background image

HEAT PUMP TERMINAL OUTPUTS

Refer to equipment manufacturers’ instruc-
tions for specific system wiring information.

You can configure the thermostat for use
with the following heat pump system types:

HEAT PUMP TYPE 1. Single-stage
compressor system; gas or electric backup.

HEAT PUMP TYPE 2. Multi-stage or two-
compressor system; gas or electric backup.

This thermostat is designed to operate a
single-transformer system. If you have a two-
transformer system, cut and tape off one
transformer.  If transformer safety circuits are
in only one of the systems, remove the
transformer of the system with NO safety
circuits. If required, replace remaining
transformer with a 75VA Class II transformer.
After disconnecting one transformer, the two
commons must be jumpered together.

Use the terminal output information below to
help you wire the thermostat properly for
your heat pump system type. After wiring,
see CONFIGURATION section for proper
thermostat configuration.

MULTI-STAGE TERMINAL  OUTPUTS

Refer to equipment manufacturers’ instruc-
tions for specific system wiring information.

You can configure the thermostat for use
with either multi-stage electric heat systems
or multi-stage gas systems. When configured
for electric heat, the G terminal (blower/fan)
will be energized on a call for heat, using the
installer table (pgs. 5 & 6).

This thermostat is designed to operate a
single-transformer system. If you have a two-
transformer system, cut and tape off one
transformer.  If transformer safety circuits are
in only one of the systems, remove the
transformer of the system with NO safety
circuits. If required, replace remaining
transformer with a 75VA Class II transformer.
After disconnecting one transformer, the two
commons must be jumpered together.

Use the terminal output information below to
help you wire the thermostat properly for
your multi-stage system. After wiring, see
CONFIGURATION section for proper
thermostat configuration.

THERMOSTAT TERMINALS (Upper)

L

SA

SB

SC

OT

Malfunction Light/

Remote Sense A

Remote Sense B

Remote Sense C

Outdoor Sensor

Comfort Alert
Interface Module

THERMOSTAT TERMINALS (Upper)

L

SA

SB

SC

OT

Malfunction Light/

Remote Sense A

Remote Sense B

Remote Sense C

Outdoor Sensor

Comfort Alert
Interface Module

3

THERMOSTAT TERMINALS (Lower)

SYSTEM

C

R

HM

W2

DHM

E/W1

Y2

Y1

B

O

G

Multi-Stage

24 Volt 

(Common)

24 Volt 

(Hot)

Energizes on a 

call for heat if 

Humidity setpoint is

above room

humidity.

Heat mode 

2nd stage

E2/P switch in the P position, 

Energizes on a call for 

Dehumidification. 

E2/P switch in E2 position, 

De-energizes on a 

call for Dehumidification. 

Heat mode 

1st stage

Cool mode 

2nd stage

Cool mode 

1st stage

Energized in Heat 

and Off Mode

Energized in 

Cool Mode

Blower/Fan 

Energized on 

call for Cool 
(and Heat if 

configured 

to Electric Heat).

THERMOSTAT TERMINALS (Lower)

SYSTEM

C

R

HM

W2

DHM

E/W1

Y2

Y1

 B

O

G

Heat Pump 1

24 Volt 

(Common)

24 Volt 

(Hot)

Energizes on a 

call for heat if 

Humidity setpoint is

above room

humidity.

Heat mode 

3rd stage, 

Emergency Mode

2nd stage

E2/P switch in P position, 

Energizes on a call for 

Dehumidification. 

E2/P switch in E2 position, 

De-energizes on a 

call for Dehumidification.

Heat mode 

2nd stage, 

Emergency Mode

1st stage

No Output

Heat and

Cool mode 

1st stage

(compressor 1)

Energized in Heat, 

Off, Emergency

Mode

Energized in 

Cool Mode

Blower/Fan 

Energized on 

call for Heat and Cool 

Single-stage compressor system; gas or electric backup

 Multi-stage or two compressor system; gas or electric backup

Heat Pump 2

24 Volt 

(Common)

24 Volt 

(Hot)

Energizes on a 

call for heat if 

Humidity setpoint is

above room

humidity.

Emergency Mode

2nd stage

E2/P switch in P position, 

Energizes on a call for 

Dehumidification. 

E2/P switch in E2 position, 

De-energizes on a 

call for Dehumidification.

Heat mode 

3rd stage, 

Emergency Mode

1st stage

Heat and

Cool mode 

2nd stage

(compressor 2)

Heat and

Cool mode 

1st stage

(compressor 1)

Energized in Heat, 

Off, Emergency

Mode

Energized in 

Cool Mode

Blower/Fan 

Energized on 

call for Heat and Cool

Summary of Contents for 1F95CA-391

Page 1: ...t or incorrect wiring will damage thermostat and could cause personal injury and or property damage Do not use on circuits exceeding specified voltage Higher voltage will damage thermostat and could cause shock or fire hazard Thermostat installation and all compo nents of the system shall conform to Class II circuits per the NEC code To prevent electrical shock and or equipment damage disconnect e...

Page 2: ...es from the old thermostat one at a time DO NOT let the wires fall back into the wall Install the new thermostat using the follow ing procedures ATTACH BASE TO WALL Remove packing material from the thermo stat Place fingers of one hand on the center top and bottom portion of the thermostat Grasp the base in the other hand on top and bottom center and gently pull straight out Forcing or prying on t...

Page 3: ...ection for proper thermostat configuration THERMOSTAT TERMINALS Upper L SA SB SC OT Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor Comfort Alert Interface Module THERMOSTAT TERMINALS Upper L SA SB SC OT Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor Comfort Alert Interface Module 3 THERMOSTAT TERMINALS Lower SYSTEM C R HM W2 DHM E W1 Y2...

Page 4: ...YSTEM ONLY If you have a single stage compressor system see the diagram below A relay customer provided should be installed as shown in Fig 5 to switch the fan speed to the next lower speed on a call for dehumidification from the thermostat The reduction in air flow allows the coil to remove more humidity from the air The relay should be rated for blower motor load Since this configuration reduces...

Page 5: ...h 6 step 6 is for heat pump only These items allow the cycle times in heating cooling and auxiliary heat pump systems only to be increased or decreased The factory set values can be adjusted higher for longer cycles or lower for shorter cycles NOTE Some manufacturers still instruct you to set the anticipator to the current draw of the equipment That instruction applies only to mercury bulb or mech...

Page 6: ... in sequence after HEAT if HEAT PUMP is selected Program RUN TIME FWD Heat Pump ONLY TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD 6 SET CYCL AUX 08 1 to 40 9 HEAT FAN DELA OFF 00 0 to 127 seconds 10 PUMP ON OFF 11 COMP OFF DELA 60 0 to 99 7 COOL FAN DELA OFF 00 0 to 127 seconds 8 5 5 5 5 5 5 5 5 7 7 7 7 7 7 5 5 FAN DELA ON 01 1 to 30 seconds Selects time delay for fan ON Applies ...

Page 7: ...nst premature compressor failure by locking out the compressor for at least five minutes after each cycle When the thermo stat is in compressor lockout the word COOL will flash on the display With heat pump systems the word HEAT will flash if the lockout occurs during a heat cycle During this period the compressor will not be energized COMFORT ALERT WITH ACTIVE PROTECTION Installer table step 16 T...

Page 8: ...t service interval SERVICE REMINDER 8 1 Step Press Button s Displayed Press or to select COMMENTS Factory Default PAD TIME OFF Hrs or REM PAD TIME No of Hrs ON or OFF Set Humidifier Maintenance Reminder SERVICE 3 FLTR TIME OFF Hrs or REM FLTR TIME No of Hrs ON or OFF Set Air Filter Maintenance Reminder TIME FWD Service Button Menu Returns to Normal Operation PRGM RUN 2 SET PAD TIME 100 Hrs 25 to 1...

Page 9: ...e and yellow for second stage EMERGENCY heat pump only Press SYSTEM to select EMER mode The LED indicator will glow red for first stage Aux in emergency mode A flashing red LED indicates a malfunction in the system HUMIDIFIER SYSTEM IF INSTALLED 1 Press SYSTEM until HEAT is shown at the top of the display 2 Press the HUMIDITY button once and release Then press the to the maximum humidity setpoint ...

Page 10: ...t does not respond when keys are pressed or the thermostat is not operating properly you may use the reset button located on the back of the thermostat body see fig 2 Thermostat programming and configuration will not be affected by pressing the reset button However the clock will need to be reset RESETTING THERMOSTAT CONFIGURATION AND PROGRAMMING The thermostat can be reset back to default program...

Page 11: ... the size Digital thermostats normally provide precise narrow or wide temperature swing of the Heating System equipment may be temperature control and may cycle faster than influencing the cycle rate someoldermechanicalmodels Afastercycle ratemeanstheunitturnsononoffmorefrequently but runs for a shorter time so there is no increase in energy use If you would like to increase the cycle time refer t...

Page 12: ... will indicate HOLD and the number of hours remaining in the hold period will be indicated with the word HRS To adjust the length of time for the override press TIME FWD or TIME BACK The time you select will become the new number of hours for the Hold Til timing Once your time is selected let the thermostat revert back to normal operation on its own to accept the change Many furnaces have safety d...

Reviews: