background image

-

19

-

Troubleshooting

Operation problems are often due to minor causes, please check and refer to the following chart before 

contacting the service. This may save time and unnecessary expenses.

Trouble

Analysis

Air conditioner does 

not operate

•  The power supply cord is unplugged. Plug into a grounded outlet. See “Electrical Requirements.”

•  A household fuse has blown, or a circuit breaker has tripped. Replace the fuse, or reset the circuit 

breaker. See “Electrical Requirements.”

•  The On/Off button has not been pressed. Press ON/OFF.

•  The local power has failed. Wait for power to be restored.

•  Time-delay fuse or circuit breaker of the wrong capacity is being used. Replace with a time delay 

fuse or circuit breaker of the correct capacity. See “Electrical Requirements.”

Air conditioner blows 

fuses or trips circuit 

breakers

•  Too many appliances are being used on the same circuit. Unplug or relocate appliances that share 

the same circuit.

•  You are trying to restart the air conditioner too soon after turning off air conditioner. Wait at least 

3 minutes after turning off air conditioner before trying to restart it.

•  You have changed modes. Wait at least 3 minutes after turning off air conditioner before trying to 

restart the appliance.

Air conditioner seems 

to run too much

•  Is there a door or window open? Keep doors and windows closed.

•  In cooling mode: the air conditioner is in a heavily occupied room, or heat producing appliances 

are in use in the room. Use exhaust vent fans while cooking or bathing and try not to use heat 

producing appliances during the hottest part of the day. Local air conditioners are designed 

as supplemental cooling to local areas within a room. A higher capacity air conditioner may be 

required, depending on the size of the room being cooled.

Air conditioner runs for 

a short time only, but 

room is not cool or hot

•   Set temperature is close to room temperature. Lower or Higher set temperature.  

See “Operating mode description”.

Display error code

•  If the unit display error code E5, it is water full in the unit, you should drain the water,  

see “Draining the air conditioner”. After draining, you can operate the unit.

•  If the unit display error code EI/E2/E3/E6/E7/EA, please contact customer service.

Air conditioner runs, 

but does not cool/hot

•  The filter is dirty or obstructed by debris. Clean the filter.

•  Air outlet is blocked. Clear air outlet.

•  The setting temperature is not compatible. In cooling mode: set temperature is too high.  

Lower set temperature.

Air conditioner cycles 

on and off too much

•  The air conditioner is not properly sized for your room. Check the cooling capabilities of your local 

air conditioner. Local air conditioners are designed as supplemental cooling to local areas within a 

room.

•  The filter is dirty or obstructed by debris. Clean the filter.

•  In cooling mode there is excessive heat or moisture (open container cooking, showers, etc.) in 

the room. Use a fan to exhaust heat or moisture from the room. Try not to use heat producing 

appliances during the hottest part of the day. 

•  The louvers are blocked. Install the air conditioner in a location where the louvers are free from 

curtains, blinds, furniture, etc.

•  The outside temperature is below 18°C. Do not try to operate your air conditioner in the cooling 

mode when the outside temperature is below I8°C.

Note: If the problems still have, turn off the appliance and disconnect from power supply, then contact the 

nearest Whirlpool Authorized Service Center. Do not attempt to move, repair, disassemble, or modify the 

appliance by yourself.

Summary of Contents for PACHW2900CO

Page 1: ...Instructions for use ...

Page 2: ......

Page 3: ... 3 PACHW2900CO ENGLISH Instructions for use Page 4 ...

Page 4: ...ppliance unless continuously supervised Children from 8years old and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge can use this appliance only if they are supervised or have been given instructions on safe use and understand the hazards involved Children must not play with the appliance Cleaning and user maintenance must not be carried o...

Page 5: ...he event of problems contact the dealer or your nearest After sales Service Once installed packaging waste plastic styrofoam parts etc must be stored out of reach of children risk of suffocation The appliance must be disconnected from all remote power supply before any installation operation risk of electric shock During installation make sure the appliance does not damage the power cable risk of ...

Page 6: ...rdance with national wiring regulations Model 9K Required capacity of circuit breaker 16A Fuse Type T3 15A 250VAC CLEANING AND MAINTENANCE WARNING Ensure that the appliance is switched off and disconnected from the power supply before performing any maintenance operation never use steam cleaning equipment risk of electric shock DISPOSAL OF PACKAGING MATERIALS The packaging material is 100 recyclab...

Page 7: ...ic heater Do not pierce or burn Be aware that the refrigerants may not contain an odor Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry accredited assessment authority which authorizes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification Servicing s...

Page 8: ...e atmospheres Ensure that hte leak detection equipment being used is suitable for use with flammable refrigerants i e non sparking adequately sealed or intrinsically safe 6 5 Presence of fire extinguisher If any hot work is to be conducted on the refrigerating equipment or any associated partsappropriate fire extinguishing equipment shall be avalaible to hand Have a dry powder or CO2 fire extingui...

Page 9: ...lt with if the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall be reported to the owner of the equipment so all parts are advised Initial safety checks shall include That capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking That there no live electrical components and w...

Page 10: ...nsitivity may not be adequate or may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of ga...

Page 11: ...ith OFN The system shall be leak tested on completion of charging but prior to commissioning A follow up leak test shall be carried out prior to leaving the site 13 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the...

Page 12: ...free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recover...

Page 13: ... before restarting If a button is pressed during this time the compressor will not restart for another 3 to 5 minutes In Cooling or Dry mode the compressor and condenser fan will stop when the room temperature reaches the set temperature In Fan Only mode the temperature can NOT be set Below operation modes can only be set by remote controller In the event of a power failure your air conditioner wi...

Page 14: ...replaced in the remote controller the remote controller pre set at Heat Pump mode The heat pump AC remote controller can be used to control the cool only AC models The remote control will operate the air conditioner at a distance of up to 7m Use RC to control the appliance To operate the appliance by remote control point the remote control at the receiving device on the indoor unit to ensure recei...

Page 15: ...l Around U function When you press this button remote control transmits the actual room temperature around it to the indoor unit and the appliance will operate according this temperature to let you feel more comfortable 10 TIMER BUTTON Used to set or cancel the timer on operation Used to set or cancel the timer off operation With the product turned off consumer must select the Mode Fan speed and t...

Page 16: ...ely before replacing to ensure maximum efficiency 6 Reattach the air filter to the filter panel door 7 Reinstall filter panel door 8 Press ON OFF to start the air conditioner Cleaning the Outside 1 Unplug air conditioner or disconnect from power 2 Remove the air filter and clean separately See Cleaning the Air Filter 3 Wipe outside of the air conditioner with a soft damp cloth 4 Plug in air condit...

Page 17: ...window exhaust adapter into the flexible exhaust hose both the coupling and window exhaust adapter have integrai clips that snap onto the hose 3 lnsert the coupling into the slot on the back of the air conditioner 4 Slide down to lock the hose into place 5 Confirm the hose is locked in place before operating coupling flexible exhaust hose windows exhaust adapter exhaust hose assembly A A Flexible ...

Page 18: ...dow Kit are available online and are compatible with any window and sliding doors in aluminun wood and PVC Electrical Requirements The local air conditioner should be connected to a 220 240V 50Hz 20 amp fused grounded outlet The use of a time delay fuse or time delay circuit breaker is recommended All wiring must comply with local and national electrical regulations and be installed by a qualified...

Page 19: ...n a room A higher capacity air conditioner may be required depending on the size of the room being cooled Air conditioner runs for a short time only but room is not cool or hot Set temperature is close to room temperature Lower or Higher set temperature See Operating mode description Display error code If the unit display error code E5 it is water full in the unit you should drain the water see Dr...

Page 20: ... Service on service sticker which is located on the side or on the bottom of the indoor unit The service number can also be found in the warranty booklet your full address your telephone number If repair work has to be carried out contact the Customer Care Centre Use of original spare parts and a proper repair is guarenteed You will need to present the original invoice Failure to comply with these...

Reviews: