background image

9

TROUBLESHOOTING 

Reset Operation

If  a  voltage  spike  or  static  discharge  blanks  out  the  display 
or  causes  erratic  thermostat  operation,  reset  the  thermostat 
by  pressing  the 

  and TIME  buttons  simultaneously. 

If the thermostat has power, has been reset and still does not 
function correctly contact your heating/cooling service person 
or place of purchase. 

Symptom

Possible Cause

Corrective Action

No Heat/No Cool/No Fan
(common problems)

1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or  
    panel loose or not properly installed.

Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety 
interlock or door switch.

No Heat

1. System Switch not set to Heat.

2. Loose connection to thermostat or 
    system
3. Heating System requires service or 
    thermostat requires replacement.

Set System Switch to Heat and raise setpoint above 
room temperature.
Verify thermostat and system wires are securely attached.
Diagnostic: Set System Switch to Heat and raise the 
setpoint above room temperature. Within a five minutes 
the thermostat should make a soft slick sound. This 
sound usually indicates the thermostat is operating 
properly. If the thermostat does not click, try the reset 
operation listed above. If the thermostat does not click 
after being reset contact your heating and cooling 
service person or place of purchase for a replacement. 
If the thermostat clicks, contact the furnace manufac-
turer or a service person to verify the heating system is 
operating correctly.

No Cool

1. System Switch not set to Cool.

2. Loose connection to thermostat or 
    system.
3. Cooling System requires service or 
    thermostat requires replacement

Set System Switch to Cool and lower setpoint below 
room temperature.
Verify thermostat and system wires are securely attached.
Same procedures as diagnostic for No Heat condi-
tion except set the thermostat to Cool and lower the 
setpoint below the room temperature. There may be up 
to a five minute delay before the thermostat clicks in 
Cooling if the compressor lock-out option is selected in 
the configuration menu (Item 6). 

Heat, Cool or Fan Runs 
Constantly

1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in Heat/Cool/Fan 
    system.
4. Fan Switch set to Fan On.

Check each wire connection to verify they are not 
shorted or touching together. No bare wire should 
stick out from under terminal screws. Try resetting the 
thermostat as described below. If the condition persists, 
the manufacturer of your system or service person 
can instruct you on how to test the Heat/Cool/ system 
for correct operation. If the system operates correctly, 
replace the thermostat.

Furnace Cycles Too Fast or Too Slow 
Cooling Cycles Too Fast or Too Slow 
(narrow or wide temperature swing)

1. The location of the thermostat and/
    or the size of the Heating or Cooling 
    System may be influencing the 
    cycle rate.

Item 4 (CR Heat) or 5 (CR Cool) in the Configuration 
Menu is the adjustment that controls the cycle rate. If 
an acceptable cycle rate is not achieved using the FA 
(Fast) or SL (Slow) adjustment contact a local service 
person for additional suggestions.

Thermostat Setting and 
Thermometer Disagree

1. Thermostat thermometer setting 
    requires adjustment.

The thermometer can be ad/-4 degrees as 
listed in item 8 of the Configuration Menu. No other 
adjustment is possible.

Clock Loses or Gains Time

1. Loss of power to thermostat.

The thermostat will maintain its program in memory 
even with no power but the clock time will be incorrect 
when power is restored. See No Heat/No Cool /No Fan 
(common problems) above for items to check in the 
system. 

Heat or Cool Starts Early

1. EMR activated.

See Configuration Menu (Item 3)

Thermostat Does Not Follow 
Program

1. AM or PM set incorrectly in program.
2. AM or PM set incorrectly on the clock.
3. Voltage spike or static discharge.
4. See “Heat or Cool Starts Early” above.

Check current clock and program settings including 
the AM or PM designations for each time period. If a 
voltage spike or static discharge occurs use the Reset 
Operation listed above.

Blank Display and/or Keypad Not 
Responding

1. Voltage Spike or Static Discharge.

If a voltage spike or static discharge occurs use the 
Reset Operation listed above.

Summary of Contents for 1F87-0261

Page 1: ...7 0261 Thermostat Model Programming Choice 1F87 0261 7 Day Programmable SPECIFICATIONS Electrical Rating Battery Power mV to 30 VAC 50 60 Hz or DC Input Hardwire 20 to 30 VAC Terminal Load 1 0 A per terminal 1 5A maximum all terminals combined Setpoint Range 45 to 90 F 7 to 32 C Differential Single Stage Heat 0 6 F Cool 1 2 F adjustable Differential Heat Pump Heat 1 2 F Cool 1 2 F adjustable Opera...

Page 2: ...e O B switch on this thermostat is factory set to the O position This will accommodate the majority of heat pump applications which require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay in HEAT the O B switch must be moved to the B position Mounting Hole M...

Page 3: ...of the next program period To deactivate the EMR function see the Configuration menu on Page 5 The thermostat will then wait until the programmed time to start the system for a temperature change INSTALLATION WIRING DIAGRAMS R C 24 VAC 120 VAC Hot Neutral THERMOSTAT SYSTEM G W Figure 2 Typical wiring diagram for single transformer single stage systems TRANSFORMER Class II Current Limited Changeove...

Page 4: ...lace the cover line up the cover with the base and press until the cover snaps onto the base The Thermostat Buttons and Switches 1 Raises temperature setting 2 Lowers temperature setting 3 TIME button 4 SYSTEM switch COOL OFF HEAT EMER 5 PRGM program button 6 FAN switch ON AUTO 7 RUN HOLD program button The Display 8 Indicates days of the week 9 Indicates setpoint temperature This is blank when sy...

Page 5: ... humidity in the home will be lower and a higher setpoint temperature will feel comfortable After 20 minutes of run time the thermostat will start increasing the setpoint temperature in steps of less than one degree as the system continues to run These adjustments will eventually cause the system to satisfy the thermostat and turn the system off to reduce the energy consumption When the Cool Savin...

Page 6: ...reminder On or OFF If selected On press RUN HOLD to select the time period from 25 to 1975 hours in 25 hour increments In a typical application 200 hours default of run time is approximately 30 days After the selected time of blower operation the thermostat will display Change Filter as a reminder to change or clean your air filter When Change Filter is displayed press the RUN HOLD button to clear...

Page 7: ...t Current Time and Day 1 Press TIME button once The display will show the hour only EXAMPLE 2 Press and hold either or until you reach the correct hour and AM PM designation AM begins at midnight PM begins at noon 3 Press TIME once again The display window will show the minutes only EXAMPLE 4 Press and hold either or until you reach the correct minutes 5 Press TIME once again The display will show...

Page 8: ...g Program 1 Move SYSTEM switch to COOL position 2 Follow Enter Heating Program for entering your cooling program using your selected cooling times and temperatures PROGRAMMING If the outside temperature is below 50o F disconnect power to the cooling system before programming Energizing the air conditioner compressor during cold weather may cause personal injury or property damage CAUTION CHECK YOU...

Page 9: ...hermostat clicks in Cooling if the compressor lock out option is selected in the configuration menu Item 6 Heat Cool or Fan Runs Constantly 1 Possible short in wiring 2 Possible short in thermostat 3 Possible short in Heat Cool Fan system 4 Fan Switch set to Fan On Check each wire connection to verify they are not shorted or touching together No bare wire should stick out from under terminal screw...

Page 10: ...10 NOTES ...

Page 11: ...11 NOTES ...

Page 12: ...www white rodgers com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 ...

Reviews: