Page 7
17375-6-0705
Mantel Chart (Figure 3)
Figure 3
Clearances (Figure 4)
Clearance from top front edge of fireplace to ceiling is 36"
Clearance from side of fireplace to adjacent sidewall is 6".
(914mm)
Figure 4
LOCATING FIREPLACE
Figure 5
Note: Island (C) and Room Divider
(D) installation is possible as long
as the horizontal portion of the
vent system (H) does not exceed
20 feet with a minimum vertical
run of 8 feet. See details in Venting
Section.
When you install your Direct Vent
Fireplace in (D) Room divider or
(E) Flat on wall corner positions,
a minimum of 6 inches clearance
must be maintained from the
perpendicular wall and the front
edge of the appliance.
CLEARANCES
Figure 2
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the fireplace. The flow of heat can
ignite combustibles.
CABINET
INSTALLATION
FLUSH WALL
INSTALLATION
ROOM DIVIDER
INSTALLATION
CORNER
INSTALLATION
ANGLED CORNER
INSTALLATION
ISLAND
INSTALLATION
Clearance to Combustibles
Back
0" (0 mm)
Side
0" (0 mm)
Floor
0" (0 mm)
Top Stand-off
0" (0 mm)
Top Framing Edge
3" (76 mm)
SEE MANTLE CHART FOR
MAXIMUM MANTLE DEPTH
NON-COMBUSTIBLE
FIRST 3 (SEE MAGNIFIED
VIEW)
NAILING
FLANGES
GLASS FRONT
TOP FRAMING
LEDGE
FINISHED WALL
(COMBUSTIBLE)
SEE MANTLE CHART
FOR MINIMUM HEIGHT
OF MANTLE ABOVE UNIT
2" x 4" HEADER
STAND OFF
3" (76 mm) HEIGHT
ABOVE TOP OF
FIREPLACE
3"
”