background image

8

Heating Cycle

Upon heating demand, the thermostat closes circuit R to Y, which 
closes the heat pump contactor, starting the compressor and 
outdoor fan. The reversing valve is not energized in the heating 
mode. The thermostat again automatically brings on the indoor 
fan at the same time. Upon satisfying heating demand, the 
thermostat opens the above circuits and stops heat pump 
operation.

Defrost Cycle

If the outdoor ambient conditions are such that frost forms on the 
outdoor coil, the defrost control monitors a defrost cycle. It then 
runs the defrost cycle as ambient temperatures require. 

The defrost control is time/temperature initiated and temperature 
terminated with a maximum defrost time (time-out) of 10 minutes. 
The time between defrost cycles is preset at 60-minute intervals 
at the factory, but can be field adjusted between 30, 60, or 
90 minutes. To adjust the time period between defrost cycles, 
see “Adjust Time Between Defrost Cycles” in the “Circulating Air 
Blower” section.

The defrost control will initiate a defrost cycle when the selected 
time period has elapsed and the defrost sensor sees a 
temperature below freezing. At the start of a defrost cycle, the 
defrost control will energize the reversing valve solenoid, shifting 
the reversing valve and de-energizing the outdoor fan. The 
defrost relay will also close, energizing temporary heat for 
increased comfort during defrost (if the indoor unit is so 
equipped). The heat pump will remain in defrost until the defrost 
sensor has determined that the frost has been removed from the 
coil or a 10-minute period has elapsed, whichever comes first.

Defrost Thermostat

The defrost thermostat is located on the liquid line between the 
check/expansion valve and the distributor. When defrost 
thermostat senses 42ºF or cooler, the thermostat contacts close 
and send a signal to the defrost control board to start the defrost 
timing. It also terminates defrost when the liquid line warms up to 
70ºF.

Defrost Control

The defrost control board includes the combined functions of the 
time/temperature defrost control, defrost relay, diagnostic LEDs 
and terminal strip for field wiring connections. See “Defrost 
Control Board” in the “Adjust Defrost System” section.

The control provides automatic switching from normal heating 
operation to defrost mode and back. During compressor cycle 
(call for defrost), the control accumulates compressor run times 
at 30, 60 or 90 minute field-adjustable intervals. If the defrost 
thermostat is closed when the selected compressor run time 
interval ends, the defrost relay is energized and defrost begins.

Defrost Control Timing Pins

Each timing pin selection provides a different accumulated 
compressor run time period during one thermostat run cycle. This 
time period must occur before a defrost cycle is initiated. The 
defrost interval can be adjusted to 30 (T1), 60 (T2) or 90 (T3) 
minutes. See “Defrost Control Board” in the “Adjust Defrost 
System” section. The defrost timing jumper is factory-installed to 
provide a 60-minute defrost interval. If the timing selector jumper 
is not in place, the control defaults to a 90-minute defrost 
interval. The maximum defrost period is 14 minutes and cannot 
be adjusted.

A test option is provided for troubleshooting. The test mode may 
be started any time the unit is in the heating mode and the 
defrost thermostat is closed or jumpered. If the jumper is in the 
test position at power-up, the control will ignore the test pins. 
When the jumper is placed across the Test pins for 2 seconds, 
the control will enter the defrost mode. If the jumper is removed 
before an additional 5-second period has elapsed (7 seconds 
total), the unit will remain in defrost mode until the defrost 
thermostat opens or 14 minutes have passed. If the jumper is not 
removed until after the additional 5-second period has elapsed, 
the defrost will terminate and the test option will not function 
again until the jumper is removed and re-applied.

Compressor Delay

The defrost board has a field-selectable function to reduce 
occasional sounds that may occur while the package unit is 
cycling in and out of the defrost mode. The compressor will be 
cycled off for 30 seconds while going in and out of the defrost 
mode when the compressor delay jumper is removed. 

NOTE: The 30-second “off” cycle is not functional when 
jumpering the TEST pins.

Time Delay

The time delay is 5 minutes long. The delay helps to protect the 
compressor from short cycling in case the power to the package 
unit is interrupted or a pressure switch opens. The delay is 
bypassed by placing the timer select jumper across the TEST 
pins for 0.5 seconds.

Pressure Switch Circuit

The defrost control includes LO-PS terminals to connect an 
optional low pressure (loss of charge pressure) switch. A high 
pressure switch (optional) can be connected to the HI PS 
terminals. See “Defrost Control Board” in the “Adjust Defrost 
System” section.

During a single demand cycle, the defrost control will lock out 
the package unit after the fifth time that the circuit is interrupted 
by any pressure switch wired to the control board. In addition, 
the diagnostic LEDs will indicate a locked-out pressure switch 
after the fifth occurrence of an open pressure switch. See 
Defrost Control Board Diagnostic LEDs chart later in this section. 
The package unit will remain locked out until power to the board 
is interrupted, then re-established, or until the jumper is applied 
to the TEST pins for 0.5 seconds.

NOTE: The defrost control board ignores input from the low 
pressure switch terminals during:

TEST mode

Defrost cycle

90-second start-up period

First 90 seconds after the reversing valve switches heat/cool 
modes

Summary of Contents for W2PC3

Page 1: ...eed Motor 10 SYSTEM MAINTENANCE 11 TROUBLESHOOTING 12 ASSISTANCE OR SERVICE 16 Accessories 16 48373F007 Whirlpool Home Cooling and Heating 14610 Breakers Drive Jacksonville FL 32258 Whirlpool Models W2PH3 W2PC3 W4PH4 W4PC4 You can be killed or seriously injured if you don t immediately You can be killed or seriously injured if you don t follow All safety messages will tell you what the potential h...

Page 2: ...it must be installed on a solid level mounting pad that will not settle or shift Isolate the pad from the building structure to avoid possible transmission of sound or vibration from the heat pump or condensing unit into the conditioned space The heat pump or condensing unit foundation should be raised to a minimum of 3 above finish grade In areas which have prolonged periods of temperature below ...

Page 3: ...ge claims should be filed with the carrier immediately Claims of shortages should be filed with the seller within 5 days NOTE If any damages are discovered and reported to the carrier do not install the heat pump or condensing unit as your claim may be denied PlaceHeatPumporCondensingUnitin Final Location IMPORTANT Place the heat pump or condensing unit in the final location and position it in the...

Page 4: ...d at the bottom on the side of the heat pump or condensing unit A drain line with trap must be installed on all applications to avoid accumulation of condensate under or around the heat pump or condensing unit Install Condensate Trap 1 Construct the condensate trap from PVC tubing as shown in Condensate Trap Construction NOTES The condensate trap allows a standing column of water of at least 2 50 ...

Page 5: ...ed Surface Area for Disposable Filters chart and are based on a face velocity of 325 ft 99 1 m per min for disposable filters and 525 ft 160 m per min for cleanable filters InstallAccessoryHeater 1 Disconnect power 2 Remove the heater compartment access panel 3 Remove the heater blockoff by removing the 4 screws holding it in place 4 Insert the heater kit into the control panel and fasten in the s...

Page 6: ... prevent moisture from entering the heat pump or condensing unit Low voltage wiring must be separated from line voltage wiring Line Voltage Connections 1 Disconnect power 2 Remove the blower access panel 3 Remove the heater compartment access panel 4 Route the field supply wires through the line voltage conduit opening to the electrical connection area providing sufficient length to connect to the...

Page 7: ...t pump or condensing unit in its final location SEQUENCE OF OPERATION CoolingCycle CoolingOnly Upon cooling demand the thermostat closes circuit R to Y Closing R to Y energizes the package unit for cooling operation and closes the contactor starting the compressor and outdoor fan The thermostat automatically closes R to G circuit which also brings on the indoor fan at the same time Upon satisfying...

Page 8: ...at run cycle This time period must occur before a defrost cycle is initiated The defrost interval can be adjusted to 30 T1 60 T2 or 90 T3 minutes See Defrost Control Board in the Adjust Defrost System section The defrost timing jumper is factory installed to provide a 60 minute defrost interval If the timing selector jumper is not in place the control defaults to a 90 minute defrost interval The m...

Page 9: ... Plug to the pins corresponding to 90 4 Replace the heater compartment access panel 5 Reconnect power TroubleshoottheDefrostSystem Diagnostic LEDs The defrost board uses 2 LEDs for diagnostics The LEDs flash a specific sequence according to the condition Defrost Control Board Diagnostic LEDs Mode Green LED DS2 Red LED DS1 No Power to Board Off Off Normal Operation Power to Board Simultaneous Slow ...

Page 10: ...y a timing circuit in the blower control Timings are not adjustable There is no blower on delay after a call for heating or cooling Blower off delay is 90 seconds after the thermostat is satisfied NOTE No blower speed adjustments are required CirculatingAirBlower VariableSpeedMotor Packaged units equipped with a variable speed circulation air blower motor will deliver a constant airflow within a w...

Page 11: ... reduction in the normal airflow rate The variable speed motor interface board provides a connection for a humidistat on the HUM terminal When a humidistat is connected the dehumidifier resistor on the interface must be cut The humidistat should be wired to open during high humidity which will reduce blower airflow ADJUST HEAT and COOL Taps and Dehumidify Resistor SYSTEM MAINTENANCE Leaves and oth...

Page 12: ...UT CMC1 S6 L1 24 V Fuse Y A15 W2 R Y BU W G OR R BU BU Y BU BK BK Defrost Control BU W P 1 P 2 P 4 P 6 P 5 Reversing Valve Defrost Thermostat Defrost Control High Pressure Switch if used Contactor Blower Control Indoor Blower Motor Capacitor Condenser Fan Motor Blower Control Compressor Contactor Compressor Compressor Contactor Thermostat Blower Speed Chart for Heat Pump and Cooling Only Models Un...

Page 13: ... 60 Dual Capacitor Y W R R C12 L2 T2 T1 L1 Compressor B1 C R S F C H PCO if used NC C B3 BU 24V 240V 208V R Reversing Valve High Pressure Switch S4 NOTE Connection must be jumpered when pressure switch is not used Defrost Control CMC1 Defrost Thermostat S6 P 4 Contactor Low Pressure Switch S79 L1 BU BK BK BK BK Y Y Y Y Y K1 Fan O OUT LO PS DF COMMON Y1 OUT HI PS 24V W1 C L R O Y1 W BU R OR Y W R P...

Page 14: ...K R P 3 A15 Blower Control C NC NO C L M H B3 C4 Indoor Blower Motor Capacitor Condenser Fan Motor B4 BK BK R Y Compressor Compressor Contactor R BR PR K1 2 P 2 L2 L2 T2 K1 1 Compressor Contactor BK Dual Capacitor C12 R S C C F H T1 P 1 B1 208 230V 1 60 L1 L1 T1 Blower Speed Chart for Heat Pump and Cooling Only Models Unit Factory shipped Settings Cooling Input BLK 24 L Low 30 M Medium 36 H High 4...

Page 15: ...OOL NORM TEST A B C D A B C D ICM Board A54 HUM R C1 EM W1 O Y2 Y1 G B3 Indoor Blower Motor R BU W OR Y G Transformer BU 24V 240V 208V R T1 Y B4 PR BR BK BK BK BK K1 1 Compressor Contactor Indoor Blower Motor P 1 BK BK L1 208 230V 1 60 Dual Capacitor W R R C12 T2 T1 L1 Compressor B1 C R S F C H PCO if used B3 BK K1 1 Compressor Contactor L2 P 2 Y L2 Y Factory Shipped Settings Unit ADJUSTHEAT COOL ...

Page 16: ...1 W G G W2 W2 O O Without Economizer Thermostat Outdoor Unit C C R R Y1 Y W W1 W1 G G Y2 W2 W2 O O Thermostat Outdoor Unit With Economizer Economizer Blue White Yellow Orange Green Black Part Number Accessory Model s 48193 001 ALIFT801 1 Lifting Bracket Kit All Electric Heater Kits Cat No Model No Description Used On 10W47 PHK05BP 1 5 kw Electric Heater Kit All 10W48 PHK07BP 1 7 5 kw Electric Heat...

Reviews: