background image

Figure 3 – Single Stage or Multi-Stage System (No Heat Pump)

with Two Transformers

Single
Stage 1

(SS1)

Multi-
Stage 2

(MS2)

O

Energized

Constantly

in

Cool Mode

B

Energized

Constantly

in Heat, Off,

Emergency

Mode

No
Output

Cool
Mode
2nd
Stage

Cool Mode
1st Stage

Blower/
Circulator
Fan Energized
on Call for
Cool (and
Heat if
configured
for Electric
Heat)

No Output

Heat Mode
2nd Stage

Heat
Mode
1st Stage

Optional 

24 Volt

(Com-

mon)

Fault
Indicator
(NOT
USED)

24 Volt
(Hot)
Cool

System

Y

G

W/E

C

L

RC

CLASS II

TRANSFORMER

HOT

24VAC

NEUTRAL

120VAC

24 Volt
(Hot)
Heat

RH

120VAC

Remove Jumper Wire
between RH & RC

HOT

24VAC

NEUTRAL

CLASS II

TRANSFORMER

HEATING

COOLING

Y2

W2

Jumper

O/B

Single Stage
3-wire
Zone Valve
application

Blower/Circulator
Fan Energized

Opens
Valve
(4)

Constant

24 Volt

(Com-

mon)

24 Volt
(Hot)
Cool

System

6

Y

W

C

RC

CLASS II

TRANSFORMER

HOT

24VAC

NEUTRAL

120VAC

24 Volt
(Hot)
Heat
(5)

RH

G

Jumper

Closes
Valve
(6)

NOTE: 

If continuous backlight or 

hardwired power input are desired but 
do not function in both HEAT and COOL 
modes, cut the heating transformer 24V 
wires and tape off. Connect the neutral 
circuit disconnected from the heating 
transformer to the neutral circuit of the 
cooling transformer. Disconnect the wire 
to the RH terminal and install a jumper 
between RH and RC. Depending on 
the system requirements, replace the 
cooling transformer with a 75VA class II 
transformer if needed.

Figure 4 – 3-Wire (SPDT) Heat Only Zone Valve Wiring