background image

13369-1-0203

Page 19

DVS-30 FRAMING AND FINISHING

Installing Support Brackets (Figure 29)
A horizontal pipe support MUST BE used for each 3 feet of
horizontal run. The pipe supports should be placed around 8 inch
diameter pipe and nailed in place to framing members. There
MUST BE a 3 inch clearance to combustibles above 6 5/8 inch
diameter pipe and elbows and 1 inch clearance on both sides and
bottom of  6 5/8 inch pipe to combustibles on all horizontal pipe
sections and elbows.

Vertical runs of this vent systems must be supported every 4
feet above the appliance flue outlet by wall brackets attached
to the  6 5/8  inch vent pipe and secured with nails or screws
to structural framing members.

 

Figure 29

Installing Firestops (Figures 30, 31, 32 and 33)
Firestops are required for safety whenever the vent system passes
through an interior wall, an exterior wall, or a ceiling. These
firestops act as a firebreak heat shield and as a means to insure that
minimum clearances are maintained to the vent system.

Horizontal runs in the vent system which pass through either
interior or exterior walls, require the use of wall firestops on both
sides of the wall through which the vent passes.

Position the firestops on both sides of the 10 inch x 10 inch hole,
previously cut. Secure with nails or screws. The heat shields of
the firestops MUST BE placed towards the top of the hole.
Continue the vent run through the firestops. (Figure 30)

Figure 30

Vertical runs of this system which pass through ceilings require
the use of ONE (1) ceiling firestop at the hole in each ceiling
through which the vent passes.

Position a plumb bob directly over the center of the vertical vent
component and mark the ceiling to establish the center point of
the vent. Drill a hole or drive a nail through this center point and
check the floor above for any obstructions such as wiring or
plumbing runs. Reposition the appliance and vent system, if
necessary, to accommodate ceiling joists and/or obstructions.

Cut a 10 inch x 10 inch hole through the ceiling, using the center
point previously marked. Frame the hole with framing lumber the
same size as the ceiling joists. (See Figure 31) If the area above
the ceiling is NOT an attic, position and secure the ceiling firestop
(SD-963) on the ceiling side of the previously cut and framed
hole. (See Figure 32) If the area above the ceiling IS an attic,
position and secure the firestop on top of the previously framed
hole. (See Figure 33)

NOTE:  Remove insulation from the framed area in the attic
before installing the firestop and/or vent pipes.

Summary of Contents for DVS-30RF-2

Page 1: ...pors and liquids in the vicinity of this or any other appliance WHAT TO DO IFYOU SMELLGAS Do not try to light any appliance Donottouchanyelectricalswitch donotuseanyphoneinyourbuild ing Immediatelycallyourgassupplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas sup plier call the fire department Installation and service must be per formedbyaqualifiedi...

Page 2: ...ng Pilot Lighting Instructions 29 Standing Pilot Troubleshooting 30 DVS 36 DVS 42 Intermittent Pilot Operating Instructions 31 DVS 36 DVS 42 Intermittent Pilot Wiring Diagram 31 DVS 36 DVS 42 Intermittent Pilot Lighting Instructions 32 DVS 36 DVS 42 Intermittent Pilot Troubleshooting 33 36 RF Standing Pilot Operating Instructions 37 RF Wiring Diagram with Optional Blower 38 RF Standing Pilot Light...

Page 3: ...y Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies The glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment clean Vent cap is hot while fireplace is in operation Installation and repair should be ...

Page 4: ...m service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of new cylinders and tanks is possible Therefore people should be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new tanks or reinstalled old tank...

Page 5: ...an National Standards Institute Inc 11 West 42nd St New York N Y 10036 WARNING ANY CHANGE TO THIS FIREPLACE OR ITS CONTROLS CAN BE DANGEROUS Improperinstallationoruseoftheheatercancauseserious injury or death from fire burns explosion or carbon monoxide poisoning Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shown on the rat...

Page 6: ...G T 750MillivoltWallThermostat OnlyusedwhenDVS 36 or DVS 42 fireplace is converted into a heater FRBC 1 Battery Operated Remote Control FRBTC 1 Battery Operated Remote Control with Thermostat Only used when DVS 36 or DVS 42 fireplace is converted into a heater FREC 1 Electric Remote Control FWS 1 Wall Switch EK 1 Embers Kit FB BK 2 Variable Speed Automatic Blower FBB1A Single Speed Automatic Blowe...

Page 7: ...Release two door latches at bottom of firebox 4 Grasp bottom of glass frame lift glass frame upward in order to release glass frame from lip on top of firebox 5 Insert heater baffle into interior top of fireplace The heater baffle will be installed in front of 5 diameter vent outlet Align two 2 clearance holes on heater baffle with two 2 screws within interior top of fireplace Remove two 2 screws ...

Page 8: ...HEADER STAND OFF STAND OFF 3 76mm HEIGHT 3 76mm HEIGHT ABOVE TOP OF FIREPLACE GLASS FRONT GLASS FRONT TOP FRAMING LEDGE FINISHED WALL FINISHED WALL ADJUSTABLE NAILING FLANGES SEE MANTLE CHART SEE MANTLE CHART FOR MAXIMUM MANTLE FOR MAXIMUM MANTLE DEPTH SEE MANTLE CHART SEE MANTLE CHART FOR MINIMUM HEIGHT FOR MINIMUM HEIGHT OF MANTLE ABOVE UNIT OF MANTLE ABOVE UNIT CLEARANCE TO COMBUSTIBLES BACK 0 ...

Page 9: ...useanexposedflametocheckforleaks Appliancemust be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage NOTE The gas control is equipped with a captured screw type pressure test point therefore it is not necessary to provide a 1 8 test point up stream of the control A gas valve ...

Page 10: ... wall flange must not exceed 6 5 feet EXAMPLE B If the vertical dimension from the floor of the unit is 6 5 feet thehorizontalruntotheouterwallflangemustnotexceed14 5 feet SPECIAL NOTE For each 45 degree elbow installed in the horizontal run the length of the horizontal run MUST be reduced by 18 45cm This does not apply if the 45 degree elbows are installed on the vertical part of the vent system ...

Page 11: ...als may be used to cover the black fireplace front WARNING When finishing the fireplace never obstruct or modify the air inlet outlet louvers in any manner Provide adequate clearances around air openings into the combustion chamber Caution If the joints between the finished wall and the fireplace surround top and sides are sealed a 300 F mini mum sealant material must be used These joints are not ...

Page 12: ...02mm TO 143mm 14 1 8 TO 17 5 8 14 1 8 TO 17 5 8 11 1 8 TO 14 5 8 11 1 8 TO 14 5 8 5 5 8 TO 11 5 8 5 5 8 TO 11 5 8 4 TO 5 5 8 4 TO 5 5 8 Figure 15 VERTICAL 90 ELBOW TO HORIZONTAL OUT THE WALL WALL FIRESTOP WALL FIRESTOP 275mm TO 344mm 275mm TO 344mm 240mm TO 268mm 240mm TO 268mm 356mm TO 421mm 356mm TO 421mm 14 TO 16 9 16 14 TO 16 9 16 10 13 16 TO 13 9 16 10 13 16 TO 13 9 16 9 7 16 TO 10 9 16 9 7 1...

Page 13: ... 1 2 4 TO 7 1 2 B Figure 18 Vertical Sidewall Application Figure 19 Figure 20 and Chart 1 lists examples of possible venting systems using one 1 90 elbow Eight 8 feet is listed as maximum vertical vent run with 20 feet of maximum horizontal vent run Vertical dimensions are based on centerline to centerline of pipe Horizontal dimensions are based on centerline of pipe to end of termination SEE CHAR...

Page 14: ...um 6 minimum 12 maximum 7 minimum 15 maximum 8 minimum 20 maximum 25 maximum vertical 20 maximum horizontal run Figure 21 and Chart 1 list examples of possible venting systems using two 2 90 elbows V is listed as minimum vertical dimensions and H1 H2 is listed as total of maximum horizontal dimensions The maximum vertical and horizontal distances for two 2 90 elbows as shown in Figure 21 are 20 fe...

Page 15: ...ee Figures 22 and 23 When locating the hole it must be noted that the bottom of the cap must be 12 above the ground level and top of the cap must be no less than 18 below a combustible projection and no closer than 9 to any wall running parallel to vent termination See Figure 24 Figure 24 3 914 mm 914 mm 20 6 1 M 20 6 1 M MAX MAX 8 244 cm 8 244 cm TO BOTTOM TO BOTTOM OF UNIT OF UNIT PIPE STRAPS PI...

Page 16: ...he fireplace in such a way that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust certain limitations as to vent configurations apply and must be strictly adhered to The graph showing the relationship between vertical and horizontal side wall venting will help...

Page 17: ...ontally from the center line of the regulator I clearance to service regulator vent outlet 6 feet 1 8m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 inches 30cm minimum for appliances 100 000 Btuh 30 kW 36 inches 90cm minimum for appliances 100 000 Btuh 30kW K clearance to a mechanical air supply inlet 6 feet 1 8m minimum L...

Page 18: ...e is now locked together Continue adding components per the pre planned vent system configuration Be certain that each succeeding vent component is securely fitted and locked into the preceding component in the vent system Figure 28 Venting Components Simpson Dura Vent Part Number Part Number Description DVS 30 DVS 36 DVS 42 SD 908B SD 1208 6 Pipe Length SD 907B SD 1207 9 Pipe Length SD 906B SD 12...

Page 19: ...t passes Position the firestops on both sides of the 10 inch x 10 inch hole previously cut Secure with nails or screws The heat shields of the firestops MUST BE placed towards the top of the hole Continue the vent run through the firestops Figure 30 Figure 30 Vertical runs of this system which pass through ceilings require the use of ONE 1 ceiling firestop at the hole in each ceiling through which...

Page 20: ...Page 20 13369 1 0203 Figure 31 Figure 32 Figure 33 See Horizontal Termination for all Models Page 22 and Vertical Termination for all Models Page 23 24 DVS 30 FRAMING AND FINISHING continued ...

Page 21: ...an interior wall an exterior wall or a ceiling These firestopsactasafirebreakheatshieldandasameanstoinsurethat minimum clearances are maintained to the vent system Cut a 10 3 8 inch x 12 3 8 inch hole in wall Position firestop SD 1249 on interior side of wall for 10 3 8 inch x 12 3 8 inch hole Attention Wall firestop hole is off set towards bottom of wall opening Secure with nails or screws Contin...

Page 22: ...cap should pass through the wall firestop from the exterior of the building Adjust the termination cap to its final exterior position on the building WARNING Termination cap must be positioned so that arrow is pointing up Attach the termination cap with the four wood screws provided Before attachment of the termination run a bead of silicone sealant rated above 250 F on its outside edge too so as ...

Page 23: ...idence of excessive condensate such as water droplets forming in the inner liner and subsequently dripping outatjoints Continuecondensatecancausecorrosionofcaps pipe and fittings It may be caused by having excessive lateral runs too many elbows and exterior portions of the system being exposed to cold weather 4 Inspect joints to verify that no pipe sections or fittings have been disturbed and cons...

Page 24: ...orpreviouslyinstalledcomponent end with four 4 equally spaced indented sections When the internal beads of each starting outer pipe line up rotate pipe section clockwise 90 approximately 3 inches The vent pipe is now locked together Continuereplacingcomponentspertheventsystemconfiguration Be certain that each succeeding vent component is securely fitted and locked into the preceding component in t...

Page 25: ... slots casing top Push downward to lock the top louver into position Refer to Figures 43 44 and 45 for the following warning Warning Failure to position the parts in accordance with this diagram or failure to use only parts specifically approved with this appliance may result in property damage or personal injury Attention Do not use Figure 44 or Figure 45 to order logs Refer to Pages 41 42 and 43...

Page 26: ...ur fireplace STANDING PILOT OPERATING INSTRUCTIONS HI LO REGULATOR CONTROL KNOB PIEZO IGNITOR Placement of the glowing embers rock wool is very individual and light coverage of the areas indicated will provide your best effects We recommend separation of the rock wool by hand and make your coverage as light and fluffy as possible Place just enough rock wool on the burner to obtain the glow and a g...

Page 27: ... It is important to use wire of a gauge proper for the length of the wire RECOMMENDED WIRE GAUGES Maximum Wire Length Gauge 1 to 10 18 10 to 25 16 25 to 35 14 Wall Switch FWS 1 Connect the green and red stripped and bare wires on the ON OFF REMOTE switch wire harness to the wall switch Turn the ON OFF REMOTE switch to the REMOTE position Pivot the rocker switch on the FWS 1 to the ON position Batt...

Page 28: ...le Attention The velcro loop and hook are not necessary in this installation but can be used to secure remote receiver Refer to remote control installation and operating instructions for more details on remote control STANDING PILOT OPERATING INSTRUCTIONS continued Millivolt Control The valve regulator controls the burner pressure which should be checked at the pressure test point Turn captured sc...

Page 29: ...bove If you do not smell gas go to the next step 7 Findpilot Followmetal tubefromgascontrol The pilot is behind the second log on the left side TO TURN OFF GAS TO FIREPLACE FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A Thisfireplacehasapilotwhichmustbelightedbyhan...

Page 30: ...he gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading at TH TP TP terminals of the gas valve The meter should read 350 millivolts minimum while holding the valve knob depressed in the PILOT position with the pilot lit and the ON OFF switch in the OFF position Replace the faulty thermopile if the rea...

Page 31: ...e receiver DVS 36 DVS 42 INTERMITTENT PILOT WIRING DIAGRAM ELECTRICAL CONNECTION Figure 53 The DVS36 42IP with optional fan requires 120 VAC electrical hookup to the electrical box installed The appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 if an external electrical source is uti...

Page 32: ...ly call a qualified service techni cian to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do ...

Page 33: ...tion A With power off make sure all wiring connections are clean and tight B Turn on power to appliance and ignition module C Open manual shutoff valves in the gas line to the appli ance D Do gas leak test ahead of gas control if piping has been disturbed GAS LEAK TEST Paint pipe joints with rich soap and water solution Bubbles indicate gas leak Tighten joints to stop leak STEP 2 Review Normal Ope...

Page 34: ...iming the moment the trial for ignition starts Ignition spark continues only until the timed trial for ignition period ends Then the module goes into safety lockout Lockout de energizes the first main valve operator and closes the first main valve in the gas control stopping pilot gas flow The control system must be reset by setting the thermostat below room temperature for one minute or by turnin...

Page 35: ...nition cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module WARNING When performing the following steps do not touch stripped end of jumper or SPARK terminal The ignition circuit generates 13 000 volts at 25 pf load and electrical shock can result C Energize the module and immediately touch one end of the jumper firm...

Page 36: ...ing or buckling Take protective action to shield cable and boot from excessive temperatures Check for 24 VAC across MV MV PV terminals If no voltage replace module Check electrical connections between module and gas control If okay replace gas control Note If S8600H goes into lockout reset system Check continuity of ignition cable and ground wire Note If ground is poor or erratic shutdowns may occ...

Page 37: ...inimum of 25 feet from the receiver Make sure antennae is not touching metal and is horizontal Refer to Figure 54 Receiver Shutdown of Burner In the remote auto mode the valve shuts off if it does not receive a signal within 3 hours from the transmitter In the local mode the valve does not shut off In the remote manual mode the vavle shuts off if it does not receive a signal within 6 hours from th...

Page 38: ...Page 38 13369 1 0203 RF WIRING DIAGRAM Figure 54 ...

Page 39: ...13369 1 0203 Page 39 STANDING PILOT LIGHTING INSTRUCTIONS RF STANDING PILOT LIGHTING INSTRUCTIONS ...

Page 40: ...es with a non abrasive household cleaner and warm water we recommend gas fireplace glass cleaner After that the glass should be cleaned two or three times during each heating season depending on the circumstances present General Glass Information WARNING Do not operate appliance with the glass front removed cracked or broken Replacement of the glass should be done by a licensed or qualified servic...

Page 41: ...GAS VALVE NATURAL DVS 30 49b R 5455 GAS VALVE LP DVS 30 49c R 6114 GAS VALVE NATURAL DVS 30RF 49c R 6115 GAS VALVE LP DVS 30RF 50 M 173 PILOT GASKET 57 R 3436 REMOTE OFF ON SWITCH DVS 30 58 11663 VALVE BRACKET 2 REQ D DVS 30RF 59 R 6110 LOG LEFT FRONT 60 R 6109 LOG RIGHT FRONT 61 R 6111 LOG MIDDLE 62 R 6113 LOG BRANCH 63 R 6112 LOG REAR NOT SHOWN 11281 VENTURI TARGET NAT ONLY NOT SHOWN R 3435A WIR...

Page 42: ...R SUPPORT LEFT 43 11377 BURNER SUPPORT RIGHT 44 R 5747 PILOT ASSEMBLY NATURAL DVS 36IP 44 R 5748 PILOT ASSEMBLY LP DVS 36IP 45 R 5705 PILOT ASSEMBLY NATURAL DVS 36 45 R 5706 PILOT ASSEMBLY LP DVS 36 45a R 5710 THERMOPILE DVS 36 45b R 5709 THERMOCOUPLE DVS 36 46 R 6116 PILOT ASSEMBLY NATURAL DVS 36RF 46 R 6117 PILOT ASSEMBLY LP DVS 36RF 46a R 6761 THERMOPILE 2 REQ D DVS 36RF 47a 11439 FIREBOX BOTTO...

Page 43: ...LEFT 43 11377 BURNER SUPPORT RIGHT 44 R 5747 PILOT ASSEMBLY NATURAL DVS 42IP 44 R 5748 PILOT ASSEMBLY LP DVS 42IP 45 R 5705 PILOT ASSEMBLY NATURAL DVS 42 45 R 5706 PILOT ASSEMBLY LP DVS 42 45a R 5710 THERMOPILE DVS 42 45b R 5709 THERMOCOUPLE DVS 42 46 R 6116 PILOT ASSEMBLY NATURAL DVS 42RF 46 R 6117 PILOT ASSEMBLY LP DVS 42RF 46a R 6761 THERMOPILE 2 REQ D DVS 42RF 47a 11447 FIREBOX BOTTOM WELDED A...

Page 44: ...Page 44 13369 1 0203 PARTS VIEW ...

Page 45: ...s Designed to enhance appearance DVS BL 30 looking more like real masonry DVS BL 36 DVS BL 42 DVP1A 30 1 DVP1A 36 1 DVP1A 42 1 Fresh Air Intake Kit Designed to provide heated fresh DVFB AK 30 air to the house FB AK 2 Trim Kit Frame Brass DVSBF 36BR 1 DVSBF 42BR 1 DVSBF 42BR 1 Frame High Gloss Black FBF 30BP 2 FBF 36BP 2 FBF 42BP 2 Frame Black FBF 30BL 2 FBF 36BL 2 FBF 42BL 2 Louvers Brass Louvers ...

Page 46: ...bottom of fireplace for attachment of speed control 11 Insert speed control into interior bottom of fireplace Align and place two 2 clearance holes on speed control onto two 2 weld studs 12 Use two 2 wing nuts to attach speed control to weld studs 13 Refer to Figure 1 for mounting hole location on right side of firebox top that applies to your appliance Measure from front edge of firebox top to de...

Page 47: ...ceptacle mounting screw With this wire completing the ground the appliance cord plug can be plugged into the adapter and be electrically grounded CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Part Part Quantity Description Number Supplied Fan Kit R 6158 1 Cord Set R 6159 1 Hard...

Page 48: ...uds 8 Push up and outward to remove top louver 9 Refer to Figure 1 for mounting hole location on right side of firebox top that applies to your appliance Measure from front edge of firebox top to determine mounting hole location Remove appropriate screw from firebox top 10 Refer to Figure 2 for fan control bracket location that applies to your firebox Align clearance hole on fan control bracket wi...

Page 49: ...r remove the grounding prong from this plug For an ungrounded receptacle an adapter which has two prongs and a wire for grounding can be purchased plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can be plugged into the adapter and be electrically grounded CAUTION Label all wires prior to dis...

Page 50: ...fireplace insert damper rod bracket into left interior bottom of fireplace for 36 42 models The 3 4 flange on damper rod bracket must face toward the rear of fireplace Align 2 clearance holes on damper rod bracket with 2 screw holes on left side of hearth pan Attach damper rod bracket to the underside of hearth pan with 2 10 x 1 2 provided screws See Figure 3 OUTER CASING REMOVE AIR DILUTION COVER...

Page 51: ...when ducting through a heated space Note 6 C vent or 6 flex vent can be used 10 Cut a 6 diameter hole in structure after determining duct termination rain cap location 11 Caulk exterior of structure that will be contacted by outside air tube assembly See Figure 5 12 Insert outside air tube assembly into 6 diameter hole in structure Align clearance holes on rain cap with clearance holes on outside ...

Page 52: ...rance holes on the brick panel Z bracket and into the inner casing front OPTIONAL BRICK LINER INSTALLATION INSTRUCTIONS PARTS LIST Part Description Kit Number Kit Number Kit Number Quantity DVS BL 30 2 DVS BL 36 2 DVS BL 42 2 Supplied Brick Panel Z Bracket 11573 10990 10991 2 Brick Panel Right R 6505 R 6508 R 6511 1 Brick Panel Left R 6503 R 6506 R 6509 1 Brick Panel Back R 6504 R 6507 R 6510 1 Pa...

Reviews: