 4: ...D LO IND N IGN N CIRC N LINE N XFMR N HUM N EAC N R W2 W1 Y R W2 W1 Y2 CONDENSING UNITS 50M58 289 in other furnace THERMOSTAT FLAME SENSOR PROBE 2ND STAGE PRESSURE SWITCH N O HIGH LIMIT N C AUX HIGH LIMIT N C 1ST STAGE PRESSURE SWITCH N O GAS VALVE HLO HLI FP PS1 MVL MVH GND GND PS2 MV COM TR TH Low Voltage 24 VAC Line Voltage 120 VAC G G ROLLOUT SWITCH N C LEGEND N C Normally closed switch N O No...

Page 5: ...alve FIRST STAGE W2 two stage thermostat W2 terminal or equivalent IGN 1 ignitor HOT side IGN N 5 ignitor NEUTRAL side circulator blower terminal TAP 1 L1 1 4 spade terminal input voltage 120 VAC HOT SIDE T1 XFMR 1 4 spade terminal 24 VAC transformer line voltage HOT SIDE EAC H 1 4 spade terminal air cleaner HOT side HUM 1 4 spade terminal humidifier HOT side CIRC N 1 4 spade terminal circulator b...

Page 6: ...On 4 Off On Off On 90 sec 120 sec 150 sec 180 sec Factory default setting OPTION SWITCHES S1 1 S1 2 POSITIONS COOL CIRCULATOR SPEED 2nd Stage delay for single stage thermostats Delay Time On S1 set switch 1 2 Off Off Off 10 min On Off Auto min Off On 20 min On On Factory default setting two stage thermostat OPTION SWITCH S3 POSITION HEAT CIRCULATOR SPEED DIP Switch S3 Setting S3 1 2 1 2 1 2 1 2 Po...

Page 7: ...emory the LED will flash two green flashes The control will flash the most re cent error first and the oldest error last last in first out There shall be 2 seconds between codes Solid LED error codes will not be displayed FAULT CODE RESET To clear the fault code memory push and hold the LAST ER ROR button for more than 5 seconds and less than 10 seconds Control will indicate this period by RAPID G...

Page 8: ...wer failure restricted air flow through appliance or duct work Verify continuity through limit switch circuit and correct overheating cause 12 Module Ignitor contact failure Fault code indicates the module ignitor contacts are not functioning properly Replace module Solid Module internal fault condition Module contacts for gas valve not operating or processor fault Reset control if condition persi...