Whirlpool W10459122A Installation Instructions Manual Download Page 5

5

Electrical Requirements

If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrical installer determine that 
the ground path is adequate and wire gauge is in accordance 
with local codes.

Do not use an extension cord.

Be sure that the electrical connection and wire size are adequate 
and in conformance with the National Electrical Code, ANSI/
NFPA 70-latest edition and all local codes and ordinances.

A copy of the above code standards can be obtained from:

National Fire Protection Association

1 Batterymarch Park

Quincy, MA 02169-7471

WARNING: Improper connection of the equipment-grounding 
conductor can result in a risk of electric shock. Check with a 
qualified electrician or service technician if you are in doubt as to 
whether the appliance is properly grounded. Do not modify the 
power supply cord plug. If it will not fit the outlet, have a proper 
outlet installed by a qualified electrician.

Electrical Connection

To properly install your range, you must determine the type of 
electrical connection you will be using and follow the instructions 
provided for it here.

Range must be connected to the proper electrical voltage 
and frequency as specified on the model/serial number rating 
plate. The model/serial number rating plate is located under 
the front left burner bowl. Refer to the figure in the “Location 
Requirements” section.

This range is manufactured with the neutral terminal 
connected to the cabinet. Use a 3-wire UL listed, 40- or 50-
amp power supply cord (pigtail) (see Range Rating chart 
below). If local codes do not permit ground through the 
neutral, use a 4-wire power supply cord rated at 250 volts, 
40 or 50 amps and investigated for use with ranges.

*The NEC calculated load is less than the total connected load 

listed on the model/serial rating plate.

**If connecting to a 50-amp circuit, use a 50-amp rated cord with 

kit. For 50-amp rated cord kits, use kits that specify use with a 
nominal 1

³⁄₈

" (34.93 mm) diameter connection opening.

A circuit breaker is recommended.

The range can be connected directly to the circuit breaker 
box (or fused disconnect) through flexible or nonmetallic 
sheathed, copper or aluminum cable. See the “Electrical 
Connection” section.

Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that 
the range can be moved if servicing is ever necessary.

A UL listed conduit connector must be provided at each end 
of the power supply cable (at the range and at the junction 
box).

Wire sizes and connections must conform with the rating of 
the range (40 amps).

The wiring diagram is located on the underside of the storage 
drawer in a clear plastic bag.

If connecting to a 4-wire system:

This range is manufactured with the ground connected to the 
neutral by a link. The ground must be revised so the green 
ground wire of the 4-wire power supply cord is connected to the 
cabinet. See the “Electrical Connection” section.

Grounding through the neutral conductor is prohibited for new 
branch-circuit installations (1996 NEC); mobile homes; and 
recreational vehicles, or an area where local codes prohibit 
grounding through the neutral conductor.

When a 4-wire receptacle of NEMA Type 14-50R is used, a 
matching UL listed, 4-wire, 250-volt, 40-amp, range power 
supply cord (pigtail) must be used. This cord contains 4 copper 
conductors with ring terminals or open-end spade terminals with 
upturned ends, terminating in a NEMA Type 14-50P plug on the 
supply end. 

The fourth (grounding) conductor must be identified by a green or 
green/yellow cover and the neutral conductor by a white cover. 
Cord should be Type SRD or SRDT with a UL listed strain relief 
and be at least 4 ft (1.22 m) long. 

The minimum conductor sized for the copper 4-wire power 
cord are:

40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding

If connecting to a 3-wire system:

Local codes may permit the use of a UL listed, 3-wire, 
250 volt, 40-amp range power supply cord (pigtail). This cord 
contains 3 copper conductors with ring terminals or open-end 
spade terminals with upturned ends, terminating in a NEMA Type 
10-50P plug on the supply end. Connectors on the appliance end 
must be provided at the point the power supply cord enters the 
appliance. This uses a 3-wire receptacle of NEMA Type 10-50R.

Range Rating*

Specified Rating of 
Power Supply Cord Kit 
and Circuit Protection

120/240 Volts

120/208 Volts

Amps

8.0 - 16.5 KW
16.6 - 22.5 KW

6.0 - 12.5 KW
12.6 - 18.5 KW

40 or 50**
50

4-wire receptacle (14-50R)

3-wire receptacle (10-50R)

Summary of Contents for W10459122A

Page 1: ...NTS 3 Tools and Parts 3 Location Requirements 3 Electrical Requirements 5 INSTALLATION INSTRUCTIONS 6 Unpack Range 6 Install Anti Tip Bracket 6 Electrical Connection 7 Verify Anti Tip Bracket Is Installed and Engaged 11 Level Range 12 Complete Installation 12 Check Operation 12 W10459122A IMPORTANT Save for local electrical inspector s use ...

Page 2: ... the safety alert symbol and either the word DANGER or WARNING These words mean follow instructions instructions DANGER WARNING Tip Over Hazard A child or adult can tip the range and be killed Install anti tip bracket to floor or wall per installation instructions Slide range back so rear range foot is engaged in the slot of the anti tip bracket Re engage anti tip bracket if range is moved Do not ...

Page 3: ...dimensions are minimum clearances The floor anti tip bracket must be installed To install the anti tip bracket shipped with the range see Install Anti Tip Bracket section Grounded electrical supply is required See the Electrical Requirements section Contact a qualified floor covering installer to check that the floor covering can withstand at least 200 F 93 C Use an insulated pad or 0 64 cm plywoo...

Page 4: ...t less than 0 64 cm flame retardant millboard covered with not less than No 28 MSG sheet steel 0 015 0 4 mm stainless steel 0 024 0 6 mm aluminum or 0 020 0 5 mm copper 30 76 2 cm minimum clearance between the top of the cooking platform and the bottom of an uncovered wood or metal cabinet A 36 91 4 cm B 19 49 5 cm C 24 62 2 cm D 42 106 7 cm A B C D A 18 45 7 cm min clearance upper side cabinet to...

Page 5: ...allic sheathed copper or aluminum cable See the Electrical Connection section Allow 2 to 3 ft 61 0 cm to 91 4 cm of slack in the line so that the range can be moved if servicing is ever necessary A UL listed conduit connector must be provided at each end of the power supply cable at the range and at the junction box Wire sizes and connections must conform with the rating of the range 40 amps The w...

Page 6: ...he anti tip bracket from where it is attached inside the oven with a wire tie 2 Determine which mounting method to use floor or wall If you have a stone or masonry floor you can use the wall mounting method If you are installing the range in a mobile home you must secure the range to the floor 3 Determine and mark centerline of the cutout space The mounting can be installed on either the left side...

Page 7: ... and toward you to remove cover 3 Add strain relief Style 1 Power supply cord strain relief Assemble a UL listed strain relief in the opening Feed the power supply cord through the strain relief on the cord conduit plate on bottom of range Allow enough slack to easily attach the wiring to the terminal block Rear position Front position Diagonal 2 options WARNING Electrical Shock Hazard Disconnect ...

Page 8: ...od for New branch circuit installations 1996 NEC Mobile homes Recreational vehicles In an area where local codes prohibit grounding through the neutral 1 Part of metal ground strap must be cut out and removed A Large opening B Small opening A Small opening B Large opening A Small opening B Large opening A Removable retaining nut small opening B Conduit connector C Large opening A B A B A B A B C I...

Page 9: ...his method only if local codes permit connecting chassis ground conductor to neutral wire of power supply cord 1 Feed the power supply cord through the strain relief on the cord conduit plate on bottom of range Allow enough slack to easily attach the wiring to the terminal block 2 Use nut driver to connect the neutral white wire to the center terminal block post with one of the 10 32 hex nuts 3 Co...

Page 10: ...red wires Loosen do not remove the setscrew on the front of the terminal lug and insert exposed wire end through bottom of terminal lugs Securely tighten setscrew to torque as shown in the following Bare Wire Torque Specifications chart Bare Wire Torque Specifications Attaching terminal lugs to the terminal block 20 lbs in 2 3 N m 5 Use Phillips screwdriver to connect the bare green ground wire to...

Page 11: ...d grasp the lower right or left side of the control panel as shown NOTE If your countertop is mounted with a backsplash it may be necessary to grasp the range higher than is shown in the illustration 2 Slowly attempt to tilt the range forward If you encounter immediate resistance the range foot is engaged in the anti tip bracket 3 If the rear of the range lifts more than 1 3 cm off the floor witho...

Page 12: ...ction NOTE Range must be level for satisfactory baking performance CompleteInstallation 1 Check that all parts are now installed If there is an extra part go back through the steps to see which step was skipped 2 Check that you have all of your tools 3 Dispose of recycle all packaging materials 4 Check that the range is level See Level Range 5 Use a mild solution of liquid household cleaner and wa...

Reviews: