Page 1: ...e Installation Instructions with the owner Owner Keep Installation Instructions for future reference Save Installation Instructions for local electrical inspector s use DRYER 120 volt 60 Hz ELECTRIC 120 240 volt 60 Hz Part No 8528107 COMMERCIAL www whirlpool com LAUNDRY PRODUCTS ...

Page 2: ...for companion appliances Make sure you have everything necessary far proper installation Properly install dryer Contact a qualified installer to insure that the electrical and gas installations meet all national and local codes and ordinances Exhaust to outdoors Dryer must be exhausted outdoors Note The dryer must not be installed in an area where itwill be exposed to water and or weather Page 2 I...

Page 3: ...nt to avoid sagging and kinking that may result in reduced air flow Exhaust outlet is located at the center of the boftom dryer back The exhaust vent can be routed up down left right behind the dryer or straight out the back of the dryer Maximum length of exhaust system depends upon the type of vent used number of elbows and type of exhaust hood The maximum length for both rigid and flexible vent ...

Page 4: ...e roof rather than through the wall install 180 sweep elbow on the end of vent at least 2 feet 61 cm above the highest part of the building The opening wall or roof shall have a diameter 1 2 inch 1 3 cm larger than the exhaust vent diameter The exhaust vent should be centered in the opening exhaull hood or _ wall U T a main exhaull vent wall 180 _Neop 2 ft 61 cm I _ _ elbow min above highest point...

Page 5: ...nd closet installation instructions Page 12 for minimum spacing requirements Km For ease of installation operation and servicing if ever needed adequate space should be provided around the dryer Lm A 1 8 inch NPT plugged tapping accessible for gauge testing must be installed immediately upstream of the gas supply connection to the dryer The dryer must be disconnected from the gas supply piping sys...

Page 6: ...not level adjust the legs of the dryer up or down until the dryer is level m Connect gas supply to dryer Use pipe joint compound resistant to the action of L P gas for gas connections If flexible metal tubing is used be certain there are no kinks If necessary for service open the toe panel use a putty knife to press on the toe panel lock located at the center top of the toe panel Pull downward on ...

Page 7: ...Hazard Use two or more people to move and install dryer Failure to do so can result in back or other injury With dryer in laundry area exhaust_ vent sylle u _ nnectbox l mTake tape off front corners of dryer Open dryer and remove the literature and parts packages Wipe the interior of the drum thoroughly with a damp cloth mTake two of the cardboard corners from the carton and place them on the floo...

Page 8: ... WARNING Improper connection of the equipment grounding conductor can result in a risk of electric shock Check with a qualified electrician or service representative or personnel if you are in doubt as to whether the appliance is properly grounded Do not modify the plug provided with the appliance if it will not fit the outlet have a proper outlet installed by a qualified electrician Power supply ...

Page 9: ...ecure cover with hold down screw 4 Remove center terminal block screw 5 Remove appliance ground wire green with yellow stripes from external ground connector screw Fasten under center silver colored terminal block screw 6 Connect the ground wire bare of the power supply cable to the external ground conductor screw Tighten screw 7 Place the hooked end of the neutral wire white or center of power su...

Page 10: ...panel _ _ Secure cover with hold down _ _ screw Where local codes permit connecting cabinet ground conductor to neutral wire 4 Loosen or remove center terminal block screw 5 Place the hooked end of the neutral wire white or center of power supply cable under the center screw of the terminal block hook facing right Squeeze hooked end together Tighten screw 6 Place the hooked ends of the other power...

Page 11: ...g to seal exterior wall opening around exhaust hood m Carefully move dryer into final position Place level on top of the dryer first side to side then front to back If the dryer is not level adjust the legs of the dryer up or down until the dryer is level 1 U In U S or Canada plug power supply cord into grounded outlet Or in the U S only connect direct wire to power supply Turn power supply on 1 C...

Page 12: ...air Moving the d er to a new locatlon Slide dryer onto cardboard or hardboard before moving across floor to avoid damaging floor covering Gas dryer models Disconnect electrical cord Tape securely to dryer Shut off the gas supply valves in the gas supply line Disconnect gas pipe and fittings from dryer and cap gas supply line Tape end of dryer gas pipe Electric dryer models Shut of electrical suppl...

Page 13: ... coin operated models 7 718 20 cm SIDE VIEW 6 3 4 15 3 2 cm 27 68 6 cm dryer 35 88 9 cm I 2 5 cm 4 29 I 4 74 3 cm qr 26 1 2 67 3 cm _ _ 7 I I I0 I14 LEFT OR RIGHTSIDE EXH UST__Z 4 I 4 10 8 cm BACK VIEW SIDE VIEW non coin operated models 7 I 8 18 1 cm coin operated models 7 7 8 20 cm 7 I 4 18 4 cm I I I I 35 9cm BO ITOM EXHAUST Part No 8528107 2001WhirlpoolCorporation Prepared by Whirlpool Corporat...

Page 14: ...d6taire Conserver les insiTuc Iions d install_ion pour consultcrlion ult6rieure Conserver les inslTuc Iions d installcrlion pour consuitallon par rinspecteur local des installations 61eclTiques SECHEUSE COMMERCIALE Pi6ce n 8528107 ELECTRIQUE 120 volts 60 Hz 120 240 volts 60 Hz www whirlpool com APPAREILS DE BUANDERIE COMMERCIALE ...

Page 15: ...ion ef lee dimensions indiqu_ es Tenircompte des besoins d espoce pour lea aMTeSappareils V rifierque tout le materiel n_cessaire pour une irstallallon correcte est disponible Installercorrectement la sO _heuse Contacter un installateur qualifi_ qui pourra garanllr que I irstallallon des circuils de gazet d _leclficit_ salisfait les r_glernenls et codes nallonaL_ et Iocaux D_ horge _ I exl_ieur 11...

Page 16: ...UIT Le conduit m6talique flexJble doit 6Ire compl6tement ouved pour perrneitm le d_ bit d 6vacuafion ad_quat Sides coudes scnt utilis_s ou des changements de direction effectu_s pr_voir autont d espace que possible Plier le conduit graduellement pour 6viter de le d6former Enlever tout exc s de conduit flexible pour 6viter tout affaissement d_formation susceptible de r_duire le d6bit d air La bouch...

Page 17: ...e conduit principal suit une ITajectoire verticale 6 travers le tait plutSt qu _ travers le mur installer un coude de d_viation de 180 _ I extr_mit du conduit et d passent d au moins 61 cm 2 p_ la partie la plus levee du Ic_timent L ouverJure murale ou dans le tait dolt avoir un diam_tre sup_rieur de 1 3 cm 1 2 po _ celui du conduit d vacuation Le conduit d _vacuation devrait _tre centr_ dans I ou...

Page 18: ...ation et I entretien le cos ch_ant il est recommand de pr_voir un espace ad_cluat autour de la s_ _cheuse L mUn racoord de 0 317 cm 1 8 po NPT accessible pour le raccordement d un manom_lTe de test dolt _tre install_ imm_diatement en amont du point de raccordement de la conalisation d arriv_e de gaz de la s_ _cheuse Lors de tout test de pressurisation du syst_me _une pression de test sup_rieure _ ...

Page 19: ...iliser un campos_ d tanch_it_ compatible avec le gaz propane Si un conduit m tallique est utilis_ v rifier qu il West pas d form Sic est n_cesseire enlever le panneau de plinthe utiliser un cauteau 6 mastic pour appuyer sur le verrou situ au cenlTe au semmet du panneau de plinthe Tirer vers le bas pour provoquer I ouverture du panneau de plinthe Le ponneau de plinthe est mont_ sur des charni_res e...

Page 20: ...ion peut causer une bleseure au dos ou d aube blessure Risque de choc 61ectrique D_ onnecter le courant 61ectrique avant d entreprendre des bavaux R_installer tous les panneaux avant de faire fonctionner rappareil Avec la s6cheuso dens la buandede Le non respect de ces instructions peut causer un d_s ou un choc _lectrique coupe circuit conduit dL ave_ fusible m Oter la plaque de I ouverture d acc ...

Page 21: ...rm_ment aux prescriptions de teus les codes et r_glements Iocaux AVERTI _EMENT Une connexion d_tec_ueuse du conducteur de liaison _ la terre de I _quipement peut presenter un risque de choc _lectrique En cos de doute quant _la qualit_ de la liaison _ la terre de I appareiL consulter un _lectricien ou technicien qualifi_ Ne pas modifier la fiche du cordon d alimentetion Si la fiche du cordon ne cor...

Page 22: ...s du conducffeur nu de liaison 0 la terre Pourles3 aulTes conducteurs COUlOer une secfiion de 3 8cm 1 1 2 pc 0 I exJT_mit_ D_nuder ensuite chaque conducteur sur2 5 cm 113o nu la Fonme un crochet 6 I exlT_nn_ de choque conducteur 4 Oter la vis de la borne centrale du bloc 5 S_parer le conducteur de liaison _ la terre de I appareil vert avec rayure jaune de la vis de connexion au chOssis Connecter c...

Page 23: ...uoteurs plus conduoteur de liaison _ la tene seclionner le conducfeur de liaison 6 la tene _ la limife de la gaine Former un crochet I exJr_if6 de chaque conducteur Lorsquele code local permet le raccordement entre conducteur neutre et conducteur de liaison _ la terre de la caisse 4 Desserrer ou enlever la vis de la borne centrale du bloc de connexion 5 Placer I exlT6mit_ form_e en crochet du cond...

Page 24: ...la s_cheuse 6 son emplacement final Placer un niveau sur le sommet de la s_cheuse ITansversalement puis dans le sens avant arri_re Si la s_cheuse West pas d aplomb ajuster les pieds pour modifier la hauteur et 6tablir un bon aplomb de la s_ _cheuse 0 Aux Etals Unis et au Canada brancher le cordon d alimentetion 61ectrique sur une prise de courant reli6e 6 la terre ou connecter le c6ble de racoorde...

Page 25: ..._cheuse et me11Teun bouchon sur la canalisation de gaz Poser du ruban adh_sif pour oblurer la canalisetion de gaz de la s_cheuse S6cheuses 61eclfiques Interrompre I alimentation _lectrique de la s_oheuse D_brancher le cordon d alimentation _lectrique de la prise ou d_brancher le c6ble du bloc de connexion de la s_cheuse Tom las rnod61_s V_rifier que tousles pieds de r_glage de I aplomb sent bien v...

Page 26: ...GABLE ELECTRIQUE 14 po BOUCHEDE DECHARGE 13_ Com_ I0 2cm 4 po dia i CANALISATION DEGAZ VUE ARRII RE Sdche se 68 6 cm 27 po 88 9 cm 35 po 12 1 cm T 4 3 4 po m m_J_m 2 5 cm I po _ 74 3 cm 29 I 4 po _ 67 3 cm _ 26 I 2 po _ 26 I 2 67 3 cm i 26 cm 10 I 4 po BOUCHEDE _ DE CUARGE i COTE GAUC HF _ _ OU COTE _ DROIT _ ModUle sansm6canisme de commande a pi_ces 18 1 cm 7 I18 po ModUles avec m6canisme de comm...