background image

8

SEQUENCE OF OPERATION 

Cooling

Upon cooling demand, the thermostat closes circuit R to O and Y. 
Closing R to O and Y energizes the reversing valve for cooling 
operation and closes the heat pump contactor, starting the 
compressor and outdoor fan. The thermostat automatically 
closes R to G circuit, which also brings on the indoor fan at the 
same time. Upon satisfying cooling demand, the thermostat will 
open the above circuits and open the main contactor, stopping 
the compressor and outdoor fan. If the indoor unit is equipped 
with a delay timer, the blower will continue to operate for 60 to 
90 seconds, which improves system efficiency.

Heating

Upon heating demand, the thermostat closes circuit R to Y, which 
closes the heat pump contactor, starting the compressor and 
outdoor fan. The reversing valve is not energized in the heating 
mode. The thermostat again automatically brings on the indoor 
fan at the same time. Upon satisfying heating demand, the 
thermostat opens above circuits and stops heat pump operation.

Defrost Cycle

If the outdoor ambient conditions are such that frost forms on the 
outdoor coil, the defrost control monitors the need for and 
initiates and terminates defrost cycles as necessary to maintain 
system performance. 

The defrost control is time/temperature initiated and temperature 
terminated with a maximum defrost time (time-out) of 10 minutes. 
The time between defrost cycles is preset at 60-minute intervals 
at the factory, but can be field adjusted between 30, 60, or 
90 minutes. To adjust the time period between defrost cycles, 
see “Adjust Time Between Defrost Cycles” in “Adjusting Defrost 
System.”

The defrost control will initiate a defrost cycle when the selected 
time period has elapsed and the defrost sensor sees a 
temperature below freezing. At the start of a defrost cycle, the 
defrost control will energize the reversing valve solenoid, shifting 
the reversing valve and de-energizing the outdoor fan. The 
defrost relay will also close, energizing temporary heat for 
increased comfort during defrost (if the indoor unit is so 
equipped). The heat pump will remain in defrost until the defrost 
sensor has determined that the frost has been removed from the 
coil or a 10-minute period has elapsed, whichever comes first.

Defrost Thermostat

The defrost thermostat is located on the liquid line between the 
check/expansion valve and the distributor. When defrost 
thermostat senses 42ºF (5.6ºC) or cooler, the thermostat contacts 
close and send a signal to the defrost control board to start the 
defrost timing. It also terminates defrost when the liquid line 
warms up to 70ºF (21.1ºC).

Defrost Control

The defrost control board includes the combined functions of the 
time/temperature defrost control, defrost relay, diagnostic LEDs 
and terminal strip for field wiring connections. See “Defrost 
Control Board” in “Adjusting Defrost System.”

The control provides automatic switching from normal heating 
operation to defrost mode and back. During compressor cycle 
(call for defrost), the control accumulates compressor run times 
at 30-, 60- or 90-minute field-adjustable intervals. If the defrost 
thermostat is closed when the selected compressor run time 
interval ends, the defrost relay is energized and defrost begins.

Defrost Control Timing Pins

Each timing pin selection provides a different accumulated 
compressor run time period during one thermostat run cycle. This 
time period must occur before a defrost cycle is initiated. The 
defrost interval can be adjusted to 30 (T1), 60 (T2) or 90 (T3) 
minutes. See “Defrost Control Board” in “Adjusting Defrost 
System.” The defrost timing jumper is factory-installed to provide 
a 60-minute defrost interval. If the timing selector jumper is not in 
place, the control defaults to a 90-minute defrost interval. The 
maximum defrost period is 14 minutes and cannot be adjusted.

A test option is provided for troubleshooting. The test mode may 
be started any time the heat pump is in the heating mode and the 
defrost thermostat is closed or jumpered. If the jumper is in the 
test position at power-up, the control will ignore the test pins. 
When the jumper is placed across the test pins for 2 seconds, the 
control will enter the defrost mode. If the jumper is removed 
before an additional 5-second period has elapsed (7 seconds 
total), the heat pump will remain in defrost mode until the defrost 
thermostat opens or 14 minutes have passed. If the jumper is not 
removed until after the additional 5-second period has elapsed, 
the defrost will terminate and the test option will not function 
again until the jumper is removed and reapplied.

Summary of Contents for W2H3

Page 1: ...s 6 Complete Installation 7 SEQUENCE OF OPERATION 8 Cooling 8 Heating 8 Defrost Cycle 8 Adjusting Defrost System 9 Troubleshoot the Defrost System 10 SYSTEM MAINTENANCE 10 ASSISTANCE OR SERVICE 10 Accessories 10 WARRANTY 11 Whirlpool Models W2H3 and W2H4 506112 01 You can be killed or seriously injured if you don t immediately You can be killed or seriously injured if you don t follow All safety m...

Page 2: ...e to the inlet and discharge air openings The location must also allow for adequate service access See Minimum Clearances Where possible select a location for the heat pump which is shaded from the direct rays of the sun most of the time North or east locations are usually most desirable Position the heat pump to avoid direct contact with water snow or ice from a roofline overhead The heat pump mu...

Page 3: ...e as ordered 2 Upon receipt of heat pump inspect it for possible shipping damage Examine the heat pump inside the carton if the carton is damaged If damage is found it should be noted on the carrier s freight bill Damage claims should be filed with the carrier immediately Claims of shortages should be filed with the seller within 5 days NOTE If any damages are discovered and reported to the carrie...

Page 4: ...r or copper and phosphorus with a melting point above 1 100 F 593ºC NOTE Do not use soft solder 6 Make sure indoor coil has been put in place according to the Installation Instructions and is connected to the refrigerant lines 7 Replace valve cores 8 Pressurize the lines and indoor coil with a pressure not to exceed 20 psi 9 Leak test the lines with a pressure not to exceed 20 psig 10 Evacuate the...

Page 5: ...f this factory charge Adjustment of the refrigerant charge will be necessary based on the system combination and line length To adjust the refrigerant size for increased line lengths add the following amount of refrigerant For line set lengths greater than 15 ft 4 6 m add refrigerant by weighing in 0 60 oz per ft of 1 cm O D liquid line If necessary adjust the refrigerant charge for compatibility ...

Page 6: ...lace control box cover 7 Reconnect power WARNING Rating Plate Ampacity Less than 15 16 20 21 30 AWG 14 12 10 8 31 50 Electrical Shock Hazard Electrically ground condensing unit or heat pump Connect ground wire to ground lug Use copper wire for supply connection Correct wire gauge is shown in the chart below Failure to follow these instructions can result in death or electrical shock WARNING Electr...

Page 7: ...ld Line voltage Factory Low voltage Factory Ground Thermostat S87 Low Pressure Switch if used BK BK BK BK PR R Y Fan OR R Reversing Valve Defrost Thermostat Ground Lug Equipment Ground PR BK BK OR R Y Compressor Crankcase Heater if used Compressor Contactor Outdoor Fan BK Low Pressure Switch if used FAN Fan High Pressure Switch if used High Pressure Switch if used Defrost Control Reversing Valve D...

Page 8: ...coil or a 10 minute period has elapsed whichever comes first Defrost Thermostat The defrost thermostat is located on the liquid line between the check expansion valve and the distributor When defrost thermostat senses 42ºF 5 6ºC or cooler the thermostat contacts close and send a signal to the defrost control board to start the defrost timing It also terminates defrost when the liquid line warms up...

Page 9: ...wer 2 Remove the control box cover 3 Adjust the time period between defrost cycles by placing the defrost time plug in the proper position See Defrost Control Board For 30 minute intervals between defrost cycles move the Defrost Time Setting Plug to the pins corresponding to 30 For 60 minute intervals between defrost cycles move the Defrost Time Setting Plug to the pins corresponding to 60 this se...

Page 10: ...restricting airflow call a qualified service person to clean the coil surface An annual inspection by a qualified person should be performed to ensure continued high quality performance ASSISTANCE OR SERVICE If you need further assistance you can write to the below address with any questions or concerns Whirlpool Home Cooling and Heating 14610 Breakers Drive Jacksonville FL 32258 Please include a ...

Page 11: ...ED COVERAGE Your Whirlpool Home Cooling and Heating limited warranty provides extended coverage on the components outlined below The extended coverage begins with the date of the original unit installation and represents the total warranty period for the specific component Heat Exchangers WFAT WFAR WGFA WGFB W2PG3 Twenty 20 Years Residential Applications WFAT WFAR WGFA WGFB W2PG3 Ten 10 Years Non ...

Page 12: ...d by Whirlpool Home Cooling and Heating e Operation of furnaces with return air temperatures of less than 60 F 16 C or operation of a furnace field installed downstream from a cooling coil f Use of contaminated or alternate refrigerant 3 The installation of replacement parts under the terms of this warranty does not extend the original warranty period Whirlpool Home Cooling and Heating makes no ex...

Reviews: