background image

13

Complete Installation

NOTE: Refer to outdoor unit installation instructions for system 
start-up instructions and refrigerant charging instructions.

Pre-Start Check

Is unit properly located, level, secure, and serviceable?

Has an auxiliary pan been provided under the unit with 
separate drain for units installed above a finished ceiling or in 
any installation where condensate overflow could cause 
damage?

Have all webs been removed from the drain connections that 
are being used? Have all drain pan plugs not used been 
properly plugged?

Has the condensate line been properly sized, run, trapped, 
pitched, and tested?

Is the ductwork correctly sized, run, taped, and insulated?

Have all cabinet openings and wiring been sealed?

Is the indoor coil orifice size correct?

Have all unused orifice replacement parts and packaging 
been disposed of?

Is the filter clean, in place, and of adequate size?

Is the wiring neat, correct, and in accordance with the wiring 
diagram?

Is the unit properly grounded and protected (fused)?

Is the thermostat correctly wired and in a good location?

Are all access panels in place and secure?

Check Blower Operation

1. Set thermostat to FAN ON.

2. The indoor blower should come on.

Check Electric Heater (if used)

1. Set thermostat to call for auxiliary heat (approximately 5°F 

above ambient temperature). The indoor blower and auxiliary 
heat should come on together. Allow a minimum of 3 minutes 
for all sequencers to cycle on.

2. Set the thermostat so it does not call for heat. Allow up to 

5 minutes for all sequencers to cycle off.

Check Airflow

Cooling blower speed

For proper cooling operation, the airflow through the indoor 
coil should be between 350 and 450 CFM per ton of cooling 
capacity (or 350 - 450 CFM per 12,000 Btu/h) based on the 
rating of the outdoor unit.

The cooling blower speed is factory configured to provide 
correct airflow for an outdoor unit that matches the maximum 
cooling capacity rating of the air handler. 

If the outdoor unit is smaller than the maximum cooling 
capacity rating for the air handler, the cooling blower speed 
may need to be changed. Refer to Blower Performance 
Chart.

IMPORTANT: The cooling blower speed must be set to provide a 
minimum of 350 CFM airflow per ton (12,000 Btu/h) of outdoor 
cooling capacity.

To change blower speed: Refer to “Wiring Diagram—
Electric Heat and Blower.”

1. Disconnect all power supplies.

2. Remove the air handler access panel.

3. Locate pin number 2 on the blower relay. Two black wires are 

connected to this terminal pin. One connects to pin number 5 
on the blower relay, one connects to an inline splice 
connecting to a red or black wire.

4. Remove the wire going to the 4-pin blower motor connector 

from the splice.

5. Connect the blower lead (Red [LO], Black [HI]) onto the splice 

from the 4-pin blower motor connector.

NOTE: Unused blower speeds are shipped from the factory 
covered with a plastic cap. Remove this cap from the new 
blower speed terminal and replace it over the factory-set 
blower terminal.

6. Replace all panels.

7. Reconnect power.

Blower Performance Chart

Air 
Handler 
Model

Blower 
Speed

CFM @ ESP. - in. W.C.

0.1

0.2

0.3

0.4

0.5

18

High (Black)

952

886

795

679

529

Low (Red)

727

640

598

520

393

24

High (Black)

1,054

979

912

818

686

Low (Red)

1,033

925

854

754

621

30

High (Black)

1,298

1,252

1,202

1,130

1,031

Low (Red)

1,041

1,026

992

936

837

36

High (Black)

1,531

1,466

1,391

1,287

1,181

Low (Red)

1,294

1,262

1,216

1,139

1,049

42

High (Black)

1,670

1,600

1,511

1,393

1,218

Low (Red)

1,535

1,475

1,406

1,264

1,141

48

High (Black)

1,829

1,718

1,620

1,484

1,271

Low (Red)

1,754

1,654

1,553

1,423

1,214

60

High (Black)

2,119

1,964

1,845

1,692

1,494

Low (Red)

2,049

1,934

1,813

1,684

1,468

All factory settings are low-speed.

All data given while air handler is operating with a dry DX coil 
and no air filter installed.

WARNING

Electrical Shock Hazard

Disconnect all power supplies before servicing.

Replace all parts and panels before operating.

Failure to do so can result in death or electrical shock.

Summary of Contents for WAHM

Page 1: ...mplete Installation 12 SEQUENCE OF OPERATION 14 AIR HANDLER MAINTENANCE 14 ASSISTANCE OR SERVICE 14 Accessories 14 WARRANTY 15 Whirlpool Models WAHU WAHM 065937400 You can be killed or seriously injured if you don t immediately You can be killed or seriously injured if you don t follow All safety messages will tell you what the potential hazard is tell you how to reduce the chance of injury and te...

Page 2: ...nd follow the instructions provided with any tools listed here Tools Needed Parts Needed Check local codes check existing electrical supply and read Ductwork Requirements and Electrical Requirements before purchasing parts OutdoorSystemRequirements The air handler is designed to match and must be used with outdoor units as rated The indoor sections are manufactured with an interchangeable refriger...

Page 3: ...pply Adequate support must be provided to ensure cabinet integrity Ensure that there is adequate room to remove service and access panels if installing in the horizontal position For correct horizontal coil installation see Installation Configuration Options later in this section IMPORTANT This coil is provided with a secondary drain that should be trapped and piped to a location that will give th...

Page 4: ... drain pan and the side drain pan 5 Remove the side drain pan from the coil drain pan assembly and install on the opposite side 6 Reinstall the coil drain pan assembly in the same orientation as before by lifting and sliding into the air handler 7 Install the coil support bracket on the opposite side of the air handler A Drain connections B Coil access cover C Blower access cover A Drain connectio...

Page 5: ...E Use copper conductors only All field wiring must be done in accordance with National Electrical Code applicable requirements of UL and local codes where applicable Electrical wiring disconnect means and over current protection are to be supplied by the installer Refer to the air handler rating plate for maximum over current protection minimum circuit ampacity as well as operating voltage The pow...

Page 6: ...ension of the blower housing and minimizes air expansion losses from the blower INSTALLATION INSTRUCTIONS InspectShipment These air handlers are completely factory assembled and all components are performance tested Each unit consists of a blower assembly refrigerant coil and controls in an insulated galvanized steel factory finished enclosure Knockouts are provided for electrical wiring entrance ...

Page 7: ...ow complete drainage of the pan NOTE Horizontal runs must also have an anti siphon air vent standpipe installed ahead of the horizontal run See Typical Condensate Drain Connection in this section An extremely long horizontal run may require an oversized drain line to eliminate air trapping Typical Condensate Drain Connection secondary drain not shown NOTE Do not operate air handler without a drain...

Page 8: ...ions are ready to be completed 1 Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit Run the lines in as direct a path as possible avoiding unnecessary turns and bends 2 Make sure that the suction line is insulated over the entire exposed length and that both suction and liquid lines are not in direct contact with floors walls ductwork floor ...

Page 9: ... with electrical power 1 2 or 3 circuits See the air handler Accessory Kit label for number of circuits and ratings 2 Disconnect all power supplies 3 Knock out the correct number of knockouts 1 2 or 3 and install UL listed wires and fittings A Connect yellow to yellow B Connect black to black C Connect ground wire to ground terminal marked GND WARNING Electrical Shock Hazard Electrically ground ai...

Page 10: ...nnects are used the front panel knockouts will need to be removed 8 Reinstall the air handler blower access panel 9 Reconnect power 10 Dispose of recycle all remaining parts WARNING Electrical Shock Hazard Electrically ground electric heater Connect ground wire to ground terminal marked GND Use copper wire rated for supply connection Correct wire gauge is shown in the chart below Failure to follow...

Page 11: ...Only Application Thermostat Air Handler Air Handler Air Handler Thermostat Thermostat R R R G G G BU BU W W W Heat Pump Unit BK BK Cooling Application with Electric Heat Heat Pump Application with Electric Heat Condensing Unit Connect common wire only if required See thermostat installation instructions ...

Page 12: ...ng Diagram Electric Heat Control Circuit Wiring To Be 24 Volt N E C Class 2 Power Factory Wired Power Field Wired Control Factory Wired Control Field Wired Plug Pin Location Opt Amp 350781 1 6 Pin Cap 4 1 5 6 2 3 TB Terminal Block Opt Heaters Used 5 KW HE1 7 5 10 KW HE1 HE2 15 KW HE1 HE2 HE3 20 KW HE1 HE2 HE3 HE4 24 C 3 2 6 5 1 4 W IF 120V GND BR BR W 3 4 R BK MTR Cap 1 Y 14 BK HI 14 Y COM 2 14 R ...

Page 13: ... matches the maximum cooling capacity rating of the air handler If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler the cooling blower speed may need to be changed Refer to Blower Performance Chart IMPORTANT The cooling blower speed must be set to provide a minimum of 350 CFM airflow per ton 12 000 Btu h of outdoor cooling capacity To change blower speed Ref...

Page 14: ...position the heat pump will be locked out of the heating circuit and all heating will be electric heat if applicable A jumper should be placed between W 2 and E on the thermostat subbase so that the electric heat control will transfer to the first stage heat on the thermostat This will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the AUTO position AI...

Page 15: ...15 ...

Page 16: ...late Dealer name____________________________________________________ Address ________________________________________________________ Phone number__________________________________________________ Model number __________________________________________________ Serial number __________________________________________________ Installation date ________________________________________________ 0659374...

Reviews: